Download SECTION 16322D - MEDIUM VOLTAGE TRANSFORMERS A

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power engineering wikipedia , lookup

Stray voltage wikipedia , lookup

Rectifier wikipedia , lookup

Buck converter wikipedia , lookup

Voltage optimisation wikipedia , lookup

Mains electricity wikipedia , lookup

Opto-isolator wikipedia , lookup

Electrical substation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Metadyne wikipedia , lookup

Three-phase electric power wikipedia , lookup

History of electric power transmission wikipedia , lookup

Resonant inductive coupling wikipedia , lookup

Alternating current wikipedia , lookup

Transformer wikipedia , lookup

Transcript
Design Guidelines and Standards Manual
University of Cincinnati
SECTION 16322D - MEDIUM VOLTAGE TRANSFORMERS
A.
LOCATION OF TRANSFORMERS in general, shall be where removal can be
accomplished, and is relatively easy. Transformers located outdoors shall be
located where transformer can be loaded onto a truck. This may require analyzing
site and if necessary, construction of a service road.
B.
TYPES: Outdoor transformers may be pad mounted with approved (non-PCB)
fluid such as R-Temp. Indoor transformers shall be dry type of the barrel design.
Cast type, are not acceptable.
C.
WINDINGS: Primary winding shall be connected Delta and secondary winding
shall be connected Wye and grounded. Primary winding of oil insulated
transformers shall be equipped with no load tap changing switch with two 2-1/2
percent taps above and four 2-1/2 percent below rated voltage. Primary windings
of indoor dry type transformers shall be furnished with two 2-1/2 percent taps
above and four 2-1/2 percent taps below nominal primary voltage, changeable by
transformer jumpers. All windings copper. Indoor dry type transformers shall
have temperature sensor wells integral with windings. The main transformer shall
be equipped with a transformer monitor panel to indicate transformer coil
temperature, hottest coil temperature, fan status, and include alarm and emergency
shutdown relays. The monitor panel shall have the capability of transmitting this
information to PMCS system.
D.
PRIMARY SWITCH AND FUSES: Primary of transformer shall be fuse
protected. Transformer shall also have a gang operated switch for isolation from
the primary circuit. Switch and fuse combination shall be load break type.
Interrupting rating shall exceed the available system short circuit current, no
exceptions. Switches shall be rated at 600 amperes continuous duty, minimum.
E.
For liquid insulated transformers, provide a temperature gauge equipped with
adjustable electrical contact points which can be used for a high temperature
alarm.
F.
Provide for a “megger” test to verify dielectric strength and a TTR test for proper
voltage. Arrange through the University Architect that Facilities Management
(Electric Shop) witness test and provide copies of test results to University
Architect prior to transformer being energized.
G.
Transformers, 15KV Class, shall have a BIL rating of 95KV on the primary side.
Transformer shall have distribution class lightning protection on the primary side.
H.
Transformer shall have minimum K rating of 4.
MEDIUM VOLTAGE TRANSFORMERS
16322 - D1
9/16/96
Design Guidelines and Standards Manual
University of Cincinnati
I.
All transformer rooms shall be ventilated with outdoor air and temperature
controlled.
END OF SECTION
MEDIUM VOLTAGE TRANSFORMERS
16322 - D2
9/16/96