Download section 262200 - low-voltage transformers

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Islanding wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power inverter wikipedia , lookup

Buck converter wikipedia , lookup

Rectifier wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Stray voltage wikipedia , lookup

Rectiverter wikipedia , lookup

Distribution management system wikipedia , lookup

Power engineering wikipedia , lookup

Voltage optimisation wikipedia , lookup

Single-wire earth return wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Resonant inductive coupling wikipedia , lookup

Electrical substation wikipedia , lookup

Opto-isolator wikipedia , lookup

History of electric power transmission wikipedia , lookup

Mains electricity wikipedia , lookup

Three-phase electric power wikipedia , lookup

Alternating current wikipedia , lookup

Transformer wikipedia , lookup

Transcript
This master should be used by designers working on Port of Portland construction projects and by designers working for PDX
tenants (“Tenants”). Usage notes highlight a few specific editing choices, however the entire section should be evaluated and
edited to fit specific project needs.
SECTION 262200 - LOW-VOLTAGE TRANSFORMERS
PART 1 - GENERAL
1.1
DESCRIPTION
Choose power type from bracketed items in A.
A.
This section describes dry type transformers to provide [240V/120V single phase][208V/120V
three-phase wye] power from the 480V/277V three-phase wye system.
B.
Size transformers as shown on the drawings.
1.2
REFERENCES
A.
NEMA: National Electrical Manufacturers Association
B.
UL: Underwriters Laboratories
PART 2 - PRODUCTS
2.1
MATERIALS
A.
Low Voltage Transformers:
1.
Enclosed and ventilated, air-cooled type, Class H insulation, designed for 115ºC
temperature rise above 40ºC ambient temperature at full load continuous operation.
Equip with two 2 1/2 percent FCAN taps and four 2 1/2 percent FCBN taps. Maximum
sound level shall be NEMA standard with isolation dampers between the core and coil
assembly and case.
2.
Case shall be totally enclosed with louvers to prevent entry of foreign objects into the
interior, and shall be manufactured in accordance with all NEMA and UL-approved
standards.
3.
Transformers shall meet TP1 energy efficiencies.
4.
Acceptable manufacturers are Square D, G.E., Siemens, ACME, SOLA/Hevi-Duty,
or equal.
5/10/2017
D:\582728236.DOC
LOW-VOLTAGE TRANSFORMERS
262200-1
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Install the low voltage transformer with flexible conduit connections to housing. Make all cable
and ground wire connections.
B.
In general, transformers shall be wall-mounted. When necessary to wall or trapeze mount,
securely anchor to structure using a safety factor of 4.
C.
Install with sound isolating vibration dampers between the transformer enclosure and the hanger
or building structure.
3.2
FIELD QUALITY CONTROL
A.
Check for damage and tighten connections prior to energizing transformer.
B.
Measure primary and secondary voltages and make appropriate tap adjustments.
C.
Adjust primary taps so that secondary voltage is within 2 1/2 percent above nominal voltage
with transformer unloaded.
END OF SECTION 262200
LOW-VOLTAGE TRANSFORMERS
262200-2
5/10/2017
D:\582728236.DOC