* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download Table 2
Current source wikipedia , lookup
Immunity-aware programming wikipedia , lookup
Power inverter wikipedia , lookup
Stepper motor wikipedia , lookup
Ground (electricity) wikipedia , lookup
Resistive opto-isolator wikipedia , lookup
Power engineering wikipedia , lookup
Electromagnetic compatibility wikipedia , lookup
Automatic test equipment wikipedia , lookup
Power electronics wikipedia , lookup
Single-wire earth return wikipedia , lookup
Power MOSFET wikipedia , lookup
Buck converter wikipedia , lookup
Portable appliance testing wikipedia , lookup
Surge protector wikipedia , lookup
Voltage regulator wikipedia , lookup
History of electric power transmission wikipedia , lookup
Rectiverter wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Distribution management system wikipedia , lookup
Electrical substation wikipedia , lookup
Opto-isolator wikipedia , lookup
Transformer wikipedia , lookup
Stray voltage wikipedia , lookup
Voltage optimisation wikipedia , lookup
Three-phase electric power wikipedia , lookup
Table 1 (All Classes in 1 Table) This revision combines the Delta and the Wye-Connected Tables from Revision 8 into the new Revision 9 Applied Test From C57.12.00 Table 7 in kV Max Nominal System System Voltage in Voltage kV (V, in kV) Delta Gr Y Induced Test, in kV Dist. & Class I Class 2, >72.5 kV 2V Imp Y 3 One Enhanced Hour 7200 cy Basic Insulation Level, in kV Min. Alternates Neutral BIL, in kV GrY Impedance Distribution and Class I Power Transformers, ≤69 kV Nominal System Voltage 1.5 1.2 10 10 10 1.4 30 45 30 30 3.5 2.5 15 15 15 2.9 45 60 45 45 6.9 5 19 19 19 5.8 60 75 60 60 8.7 75 75 75 75 11 26 26 26 10 75 95 15 34 26 26 17.3 95 110 26 25 50 26 34 28.9 125 150 75 95 38 34.5 70 26 50 39.8 150 200 75 125 48.3 46 95 34 70 53.1 200 250 95 150 72.5 69 140 34 95 79.7 250 350 95 200 120 115 173 34* 95* N/A 105 120 350 450 550 110 250 145 138 207 34* 95* N/A 125 145 450 550 650 166 161 242 34* 95* N/A 145 170 550 650 750 244 230 345 34* 95* N/A 210 240 750 825 900 362 345 518 34* 95* N/A 315 360 1050 1175 550 500 N/A 34* 95* N/A 475 550 1425 1550 765 735 N/A 34* 95* N/A 750 850 1950 2050 800 765 N/A 34* 95* N/A 795 885 1950 2050 17.2 125 400 Class II Power Transformers, > 72.5 kV Nominal System Voltage Notes: 1.* 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 1675 850 110 250 110 350* 110 350* 110* 350* 110* 350* 110* 350* 110* 350* Insulation level to conform with service requirements but never less than the level shown. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated insulation levels. Front-of-wave Impulse levels must be specified prior to design of the transformer. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings. All test levels are line to ground. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for application on ungrounded systems. Minimum Phase-to-Phase Induced test levels for 3 phase Distribution Transformers shall be not less than 2.0 times nominal system voltage, and never less than the applied test level from line to ground. Minimum Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal system voltage, and never less than the applied test level from line to ground. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in accordance with the requirements of the low voltage winding. Voltages greater than Maximum System Voltage shall use the next higher voltage class test levels. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level. Single phase distribution and power transformers and regulating transformers for voltage ratings between terminals of 8.7 kV and below are designed for both Y and Delta connection so that a single line of transformers serves for the higher than needed for their voltage rating. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL of the series windings rather than the rated voltage between terminals. This example shows Table 1 split into two tables by transformer class: Table 1a (Distribution and Class 1) This revision combines the Delta and the Wye-Connected Tables from Revision 8 into the new Revision 9 Max System Voltage (kV) Nominal System Voltage (kV) Applied Test From C57.12.00 Table 7 (kV) Delta Gr Y Induced Test in kV 2V Imp Y 3 Basic Insulation Level (kV) Min. Alternates Neutral BIL (kV) GrY Impedance Distribution Transformers 1.5 1.2 10 10 10 1.4 30 30 30 3.5 2.5 15 15 15 2.9 45 45 45 6.9 5 19 19 19 5.8 60 60 60 11 8.7 26 26 26 10 75 75 75 17.2 15 34 26 26 17.3 95 75 75 26 25 50 26 34 28.9 125 150 75 95 38 34.5 70 26 50 39.8 125 150 75 125 48.3 46 95 34 70 53.1 200 250 200 95 150 72.5 69 140 34 95 79.7 250 350 95 200 Class I Power Transformers, ≤69 kV Nominal System Voltage 1.5 1.2 10 10 10 1.4 30 45 30 30 3.5 2.5 15 15 15 2.9 45 60 45 45 6.9 5 19 19 19 5.8 60 75 60 60 11 8.7 26 26 26 10 75 95 75 75 17.2 15 34 26 26 17.3 95 110 75 75 26 25 50 26 34 28.9 150 75 95 38 34.5 70 26 50 39.8 200 75 125 48.3 46 95 34 70 53.1 200 250 95 150 72.5 69 140 34 95 79.7 250 350 95 200 Notes: 1.* Insulation level to conform with service requirements but never less than the level shown. 15. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated insulation levels. 16. Front-of-wave Impulse levels must be specified prior to design of the transformer. 17. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 18. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings. 19. All test levels are line to ground. 20. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for application on ungrounded systems. 21. Minimum Phase-to-Phase Induced test levels for 3 phase Distribution Transformers shall be not less than 2.0 times nominal system voltage, and never less than the applied test level from line to ground. 22. Minimum Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal system voltage, and never less than the applied test level from line to ground. 23. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in accordance with the requirements of the low voltage winding. 24. Voltages greater than Maximum System Voltage shall use the next higher voltage class test levels. 25. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level. 26. Single phase distribution and power transformers and regulating transformers for voltage ratings between terminals of 8.7 kV and below are designed for both Y and Delta connection so that a single line of transformers serves for the higher than needed for their voltage rating. 27. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL of the series windings rather than the rated voltage between terminals. Table 1b (Class II Transformers) This revision combines the Delta and the Wye-Connected Tables from Revision 8 into the new Revision 9 Applied Test From C57.12.00 Table 7 (kV) Max Nominal System System Voltage Voltage (kV) (kV) Delta Gr Y Imp Y Induced Test (kV) Class 1 ≤69 kV Class 2, >72.5 kV Enhanced One Hour 7200 cy. Basic Insulation Level (kV) Min Alternates Neutral BIL (kV) GrY Impedance 110 250 110 110 250 350* Class II Power Transformers, > 72.5 kV Nominal System Voltage 120 115 173 34* 95* N/A 105 120 350 450 550 145 166 138 161 207 242 34* 34* 95* 95* N/A N/A 125 145 145 170 450 550 550 650 650 750 244 362 230 345 345 518 34* 34* 95* 95* N/A N/A 210 315 240 360 750 1050 825 1175 900 110 110* 350* 350* 550 765 500 735 N/A N/A 34* 34* 95* 95* N/A N/A 475 750 550 850 1425 1950 1550 1675 2050 110* 110* 350* 350* 800 765 N/A 34* 95* N/A 795 885 1950 2050 110* 350* 850 Notes: 1.* Insulation level to conform with service requirements but never less than the level shown. 2. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated insulation levels. 3. Front-of-wave Impulse levels must be specified prior to design of the transformer. 4. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 5. The Insulation levels for Class 1 and Class 2 transformers shall be selected from this table for both the high-voltage and lowvoltage windings. 6. All test levels are line to ground. 7. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for application on ungrounded systems. 8. Minimum Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal system voltage, and never less than the applied test level from line to ground. 9. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in accordance with the requirements of the low voltage winding. 10. Voltages greater than Maximum System Voltage shall use the next higher voltage class test levels. 11. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level. 12. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL of the series windings rather than the rated voltage between terminals. Table 2 High Frequency Test Tables BIL kV Crest 1.2 X 50 μ-sec Chopped Wave kV Crest 1.1*BIL Minimum Time to Flashover, μ-sec Front Of Wave kV Crest Minimum Time to Flashover, μ-sec Switching Impulse kV Crest 0.83*BIL 30 33 1.0 45 60 50 66 1.5 1.5 75 95 83 105 1.5 1.8 165 0.5 110 125 120 138 2.0 2.3 195 220 0.5 0.5 150 200 165 220 3.0 3.0 260 345 0.5 0.5 250 275 3.0 435 0.5 350 450 385 495 3.0 3.0 580 0.58 N/A unless specified 550 650 605 715 3.0 3.0 N/A unless specified N/A unless specified 460 540 750 825 825 900 3.0 3.0 N/A unless specified N/A unless specified 620 685 900 1050 990 1155 3.0 3.0 N/A unless specified N/A unless specified 745 870 1175 1290 3.0 N/A unless specified 975 1300 1430 3.0 N/A unless specified 1080 1425 1550 1570 1705 3.0 3.0 N/A unless specified N/A unless specified 1180 1290 1675 1800 1845 1980 3.0 3.0 N/A unless specified N/A unless specified 1390 1550 1950 2145 3.0 N/A unless specified 1620 2050 2255 3.0 N/A unless specified 1700 280 375 Notes: 1. Front-of-Wave tests must be specified prior to the design of the transformer. 2. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 3. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings. 4. Phase to ground specified Switching impulse levels are not always possible for low voltage windings. Table 1b This revision combines the Delta and the Wye-Connected Tables from Revision 8 into the new Revision 9 Max System Voltage (V) Nominal System Voltage (V) Applied Test From C57.12.00 Table 7 Delta Gr Y Induced Test 2V Imp Y 3 Basic Insulation Level Min. Alternates Neutral BIL GrY Impedance Distribution Transformers 1.5 1.2 10 10 10 1.4 30 30 30 3.5 2.5 15 15 15 2.9 45 45 45 6.9 5 19 19 19 5.8 60 60 60 11 8.7 26 26 26 10 75 75 75 17.2 15 34 26 26 17.3 95 75 75 26 25 50 26 34 28.9 125 150 75 95 38 34.5 70 26 50 39.8 125 150 75 125 48.3 46 95 34 70 53.1 200 250 200 95 150 72.5 69 140 34 95 79.7 250 350 95 200 Class I Power Transformers, < or = 69 kV Nominal System Voltage 1.5 1.2 10 10 10 1.4 30 45 30 30 3.5 2.5 15 15 15 2.9 45 60 45 45 6.9 5 19 19 19 5.8 60 75 60 60 11 8.7 26 26 26 10 75 95 75 75 17.2 15 34 26 26 17.3 95 110 75 75 26 25 50 26 34 28.9 150 75 95 38 34.5 70 26 50 39.8 200 75 125 48.3 46 95 34 70 53.1 200 250 95 150 72.5 69 140 34 95 79.7 250 350 95 200 Notes: 1. Insulation level to conform with service requirements but never less than the level shown. 13. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated insulation levels. 14. Front-of-wave Impulse levels must be specified prior to design of the transformer. 15. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 16. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings. 17. All test levels are line to ground. 18. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for application on ungrounded systems. 19. Minimum Phase-to-Phase Induced test levels for 3 phase Distribution Transformers shall be not less than 2.0 times nominal system voltage, and never less than the applied test level from line to ground. 20. Minimum Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal system voltage, and never less than the applied test level from line to ground. 21. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in accordance with the requirements of the low voltage winding. 22. Voltages greater than Maximum System Voltage shall use the next higher voltage class test levels. 23. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level. 24. Single phase distribution and power transformers and regulating transformers for voltage ratings between terminals of 8.7 kV and below are designed for both Y and Delta connection so that a single line of transformers serves for the higher than needed for their voltage rating. 25. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL of the series windings rather than the rated voltage between terminals. Table 2 High Frequency Test Tables BIL Chopped Wave kV Crest 1.2 X 50 μ-sec Minimum Time to Flashover, μ-sec kV Crest Minimum Time to Flashover, μ-sec Switching Impulse kV Crest 0.83*BIL 30 45 33 50 1.0 1.5 60 75 66 83 1.5 1.5 95 110 105 120 1.8 2.0 165 195 0.5 0.5 125 150 138 165 2.3 3.0 220 260 0.5 0.5 200 220 3.0 345 0.5 250 275 3.0 435 0.5 350 385 3.0 580 0.58 450 550 495 605 3.0 3.0 N/A unless specified N/A unless specified 375 460 650 750 715 825 3.0 3.0 N/A unless specified N/A unless specified 540 620 825 900 900 990 3.0 3.0 N/A unless specified N/A unless specified 685 745 1050 1175 1155 1290 3.0 3.0 N/A unless specified N/A unless specified 870 975 1300 1425 1430 1570 3.0 3.0 N/A unless specified N/A unless specified 1080 1180 1550 1675 1705 1845 3.0 3.0 N/A unless specified N/A unless specified 1290 1390 1950 1950 2145 2145 3.0 3.0 N/A unless specified N/A unless specified 1550 1620 2050 2255 3.0 N/A unless specified 1700 Notes: 1. 5. 6. 7. kV Crest 1.1*BIL Front Of Wave 280 Front-of-Wave tests must be specified prior to the design of the transformer. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings. Phase to ground specified Switching impulse levels are not always possible for low voltage windings.