Download Ferroresonance in Voltage Transformer (VT)

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Transistor wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Flexible electronics wikipedia , lookup

Power engineering wikipedia , lookup

Electromagnetic compatibility wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Stepper motor wikipedia , lookup

Capacitor wikipedia , lookup

Power inverter wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Islanding wikipedia , lookup

Triode wikipedia , lookup

History of electric power transmission wikipedia , lookup

Electrical substation wikipedia , lookup

Electrical ballast wikipedia , lookup

Voltage regulator wikipedia , lookup

Rectifier wikipedia , lookup

Distribution management system wikipedia , lookup

P–n diode wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Ohm's law wikipedia , lookup

Three-phase electric power wikipedia , lookup

Voltage optimisation wikipedia , lookup

Transformer wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Opto-isolator wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Stray voltage wikipedia , lookup

Earthing system wikipedia , lookup

Current source wikipedia , lookup

Power MOSFET wikipedia , lookup

Buck converter wikipedia , lookup

Ground (electricity) wikipedia , lookup

Current mirror wikipedia , lookup

RLC circuit wikipedia , lookup

Resonant inductive coupling wikipedia , lookup

Surge protector wikipedia , lookup

Mains electricity wikipedia , lookup

Alternating current wikipedia , lookup

Transcript
Ferroresonance in Voltage Transformer (VT) Circuits
October 1, 1997 (corrected)
In the last couple of months we have received several different questions as to what is ferroresonance in
a VT circuit, when does it occur and how do we protect against it.
Ferroresonance can occur when the primary of a voltage transformer is connected line to ground in an
ungrounded circuit. This configuration results in the magnetizing reactance of the VT being in a parallel
loop with the coupling capacitance to ground of the system (see Figure 1).
Figure 1
The coupling capacitance is primarily made up of the capacitance of the system dielectric between the
phase conductor and ground. The value of the voltage transformers magnetizing reactance varies as a
function of the amount of flux going through the iron. This results in an LC circuit and requires only a
simple voltage transient to excite the resonant frequency. Once the ringing begins the voltage across the
individual components of magnetizing reactance and coupling capacitance can reach high levels and the
ringing can go undamped if the voltage transformer is lightly loaded. The loading of the VT has a very
important part to play in limiting the magnitude of current in the oscillation circuit since the resistance of
the load will act as a current divider and send a portion of the current to ground. This graph from the
IEEE Red Book shows the impact of load on the magnitude of the current in the ringing circuit (see
Figure 2).
Powell Industries, Inc.
PO Box 12818
Houston, TX • 77217
©2005 Powell Industries, Inc. • All rights reserved.
Tel: 713.944.6900 • Fax: 713.947.4453
www.powellind.com
[email protected]
Ferroresonance in Voltage Transformer (VT) Circuits
page 2
Figure 2
During the oscillation, the current can drive the magnetizing force to saturate the VT. When the VT is
saturated, the reactance to ground will diminish and the current to ground through the primary of the VT
will go high. At the end of the sinusoid the VT will drop out of saturation, but with a low loss system the
stored charge remains relatively high across the system coupling capacitance. As the polarity of the
sinusoid changes the process repeats itself. The current surges, through the VT primary during the
periods of saturation, can be much greater than full load rating but not approaching fault current levels,
making it very difficult for the fuses on the primary of the VT to interrupt. Thus current surging may result
in a blown VT fuse but often results in a shorted VT.
To keep the resonance magnitude down, the secondary side of the VT circuit can be artificially loaded.
There are two common methods of loading used to minimize the effects of ferroresonance. One is to
install the VT’s with their secondary windings connected in a broken delta and with a resistor completing
the broken delta circuit. The watts of the resistor should equal 50% of the VA of a single VT.
Powell Industries, Inc.
PO Box 12818
Houston, TX • 77217
©2005 Powell Industries, Inc. • All rights reserved.
Tel: 713.944.6900 • Fax: 713.947.4453
www.powellind.com
[email protected]
Ferroresonance in Voltage Transformer (VT) Circuits
page 3
The second and most popular method is to put a resistor across the secondary of each VT. The rule of
thumb from several old references is that the resistive loading should range between the VA required to
excite the core at no load and 50% of the thermal rating of the VT. For specific VT’s, the manufacturer
can recommend a precise value of resistance.
Due to the varying frequency of the transient and the magnetizing reactance this is not a problem that
occurs in every system or even every time a voltage transformer is connected to ground on an
ungrounded system. If the resonant frequency of the LC circuit is excited the swamping resistor will
dampen the ringing to prevent long term effects.
If we can be of help on this or any other topic please don't hesitate to call.