Download Delta Connected Capacitors Vs Wye Connected Capacitors

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Electrical engineering wikipedia , lookup

Electric motor wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Brushless DC electric motor wikipedia , lookup

Ground (electricity) wikipedia , lookup

Power inverter wikipedia , lookup

Electric power system wikipedia , lookup

Rectifier wikipedia , lookup

Power factor wikipedia , lookup

Fault tolerance wikipedia , lookup

Coilgun wikipedia , lookup

Buck converter wikipedia , lookup

Stray voltage wikipedia , lookup

Electrical substation wikipedia , lookup

Islanding wikipedia , lookup

Power MOSFET wikipedia , lookup

AC motor wikipedia , lookup

History of electric power transmission wikipedia , lookup

Surface-mount technology wikipedia , lookup

Electrification wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Surge protector wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Induction motor wikipedia , lookup

Power electronics wikipedia , lookup

Distribution management system wikipedia , lookup

Power engineering wikipedia , lookup

Stepper motor wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Alternating current wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Voltage optimisation wikipedia , lookup

Mains electricity wikipedia , lookup

Electrolytic capacitor wikipedia , lookup

Tantalum capacitor wikipedia , lookup

Aluminum electrolytic capacitor wikipedia , lookup

Niobium capacitor wikipedia , lookup

Capacitor plague wikipedia , lookup

Capacitor wikipedia , lookup

Three-phase electric power wikipedia , lookup

Transcript
Delta Connected Capacitors Vs Wye Connected Capacitors
(On Motors and used in Capacitor Banks)
Installing a Wye connected capacitors to motors is not appropriate application of the capacitor
and can potentially cause a catastrophic failure to not only the capacitor, but to the motor as
well. The main reason for this is because Wye connected capacitors are ungrounded and thus
can present a potential difference on each phase of the capacitor which in turn contributes to
the over-all deterioration of the capacitor and the attached motor.
As can be seen in fig.1 below, the failure of any one cell of a Wye connected capacitor presents
an unbalanced load to the motor. This will effectively destroy the motor due to unbalanced voltage, temperatures.
Example: If you have a 100HP motor and an unbalance of 5%, this will cause a power loss
of 25%. (100HP – 25% = 75HP). If the motor was loaded to 85%, the motor now becomes
overloaded. The motor would run 113.5% overloaded, therefore overheated and will
eventually burn out.
Unprotected Wye connected capacitors should not be used for Power Factor correction for similar reasons. In fact, the unbalance protection required for this type of application is more costly
than the capacitors themselves and therefore not generally included with Wye connected capacitors.
In addition, Wye connected capacitors do not circulate harmonics and thus are much more vulnerable to failure due to harmonics.
Fig.1 - The total capacitance for the example above with a failed cell would be 5kVAR
Cos Phi 151 Richmond St. S.W. Hensall, Ontario, N0M 1X0
Ph: 519-262-2822 Fax: 519-262-2310
www.cosphi.com
Delta connected three phase capacitors however are friendlier to the electrical environment.
They not only provide capacitance to each phase but also provides no voltage unbalances
(harmonics).
If a capacitor cell should fail for any reason in one phase, it will move from a closed delta to an
open delta configuration. In this instance the voltage on each phase stays the same (see fig.2
below). Failure of a capacitor cell would only mean a drop in the kVAR on the circuit. In other
words, a 30kVAR delta connected three phase capacitor with a failed cell would provide 20kVAr
to the electrical system instead of 30kVAR.
Delta connected capacitors unlike the Wye connected capacitors are also capable of circulating
harmonic currents to a degree within the delta circuit and by doing so help to reduce the harmonics on the electrical system.
Fig.2 - The total capacitance for the example above with a failed cell would be 20kVAR
Cos Phi 151 Richmond St. S.W. Hensall, Ontario, N0M 1X0
Ph: 519-262-2822 Fax: 519-262-2310
www.cosphi.com
Some of our clients include…
University Health Network
Ford
Parrish & Heimbecker
Metro Convention Centre
Honda of Canada Mfg
EATON/Cutler Hammer
Schneider Electric
General Motors
Cosella Dorken
Johnson Controls
Siemens
Pepsico
City of Mississauga
Agriculture & Agri-Food Canada
Sifto Salt Mine
Thompsons
Unimotion Gear
Bluewater Recycling Association
Beavers Dental
Newform Tools
Mitten Vinyl
General Electric
All company names and Trademarks are owned by their respective companies
Products / Services
Low, Medium & High Voltage
Power Factor Correction
(Static and Auto-Switching)
Power Quality Surveys
Thermal Scanning
Transient Voltage Surge Suppression
Modeling of Power Systems
and Engineering Studies
Design of Substations and Power Systems
Engineering Drawings
Test & Measurement Services
Harmonic Filters
Power Factor & Power Quality Education
(Individual or Group Training)
Cos Phi 151 Richmond St. S.W. Hensall, Ontario, N0M 1X0
Ph: 519-262-2822 Fax: 519-262-2310
www.cosphi.com