Download G / E-Series Motor Protection Relay Product Features Specifications

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Electric power system wikipedia , lookup

Electromagnetic compatibility wikipedia , lookup

Heterodyne wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Power inverter wikipedia , lookup

Stepper motor wikipedia , lookup

Power engineering wikipedia , lookup

Bode plot wikipedia , lookup

Electrical ballast wikipedia , lookup

Mercury-arc valve wikipedia , lookup

History of electric power transmission wikipedia , lookup

Ohm's law wikipedia , lookup

Chirp spectrum wikipedia , lookup

Rectifier wikipedia , lookup

Current source wikipedia , lookup

Electrical substation wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Portable appliance testing wikipedia , lookup

Utility frequency wikipedia , lookup

Protective relay wikipedia , lookup

TRIAC wikipedia , lookup

Islanding wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Opto-isolator wikipedia , lookup

Buck converter wikipedia , lookup

Ground (electricity) wikipedia , lookup

Surge protector wikipedia , lookup

Power electronics wikipedia , lookup

Distribution management system wikipedia , lookup

Voltage optimisation wikipedia , lookup

Stray voltage wikipedia , lookup

Three-phase electric power wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Mains electricity wikipedia , lookup

Alternating current wikipedia , lookup

Earthing system wikipedia , lookup

Transcript
G / E-Series
Motor Protection Relay
Product Features
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
Din sized enclosure : 96 x 96 x 85mm
LED indication for relay status
Seperate 7 segment window with high brightness red LED display for values and its corresponding
parameters .
Auto / Manual Operation
Resetting facility at front panel is available in manual mode
Type of fault displayed through 7 segment display during unhealthy condition .
Trip delay time can be set indivisually for each parameter .
Parameters can be bypassed as per users choice
Relay can be configured to have NO or NC status during healthy condition .
Monitors and trips the load on occurance of any below mentioned fault condition aftera preset time
delay .1.Phase failure 2. Phase sequence 3.Phase unbalance 4.Under and Over Voltage 5. Under and
Over Current 6.Under and Over frequency 7.earth leakage c
User settable In-rush.
Display all the 3 phase voltages(Line to Line and Line to Neutral)3 phase currrents,frequency in a
scrolling fashion during healthy condition .
User settable earth leakage limits.
CT primary can be programmed up to 2500 in steps of 5. CT secondary will be factory set for 5.
Display the type of fault in manual mode till manual key is pressed.
Specifications
Model
MPR-E1
Function
Phase Unbalance, Phase Reversal, Phase Failure, Under & Over Voltage, Under & Over Current, Under & Over
Frequency Monitor and Control, Earth leakage protection
Rated supply voltage
415V AC, 3 phase, 4 wire
Rated frequency
50Hz ± 10%
Power consumption
5VA / 1W
Input Current
Current Input (AR,AY,AB) Ib=5A
Voltage
± 4V of display value
Current
± 5% of Ib ± 1 digit (Ib=5A)
Frequency
± 2% of FS ± 1 digit
Trip time
± 1% of set delay ± 2 sec
Earth leakage current
± 500mA of setting accuracy
Trip setting
Phase Unbalance : 1 to 20% (Adj.)
Under Voltage : 5 to 100V AC
Over Voltage : 5 to 100V AC
Over Current : 105% to 800%
Under Current : 20%* to 95%
Over Frequency : 2 to 5Hz
Under Frequency : 2 to 5Hz
Earth leakage Current sensitivity range : 1 to 8A
Minimum sensing current*
0.5A
Maximum setting current
5A (Above 5A > Ext. CT can be used, CT setting max. 2500 / 5 Amp in steps of 5)
Trip time delay
1 to 250 secs settable for UB, OV, UV, OC, UC
Earth leakage trip time delay
5 sec Earth leakage
Phase failure trip time delay
< 5 sec
Phase reverse trip time delay
Instantaneous
Frequency trip time delay
Instantaneous
Recovery time
2 sec Min
Power On delay
10 sec Max.
Inrush current delay
1 to 60sec Settable
Mode of Operation
Auto / Manual
Core Balance Current Transformer Type Toriodal core
Control Output
1 c/o rated for 10A @ 250V AC / 28V DC resistive load
Recovery time
2 sec min
Ambient temperature
Operation: -100C to +550C, Storage: -250C to +800C
Humidity
Max. 85% RH @ 400C
Service life (under no load)
106 operations minimum
Electrical life (under full load)
105 operations minimum
Rated frequency of operation
1800 ± 5% operations per hour max
Insulation resistance
>100M ohms @ 500V DC
Model
MPR-E1
Di-electrical strength
1. 2.5KV AC, 50Hz for 1minute. (Between current carrying and non-current carrying parts).
2. 1.5KV AC, 50Hz for 1minute. (Between contacts and control circuit).
3. 750V AC, 50Hz for 1minute. (Between non-continuous contacts of the relay).
Electrical connection
Screw type terminals with self lifting clamps
Mode of operation
Manual / Auto
CBCT Size internal Diameter
Circular 75 / 100 mm
Dimension (over-all)
96 x 96 x 97.5mm (W x H x D)
* Applicable for more than 2.5 Amps nominal current
Connections
Dimensions
Accessories
Instruction Manual -----1No. RC Filter -----1No.
Hints On Correct Use
Tools and Fasteners Kindly use star – type screw driver for tightening the screws.
NOTE: Installation should include a disconnecting device, like switch or circuit breaker, with clear ON/OFF markings, to turn-off the auxiliary
supply (control power).The disconnecting device should be within the reach of the equipment and the operator
Caution
●
●
●
●
●
●
●
●
●
●
●
Apply appropriate personal protective equipment(PPE) and follow safety work practices
Only qualified electrical workers should install this equipment. Such work should be performed only after reading this entire set of instructions.
If the equipment is not used in the manner specified by the manufacturer, the protection provided by the equipment may be impaired.
NEVER work alone.
Turn OFF all power supplying the energy meter and the equipment in which it is installed before working on it.
The successful operation of this equipment depends upon proper handling, installation and operation. Neglecting fundamental installation
requirements may lead to personal injury as well as damage to electrical equipment or other property.
NEVER bypass external fusing.
NEVER apply the voltages at Program Lock and Auto Reset terminals.
Before performing Dielectric or Megger testing on any equipment in which the monitoring device is installed, disconnect all the input and
output wires to the monitoring device. High voltage testing may damage electronic components contained in the monitor
The monitoring device should be installed in a suitable electrical enclosure.
EAPL is not responsible for any consequential damages arising out of use of our products, though the technology is cautiously chosen and
implemented like any other well designed good electric device.