Download 1C.2.1—Voltage Level and Range

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Electric power system wikipedia , lookup

War of the currents wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Stepper motor wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Decibel wikipedia , lookup

Ground (electricity) wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Power inverter wikipedia , lookup

Electrical ballast wikipedia , lookup

Current source wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Ohm's law wikipedia , lookup

Metadyne wikipedia , lookup

Islanding wikipedia , lookup

Power engineering wikipedia , lookup

Three-phase electric power wikipedia , lookup

Rectifier wikipedia , lookup

Schmitt trigger wikipedia , lookup

Electrical substation wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Triode wikipedia , lookup

Power MOSFET wikipedia , lookup

Power electronics wikipedia , lookup

Distribution management system wikipedia , lookup

Buck converter wikipedia , lookup

History of electric power transmission wikipedia , lookup

Opto-isolator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Voltage regulator wikipedia , lookup

Surge protector wikipedia , lookup

Alternating current wikipedia , lookup

Stray voltage wikipedia , lookup

Voltage optimisation wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
Engineering Handbook
Volume 1—General
Part C—Power Quality
Section 2.1—Voltage Level and Range
1C.2.1—Voltage Level and Range
1
Scope
The purpose of this document is to state PacifiCorp’s ranges for service voltage.
Recommended ranges of utilization voltages are also given. The voltage levels presented
apply to sustained or steady-state voltages. These levels do not apply to momentary voltage
excursions that may result from such causes as switching operations, motors starting,
fluctuating loads, and so forth.
2
General
For any specific nominal voltage, the operating voltage(s) on a power system will differ from
the nominal value due to voltage drop in the system as well as changes in the system’s
operating condition. It is important that the design and operation of power systems and
accompanying utilization equipment be coordinated with respect to voltage variations, to
ensure that the performance of customers’ equipment will be satisfactory throughout a range
of actual voltages.
PacifiCorp’s voltage ranges are based on ANSI C84.1, Voltage Ratings for Electric Power
Systems and Equipment (60Hz). This document is intended to reflect the requirements of the
current ANSI C84.1 standard. ANSI C84.1 was prepared by the National Electrical
Manufacturers Association, with participation by the Edison Electric Institute and others.
(If statements or references in this document vary from national standards, the national
standards shall apply.)
Some of the stated purposes of ANSI C84.1 are:
1.
To promote standardization of nominal system voltages and ranges of voltage
variations for operating systems
2.
To promote standardization of equipment voltage ratings and tolerances
3.
To promote coordination of relationships between system and equipment voltage
ratings and tolerances
4.
To provide a guide for future development and design of equipment in order to achieve
the best possible conformance with the needs of the users
ANSI C84.1 (2011 edition) notes that some utilization equipment has nameplate voltages
inconsistent with reliable operation. Voltage ranges for which equipment is designed should
be changed as needed to be in accordance with the ranges shown in Table 2 of this document.
Voltage ratings in each class of utilization equipment should be the same as the nominal
system voltage, or related to the nominal system voltages by an approximate ratio of 115 to
120.
8 Apr 13
1C.2.1
Page 1 of 6
Volume 1—General
Part C—Power Quality
Section 2.1—Voltage Level and Range
3
Engineering Handbook
Voltage Ranges
Voltage is divided into two ranges: A and B. Each voltage range is listed for two locations:
service and utilization. Service voltage is measured at the point of delivery; utilization
voltage is measured at the terminals of the utilizing equipment. These are illustrated in
Figure 1 and detailed in Table 1 and Table 2 of this document.
Figure 1—Illustration of Voltage Ranges Consistent with ANSI C84.1
(See Tables 1 and 2 of this document for voltage range values.)
1C.2.1
Page 2 of 6
8 Apr 13
Volume 1—General
Part C—Power Quality
Section 2.1—Voltage Level and Range
Engineering Handbook
Table 1 − Service Voltage Ranges
Nominal Service
Voltage
Range B
Range A
Range A
Range B
Minimum
Maximum
Maximum
120/240, 3-wire
110/220
Minimum
Single-Phase
114/228
126/252
127/254
220/110
191/110
440/254
95%
Three-Phase
228/114
197/114
456/263
97.5%
252/126
218/126
504/291
105%
254/127
220/127
508/293
105.8%
240/120, 4-wire
208Y/120,4-wire
480Y/277,4-wire
2.4 to 34.5 kV
% of nominal
Above 34.5 kV
See Engineering Handbook Section 1B.3.
Table 2 − Utilization Voltage Ranges
Nominal Service
Voltage
Range B
Range A
Range A
Range B
Minimum
Minimum
Maximum
Maximum
126/252
127/254
Single-Phase
120/240, 3-wire
104/208
108/216
Three-Phase
240/120, 4-wire
208/104
216/108
252/126
254/127
208Y/120, 4-wire
180/104
187/108
218/126
220/127
480Y/277, 4-wire
416/204
432/249
504/291
508/293
2.4 to 34.5 kV
% of nominal
86.7%
90%
105%
105.8%
The difference between service and utilization voltage allows for voltage drop in facility
wiring between the point of utility delivery and the utilization equipment. National Electrical
Code (NEC) Articles 210−19(a), 215−2(a), and 310−15 recommend less than three percent
(< 3%) of voltage drop in branch circuits (from the sub-panel to utilization equipment). NEC
also recommends less than three percent (< 3%) of feeder voltage drop (between the main
panel and subpanel), with the combined voltage drop (of branch and feeder) being less than
five percent (< 5%).
8 Apr 13
1C.2.1
Page 3 of 6
Volume 1—General
Part C—Power Quality
Section 2.1—Voltage Level and Range
Engineering Handbook
3.1 Range A (Favorable Zone)
Voltage range A is the “favorable” zone, in which the voltage level is near optimal.
3.1.1
Service Voltage
PacifiCorp’s supply systems are designed and operated so that most service
voltage levels are within the limits specified for range A. The occurrence of
steady-state service voltages outside these limits shall be infrequent.
3.1.2
Utilization Voltage
Customer systems shall be designed and operated such that service voltage levels
are within range A limits and most utilization voltage levels are within the limits
specified for range A.
Utilization equipment shall be designed and rated to give fully satisfactory
performance throughout this range.
3.2 Range B (Tolerable Zone)
Voltage range B is the “tolerable” zone, in which the voltage level is acceptable but not
optimal.
Range B includes voltage levels above and below range A limits that necessarily result
from operating conditions. Although such conditions result in a practical system, they
should be limited in extent, frequency, and duration. Within reasonable timeframes,
corrective measures should be taken to upgrade voltage levels in range B to those in
range A.
In some cases, sustained voltage levels will fall outside range B. In these instances,
utilization equipment may not operate satisfactorily, and protective devices may need to
operate. Such cases should be considered temporary and subject to immediate
improvement.
3.3 Voltage Imbalance
The above voltage ranges apply to all phases of a three-phase system, even in the presence of voltage imbalance. If an electric supply system is operating near the upper or
lower limits of the ANSI C84.1 voltage ranges, each individual phase voltage should be
within the listed limits.
4
Regulatory References
4.1 California
Standard service voltages for California are listed in rule number 2 of the General
Rules and Regulations, Description of Service, for Pacific Power.
4.2 Idaho
Standard service voltages for Idaho are listed in section 3 of the General Rules and
Regulations, Description of Service, for Rocky Mountain Power.
1C.2.1
Page 4 of 6
8 Apr 13
Engineering Handbook
Volume 1—General
Part C—Power Quality
Section 2.1—Voltage Level and Range
4.3 Montana
Standard service voltages for Montana are listed in section 3 of the General Rules and
Regulations, Description of Service, for Pacific Power.
4.4 Oregon
Oregon Administrative Rules, Public Utility Commission, Chapter 860, Division 23
(Service Standards), Section 860−23−0020 (Quality of Electric Service) requires a “set
of normal standard voltages,” maintained so as to “not normally vary more than plus or
minus five percent [5%] of the standard at the service entrance.” Voltage surveys and
recorded results are also required. Standard service voltages are listed in Rule 3 of the
General Rules and Regulations, Description of Service, for Pacific Power, under Public
Utility Commission Order No. 34.
4.5 Utah
Utah Public Service Commission Rules R746−310−4, Station Instruments, Voltage and
Frequency Restrictions and Station Equipment (effective 9/1/12) refers to ANSI C84.1.
4.6 Washington
Washington UTC Rules relating to electric company operations: WAC 480−100,
Section 191373 (for standard voltage and permissible variation) requires that “standard
voltages” are adopted and filed. These rules also state that the variation in voltage shall
not be more than five percent (5%) above or below the standard voltage adopted, and
the total voltage variation shall not exceed eight percent (8%). Standard service
voltages are listed in Section 3 of the General Rules and Regulations, Description of
Service, for Pacific Power.
4.7 Wyoming
Wyoming Public Service Commission Rules of Practice & Procedure, Section 314
(P.S.C Wyoming No. 14, R6 −1), refers to ANSI C84.1. Standard service voltages are
listed in Rule 6 of the Rates and Rules, Description of Service, for Rocky Mountain
Power.
8 Apr 13
1C.2.1
Page 5 of 6
Volume 1—General
Part C—Power Quality
Section 2.1—Voltage Level and Range
5
Engineering Handbook
Handbook Issuing Department
The engineering standards and technical services department of PacifiCorp published this
document. Questions regarding editing, revision history and document output may be directed to the lead editor at (503) 813−5293. Technical questions and comments may be directed
to Dennis Hansen, engineering technical services, (801) 220−4816.
This material specification shall be used and duplicated only in support of PacifiCorp
projects. This document is considered a valid publication when the signature blocks below
have been signed by the authoring engineer and standards manager.
This document was last revised by a team that included the following PacifiCorp employees:
Larry Frick
Dave Hagen
Dennis Hansen
Greg Lyons
Rohit Nair
Brandon Prescott
Craig Quist
Ken Shortt
Aleksey Shkuratkov
Chuck Wright
Manager, Area/Transmission Planning
Manager, Transmission Planning
Principal Engineer, Standards
Manager, Smart Grid
Engineer, Standards
Manager, Field Engineering
Director, Area/Trans Planning & Devt.
Director, Field Engineering
Engineer, Transmission Standards
Sr. Engineer, Transmission Standards
(503) 813−6236
(801) 220−2620
(801) 220−4816
(503) 813−6883
(801) 220−4352
(503) 280−2740
(801) 220−4264
(801) 756−1237
(503) 813−5323
(503) 813−7093
Approved:
Dennis Hansen, Manager / Engineer
Department: RMP ETS
Approved:
Greg Lyons, Mgr Smart Grid
Supervisor, Engineering Publications
1C.2.1
Page 6 of 6
8 Apr 13