Download STP 3 & 4 2.12 Station Electrical Systems

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Ohm's law wikipedia , lookup

Power inverter wikipedia , lookup

Electrification wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Electric power system wikipedia , lookup

Three-phase electric power wikipedia , lookup

Electronic engineering wikipedia , lookup

Electrical engineering wikipedia , lookup

Electromagnetic compatibility wikipedia , lookup

Islanding wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Rectifier wikipedia , lookup

Buck converter wikipedia , lookup

Portable appliance testing wikipedia , lookup

Power MOSFET wikipedia , lookup

Circuit breaker wikipedia , lookup

Power electronics wikipedia , lookup

Metadyne wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Fault tolerance wikipedia , lookup

Ground (electricity) wikipedia , lookup

Distribution management system wikipedia , lookup

History of electric power transmission wikipedia , lookup

Opto-isolator wikipedia , lookup

Power engineering wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Surge protector wikipedia , lookup

Stray voltage wikipedia , lookup

Alternating current wikipedia , lookup

Earthing system wikipedia , lookup

Voltage optimisation wikipedia , lookup

AC adapter wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Electrical substation wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
Rev. 03
STP 3 & 4
Tier 1
2.12 Station Electrical Systems
The information in this section of the reference ABWR DCD, including all subsections,
figures and tables, is incorporated by reference with the following departures.
STD DEP T1 2.12-1 (Tables 2.12.1, 2.12.12, 2.12.14 and 2.12.15)
STD DEP T1 2.12-2 (Figure 2.12.15)
2.12.1 Electrical Power Distribution System
Design Description
STD DEP T1 2.12-1
EPD System interrupting devices (circuit breakers and fuses) are coordinated to the
maximum extent possible, so that the circuit interrupter closest to the fault opens
before other devices.
2.12.12
Direct Current Power Supply
Design Description
STD DEP T1 2.12-1
Class 1E DC electrical distribution system circuit interrupting devices (circuit breakers
and fuses) are coordinated to the maximum extent possible, so that the circuit
interrupter closest to the fault opens before other devices.
2.12.14 Vital AC Power Supply
Design Description
STD DEP T1 2.12-1
Class 1E Vital AC Power Supply system interrupting devices (circuit breakers and
fuses) are coordinated to the maximum extent possible, so that the circuit interrupter
closest to the fault opens before other devices.
Station Electrical Systems
2.12-1
Rev. 03
STP 3 & 4
2.12.15
Tier 1
Instrument and Control Power Supply
Design Description
STD DEP T1 2.12-2
The Class 1E Instrument and Control Power Supply consists of three four divisions
(Division I, II, and III, and IV) of interruptible power supplies with their respective
distribution panels. Each Class 1E power supply provides interruptible, regulated AC
power to Class 1E circuits which do not require continuity of power during a loss of
preferred power (LOPP).
STD DEP T1 2.12-1
Class 1E Instrument and Control Power Supply system interrupting devices (circuit
breakers and fuses) are coordinated to the maximum extent possible, so that the circuit
interrupter closest to the fault opens before other devices.
2.12-2
Station Electrical Systems
c. System preoperational and Startup
tests will be conducted of the asbuilt Class 1E EPD System.
a. Analyses for the as-built EPD System
exist and conclude that the analyzed
operating voltage supplied at the
terminals of the Class 1E utilization
equipment is within the utilization
equipment's voltage tolerance limits,
as determined by their nameplate
ratings.
b. Connected Class 1E loads operate at
their analyzed minimum voltage, as
determined by the voltage drop
analyses.
b. Manufacturer's type test reports
exist and conclude that the
operating range is within the tested
voltage range for the Class 1E
electrical equipment.
c. The test voltages from
preoperational test reports are
compared against system voltage
analysis of the as-built Class 1E
EPD system. The results of
comparison conclude that the
available voltage is within the
operating range for the as-installed
equipment.
Rev. 03
b. Tests of the as-built Class 1E EPD
System will be conducted by operating
connected Class 1E loads at their
analyzed minimum voltage.
b. Type tests at manufacturer's shop
will be performed for the operating
voltage range of the Class 1E
electrical equipment.
Acceptance Criteria
Analyses for the as-built EPD System exist
and conclude that, to the maximum
extent possible, the analyzed circuit
interrupter closest to the fault will open
before other devices.
STP 3 & 4
Station Electrical Systems
Table 2.12.1 Electric Power Distribution System
Inspections, Tests, Analyses and Acceptance Criteria
Design Commitment
Inspections, Tests, Analyses
11.
11. Analyses for the as-built EPD System to
11. EPD System interrupting devices (circuit
determine circuit interrupting device
breakers and fuses) are coordinated to the
coordination will be performed.
maximum extent possible, so that the
circuit interrupter closest to the fault opens
before other devices.
22.
22.
22. The EPD System supplies an operating
voltage at the terminals of the Class 1E
a. Analyses for the as-built EPD System
utilization equipment that is within the
to determine voltage drops will be
utilization equipment's voltage tolerance
performed.
limits.
Tier 1
2.12-3
Inspections, Tests, Analyses and Acceptance Criteria
Design Commitment
Inspections, Tests, Analyses
8.
8. Analyses for the as-built Class 1E DC
8. Class 1E DC electrical distribution
electrical distribution system to
system circuit interrupting devices (circuit
determine circuit interrupting device
breakers and fuses) are coordinated to
coordination will be performed.
the maximum extent possible, so that
the circuit interrupter closest to the fault
opens before other devices.
Acceptance Criteria
Analyses for the as-built Class 1E DC
electrical distribution system circuit
interrupting devices exist and conclude
that, to the maximum extent possible,
the analyzed circuit interrupter closest to
the fault will open before other devices.
STP 3 & 4
2.12-4
Table 2.12.12 Direct Current Power Supply
Rev. 03
Tier 1
Station Electrical Systems
Rev. 03
Inspections, Tests, Analyses and Acceptance Criteria
Design Commitment
Inspections, Tests, Analyses
Acceptance Criteria
11.
11.
11. The Class 1E DC electrical distribution
system supplies an operating voltage at
a. Analyses for the as-built Class 1E
a. Analyses for the as-built Class 1E
the terminals of the Class 1E utilization
DC electrical distribution system
DC electrical distribution system to
equipment that is within the utilization
exist and conclude that the analyzed
determine system voltage drops will
equipment's voltage tolerance limits.
operating voltage supplied at the
be performed.
terminals of the Class 1E utilization
equipment is within the utilization
equipment's voltage tolerance limits,
as determined by their nameplate
ratings.
b. Tests of the as-built Class 1E DC
b. Connected as-built Class 1E loads
system will be conducted by
operate at less than or equal to the
operating connected Class 1E loads
minimum allowable battery voltage
at less than or equal to the minimum
and at greater than or equal to the
allowable battery voltage and at
maximum battery charging voltage.
greater than or equal to the
maximum battery charging voltage.
b. Manufacturer's type test reports
b. Type tests at manufacturer's shop
exist and conclude that the
will be performed for the
operating range is within the
operating voltage range of the
tested voltage range for the Class
Class 1E DC electrical equipment.
1E DC electrical equipment.
c. System preoperational tests will
c. The test voltages from
be conducted on the as-built
preoperational test reports are
Class 1E DC system.
compared against system voltage
analysis of the as-built Class 1E
EPD system. The results of
comparison conclude that the
available voltage is within the
operating range for the asinstalled DC equipment.
STP 3 & 4
Station Electrical Systems
Table 2.12.12 Direct Current Power Supply (Continued)
Tier 1
2.12-5
Acceptance Criteria
Analyses for the as-built Class 1E Vital
AC Power Supply system circuit
interrupting devices (circuit breakers and
fuses) coordination exist and conclude
that, to the maximum extent possible,
the analyzed circuit interrupter closest to
the fault will open before other devices.
STP 3 & 4
2.12-6
Table 2.12.14 Vital AC Power Supply
Inspections, Tests, Analyses and Acceptance Criteria
Design Commitment
Inspections, Tests, Analyses
10.
10. Analyses for the as-built Class 1E
10. Class 1E Vital AC Power Supply system
distribution system to determine circuit
interrupting devices (circuit breakers and
interrupting device coordination will be
fuses) are coordinated to the maximum
performed.
extent possible, so that the circuit
interrupter closest to the fault opens
before other devices.
Rev. 03
Tier 1
Station Electrical Systems
Inspections, Tests, Analyses and Acceptance Criteria
Design Commitment
Inspections, Tests, Analyses
9.
9. Analyses for the as-built Class 1E
9. Class 1E Instrument and Control Power
distribution system to determine circuit
Supply system interrupting devices (circuit
interrupting device coordination will be
breakers and fuses) are coordinated to the
performed.
maximum extent possible, so that the
circuit interrupter closest the fault opens
before other devices.
Acceptance Criteria
Analyses for the as-built Class 1E
Instrument and Control Power Supply
system circuit interrupting devices (circuit
breakers and fuses) coordination exist and
conclude that, to the maximum extent
possible, the analyzed circuit interrupter
closest to the fault will open before other
devices.
STP 3 & 4
Station Electrical Systems
Table 2.12.15 2.12-15Instrument and Control Power Supply
Rev. 03
Tier 1
2.12-7
Rev. 03
STP 3 & 4
Tier 1
Figure 2.12.15 Instrument and Control Power Supply
2.12-8
Station Electrical Systems