Download notes

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power inverter wikipedia , lookup

Electrical ballast wikipedia , lookup

Islanding wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Ground (electricity) wikipedia , lookup

Current source wikipedia , lookup

Ohm's law wikipedia , lookup

Power engineering wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power electronics wikipedia , lookup

Tesla coil wikipedia , lookup

Decibel wikipedia , lookup

Stepper motor wikipedia , lookup

Buck converter wikipedia , lookup

Surge protector wikipedia , lookup

Rectifier wikipedia , lookup

Earthing system wikipedia , lookup

Two-port network wikipedia , lookup

Single-wire earth return wikipedia , lookup

Electrical substation wikipedia , lookup

Stray voltage wikipedia , lookup

Voltage optimisation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Rectiverter wikipedia , lookup

History of electric power transmission wikipedia , lookup

Resonant inductive coupling wikipedia , lookup

Metadyne wikipedia , lookup

Opto-isolator wikipedia , lookup

Mains electricity wikipedia , lookup

Alternating current wikipedia , lookup

Transformer wikipedia , lookup

Three-phase electric power wikipedia , lookup

Transcript
Power transformers #2
1.0 Introduction
In the first set of notes on transformers, we
developed a basic model. Today we will see
how to use that model to identify the values
of its parameters. In addition, we will take a
look at three phase transformers.
One issue that requires mention is the
transfer of all impedances to one side of the
ideal transformer. It is possible to move all
to primary or all to secondary, and it is at
times convenient to do one and at times the
other. Generally, however, all impedances
are usually moved to the primary. The way
to do this starts by referring Z’2 to the
primary, shown in Fig. 1a.
I1
V1
Ideal network
Z1
Z’2
Lm
E1
N1
Fig. 1a
1
I2
E2
N2
V2
The relation between Z2 and Z’2 is
2
N 
Z 2   1  Z 2
 N2 
(1a)
Then we apply an approximation, which is
to move Z’2 over to be in series with Z1.
This approximation is justified by the fact
that ωLm>>>|Z’2|. The resulting circuit is
shown in Fig. 1b.
I1
Ideal network
Z1
Z’2
V1
Lm
E1
N1
I2
E2
V2
N2
Fig. 1b
Now we can combine the two impedances
2
 N1 
 Z 2
Z  r  jL  Z1  Z 2  Z1  
(1b)
 N2 
resulting in the circuit of Fig. 2.
I1
V1
I’2
Z
jXm
Ideal network
Im
E1
N1
Fig. 2
2
I2
E2
N2
V2
Note in Fig. 2 we re-labeled magnetizing
inductance as a magnetizing reactance jXm,
and current through it as Im.
2.0 Determining transformer parameters
Note in Fig. 2 that we have provided
notation for the current through the primary
winding. Note that this current is not I1.
Because of the magnetizing current Im, the
current into the primary terminal, I1, is not
the same as the current in the primary
winding. Do we need to use a new symbol
for it?
Actually, this current is related to the
secondary current I2 through the turns ratio
(N2/N1)I2. But as we have discussed, we do
not want to denote this current as I1. So let’s
use I’2.
That is, I’2=(N2/N1)I2. This notation, I’2,
may be read this way:
3
I2 referred to the primary side.
Likewise, we can use Z’2 as
 Z2 referred to the primary side.
We use double-prime notation (e.g., Z’’1) to
indicate primary quantities referred to the
secondary side.

With this notation, let’s consider two tests
often done to determine the values of the
transformer model parameters Z and Xm.
These two tests are discussed in Example
5.2 of the text.
A basic fact on which both tests are based is
that Xm>>>|Z|.
Open circuit test: In this test, rated voltage is
applied to the primary side and the
secondary side is left open. The circuit
diagram for this test is shown in Fig. 3.
I1
V1
I’2
Z
jXm
Ideal network
Im
E1
N1
4
I2
E2
N2
V2
Fig. 3
What is I’2? It is I2(N2/N1).
But I2=0.
Therefore I’2=0.
So if we measure V1 and I1, then we can find
Z  jX m
V1

I1
(2)
But because Xm>>>|Z|, it will be very
reasonable to approximate eq. (2) as:
Xm 
| V1 |
| I1 |
(3)
Eq. (3) is approximate but good. In addition,
it requires only measurement magnitudes.
Short-circuit test: In this test, the secondary
terminals are shorted, and a very low (why?)
voltage is applied to the primary terminals.
The resulting circuit appears as in Fig. 4.
I1
V1
I’2
Z
jXm
Ideal network
Im
E1
N1
Fig. 4
5
I2
E2
N2
In this case, I2 is very large. This makes I’2
also very large, and so the left side of the
circuit appears as in Fig. 5. We see from Fig.
5 that a short circuit on the secondary
“refers” to the primary as a short-circuit.
I1
I’2
Z
V1
jXm
Im
Fig. 5
We also see from Fig. 5 that jXm is shorted,
as so the circuit actually appears as in Fig. 6.
I1
I’2
Z
V1
Fig. 6
And so we see that
Z
V1
I1
(4)
If we approximate that Z=jX, then eq. (4) is:
X
| V1 |
| I1 |
(5)
6
Final comment here: Neglecting all
resistance in our transformer model is OK
for power flow analysis if we are interested
in flows and voltages only. But it is not OK
if we are interested in assessing real power
losses in the network.
In that case, you must model the winding
resistance. In addition, there is also a “coreloss” component associated with eddy
currents in the core, which occurs
independent of the loading. The core loss
component typically has a resistance on the
same order of magnitude as Xm.
3.0 Three phase connections (Sec. 5.2)
All transmission-level transformers deliver
three phase power.
There are two basic transformer designs:
7
1.Three interconnected single phase
transformers: The main disadvantage is its
cost (lots of iron); advantages are:
o they are smaller and lighter and therefore
easier to transport.
o they are relatively inexpensive to repair
2.One three-phase transformer (see Fig. 5.7
in text): The main advantage is its cost
(less iron). Disadvantages are:
o Large, heavy, difficult to transport.
o Expensive to repair.
We focus on the 1rst case (easier to visualize)
but principles apply to the 2nd case as well.
Interconnection of three single phase
transformers may be done in any of 4 ways:
 Y-Y  Δ-Y
 Δ-Δ  Y-Δ
These 4 ways are illustrated in Fig. 7:
8
Fig. 7 (Fig. 5.6 in text)
We can also use simpler diagrams, shown in
Fig. 8, where any two coils on opposite sides
of the bank (and therefore linked by the
same flux), are drawn in parallel.
9
Fig. 8 (Fig. 5.10 in text)
4.0 Turns ratio of 3-phase transformers
The turns ratio of 3-phase transformers is
always specified in terms of the ratio of the
line-to-line voltages. This may or may not be
the same as the turns ratio of the actual
windings for one of the single phase
transformers comprising the 3-phase
connection.
Nomenclature of subscripts: Upper case for
primary and lower case for secondary.
10
Example:
Consider three single phase transformers
each of which have turns ratio of
138kV/7.2kV=19.17. Find the ratio of the
line-to-line voltages if they are connected as:
a. Y-Y
b.Δ-Δ
c. Y-Δ
d.Δ-Y
(Assume all voltages are balanced.)
Since we are only interested in the ratio, we
may assume any voltage we like is
impressed across the primary winding. So
we assume that the primary winding always
has 138kV across it, and so the secondary
winding always has 7.2 kV across it. We
also assume (a) positive sequence voltages
and (b) the voltage across the 138kV
winding is reference (angle=0 degrees).
Recall: line voltages lead phase voltages by
30 degrees.
11
a. Y-Y:
V A, LN  1380
Va , LN  7.20
V A, LL  3 (138) 30
Va , LL  3 (7.2) 30
So the ratio of line-to-line voltages is:
3 (138) 30
3 (7.2) 30
 19.17
b. Δ-Δ:
V A, LL  1380
Va , LL  7.20
So the ratio of line-to-line voltages is:
138 0
 19.17
7.2 0
c. Y-Δ:
V A, LN  1380
Va , LL  7.20
V A, LL  3( 138 30 )
So the ratio of line-to-line voltages is:
3 (138) 30
 3 (19.17) 30
7.20
12
d. Δ-Y:
V A, LL  1380
Va , LN  7.20
Va , LL  3( 7.2 30 )
So the ratio of line-to-line voltages is:
1380
 19.17 

  30
3 (7.230)  3 
Conclusion (for balanced voltages):
a. Line-to-line ratio for Y-Y and Δ-Δ
connection is same as winding ratio.
b. Line-to-line ratio for Y-Δ connection is
330 times the winding ratio.
c. Line-to-line ratio for Δ-Y connection is
1
  30
times the winding ratio.
3
In the above, “Winding ratio” is the 138:7.2,
i.e., it is primary side to secondary side of
the single phase transformer.
13
We can also show the ratio of balanced line
currents on the primary to the line currents
on the secondary are exactly as above.
It is possible to connect the transformers
appropriately so that voltages & currents on
H.V. side always lead corresponding
quantities on L.V. side; it is convention in
the industry to do so. In the above, (b)
satisfies this convention; (c) does not.
As evidence of the last paragraph, Fig. 9
shows a Y-Δ transformer wrongly
connected, because high-side quantities
(lower case) lag low-side quantities by 30º.
Figs. 10 and 11 show how to correct the
problem by just changing the connections.
Note that these are step-up transformers.
14
Step-up Y-Δ three-phase transformer.
Improper transformer connection.
Vca
●
A
Low
side
a
●
●
●
c
●
B
●
C
High
side
b
VCN
VCA
VAB
VAN
Vab
Phasor
Rotation
VBN
VBC
Vbc
Fig. 9
The above is improper (not conventional)
because high-side quantities lag low side
quantities. To fix this:
1. Re-label the low side terminals (upper
case) so that C becomes A, A becomes B,
and B becomes C. This is shown in Fig. 10.
15
Step-up Y-Δ three-phase transformer.
Improper transformer connection.
Vca
●
C
Low
side
a
●
●
●
c
●
A
●
B
High
side
b
VAN
VAB
VBC
VBN
Vab
Phasor
Rotation
VCN
VCA
Vbc
Fig. 10
Now reverse all low side polarities by
reconnecting the windings so that terminals
previously tied to a common (neutral)
terminal are now connected to phase, and
terminals previously connected to phase are
now connected to a common terminal.
16
The effect of this is shown in Fig. 11.
Step-up Y-Δ three-phase transformer.
Proper transformer connection.
B
Low
side
Vca
a
●
●
●
●
C
●
c
●
A
High
side
b
VCA
VCN
VBN
Vab
VBC
VAN
Phasor
Rotation
Vbc
Fig. 11
17
VAB
The convention to label (and connect) Y-Δ
and Δ-Y transformers so that the high-side
quantities LEAD low side quantities by 30º
is referred to as the “American Standard
Thirty-Degree” connection convention.
We can show that under this convention,
high-side currents also lead low side
currents by 30º.
On pp. 139-142, the book gives a fairly
confusing discussion about voltage gain,
denoted by K. All you really need to know
about this discussion is contained in Table
5.2, pg. 142. I have repeated here with a bit
more information.
18
Table 1
Connection
Voltage gain K=VllHigh/VllLow
(Prim-Sec & Positive
Negative
Low-High)
sequence
sequence
Δ-Y
N
N
3 2 e j / 6
3 2 e  j / 6
N1
N1
Y-Δ
1 N 2 j / 6
1 N 2  j / 6
e
e
3 N1
3 N1
Some comments on the above table (focus
on positive sequence):
 Voltage gain is the increase in voltage
moving from input (primary) to output
(secondary).
 The voltage
gain of the windings is
n=N2/N1. The voltage gain of the line-line
voltage magnitudes is either 3n (Δ-Y) or
n / 3 (Y-Δ).
 The
connection is given low voltage
(primary) to high voltage (secondary) for
both connections (so that for positive
sequence, the phase shift is always +30°).
19

The book shows that current gain is
I2/I1=1/K*. So the current gain magnitude
is the inverse of the voltage gain
magnitude, but the phase shift will be
exactly the same.
The last point is an important one. For
balanced three-phase analysis, because both
the currents and voltages are shifted
precisely by 30°, we will get the same
answers, in terms of voltage and current
magnitude, and in terms of powers, if we
ignore the 30° altogether .
This fact is conducive to performing perphase analysis (and therefore per-unit
analysis).
You cannot ignore the phase shift for
unbalanced operation.
20