Download Single-Phase Test Circuit

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Regenerative circuit wikipedia , lookup

Test probe wikipedia , lookup

CMOS wikipedia , lookup

Operational amplifier wikipedia , lookup

Integrating ADC wikipedia , lookup

Josephson voltage standard wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Ohm's law wikipedia , lookup

Valve RF amplifier wikipedia , lookup

RLC circuit wikipedia , lookup

Multimeter wikipedia , lookup

Power electronics wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Automatic test equipment wikipedia , lookup

Current mirror wikipedia , lookup

Schmitt trigger wikipedia , lookup

Power MOSFET wikipedia , lookup

Voltage regulator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Opto-isolator wikipedia , lookup

Surge protector wikipedia , lookup

Network analysis (electrical circuits) wikipedia , lookup

Rectiverter wikipedia , lookup

Transcript
10.6.5 Alternate circuit for high voltage delta-connected windings
For two-winding transformers with delta-connected high voltage windings, a single phase induced test executed three times may be used in lieu of the
applied test on the HV winding. Each phase is tested separately at the required applied voltage level. Each HV terminal is therefore tested twice at the full
level. The procedure is as follows:
Short and ground the low voltage winding of the tested phase.
Both HV terminals of the tested phase must remain open during the test. The third HV terminal must be grounded.
Apply a symmetrical (plus-minus) ac voltage to the ungrounded low voltage terminals. The voltage should be started at one quarter or less of the full value
and be brought up gradually to full value. After being held for the time specified in 10.6.1, it should be reduced gradually before the circuit is opened. The
test must be made at low frequency (< 500 Hz), but at a frequency high enough to avoid core saturation.
Figure xx below shows the circuit to be used.
Figure xx: Alternate induced test circuit used in lieu of applied voltage test for two-winding transformers with delta-connected HV winding.
This circuit is particularly recommended for cases where measurements of partial discharges are specified during the test. An applied test with pd-free supply
may be particularly difficult to achieve at very high voltages.