Download TEMPUS: SWITCHING OPERATIONS 1: Introduction In case an

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Ground loop (electricity) wikipedia , lookup

Transistor wikipedia , lookup

Power inverter wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Stepper motor wikipedia , lookup

Ground (electricity) wikipedia , lookup

Power engineering wikipedia , lookup

Three-phase electric power wikipedia , lookup

Electrical ballast wikipedia , lookup

Power electronics wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Schmitt trigger wikipedia , lookup

Distribution management system wikipedia , lookup

Rectifier wikipedia , lookup

Ohm's law wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power MOSFET wikipedia , lookup

History of electric power transmission wikipedia , lookup

Voltage regulator wikipedia , lookup

Earthing system wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Electrical substation wikipedia , lookup

Current source wikipedia , lookup

Opto-isolator wikipedia , lookup

Voltage optimisation wikipedia , lookup

Metadyne wikipedia , lookup

Stray voltage wikipedia , lookup

Triode wikipedia , lookup

Network analysis (electrical circuits) wikipedia , lookup

Current mirror wikipedia , lookup

Surge protector wikipedia , lookup

Islanding wikipedia , lookup

Buck converter wikipedia , lookup

Alternating current wikipedia , lookup

Mains electricity wikipedia , lookup

Circuit breaker wikipedia , lookup

Transcript
TEMPUS: SWITCHING OPERATIONS
1: Introduction
In case an electrical grid supplies a sinusoidal voltage to a linear load, a sinusoidal current is
flowing (which is a steady state behavior). When a load switch or a circuit breaker opens, a
transient behavior occurs before the current becomes and remains zero. This transient will be
studied, mainly when interrupting a short circuit current and a distinction is made between
-
ohmic loads,
inductive loads,
ohmic-inductive loads.
2: An ohmic loaded grid
Μ‚ 𝑠𝑖𝑛(πœ”π‘‘) and suppose the grid
Consider a grid supplying a sinusoidal voltage 𝑒(𝑑) = π‘ˆ
impedance 𝑅1 is resistive. The load 𝑅2 is ohmic and 𝑅2 ≫ 𝑅1 . The circuit breaker S is closed
and the current is limited by 𝑅1 + 𝑅2 giving a current
𝑖(𝑑) =
Μ‚
𝑒(𝑑)
π‘ˆ
=
𝑠𝑖𝑛(πœ”π‘‘) .
𝑅1 + 𝑅2
𝑅1 + 𝑅2
Figure 1: Ohmic loaded grid
In case of a short circuit between a and b in Figure 1, a short circuit current will flow which is
only limited by 𝑅1 . The large short circuit current 𝑖𝐢𝐢 (𝑑) also has the same phase as the grid
voltage 𝑒(𝑑). More precisely,
𝑖𝐢𝐢 (𝑑) =
Μ‚
𝑒(𝑑)
π‘ˆ
=
𝑠𝑖𝑛(πœ”π‘‘) .
𝑅1
𝑅1
The normal load current 𝑖(𝑑) is flowing during hours (or more). As the short circuit occurs,
the short circuit current is flowing during for instance 0.5 seconds (notice 0.5 seconds
contains 25 periods of 20 milliseconds). The short circuit current, which is flowing during a
number of periods of the grid voltage, is visualized in Figure 2 (dotted lines). This short
circuit is detected and at an arbitrary 𝑑 = 𝑑0, the contacts of the circuit breaker will open.
After 𝑑 = 𝑑0 , due to the electric arc, the short circuit current is still flowing. As the
instantaneous value of the short circuit current passes zero, the arc extinguishes (at 𝑑 = 𝑑1 in
Figure 2). The circuit breaker avoids re-ignition of the arc implying the current remains zero.
As long as the circuit breaker is closed, there is no voltage across the closed contacts.
Between 𝑑0 and 𝑑1 , the contacts are open but the voltage across the contacts (across the arc) is
Μ‚ 𝑠𝑖𝑛(πœ”π‘‘) appears across the open contacts of
limited. From 𝑑 = 𝑑1 , the grid voltage 𝑒(𝑑) = π‘ˆ
the circuit breaker. Due to this voltage, no re-ignition of the arc is allowed.
Figure 2: Interrupting an ohmic short circuit current
3: An inductive loaded grid
Μ‚ 𝑠𝑖𝑛(πœ”π‘‘) and suppose the grid
Consider a grid supplying a sinusoidal voltage 𝑒(𝑑) = π‘ˆ
impedance 𝐿1 is inductive. The load 𝐿2 is purely inductive and 𝐿2 ≫ 𝐿1 . The circuit breaker S
is closed and the current is limited by 𝐿1 + 𝐿2 giving a steady state current
𝑖(𝑑) =
Μ‚
π‘ˆ
πœ‹
𝑠𝑖𝑛 (πœ”π‘‘ βˆ’ )
πœ”(𝐿1 + 𝐿2 )
2
which lags an angle πœ‹β„2 with respect to the voltage. Figure 3 visualizes this inductive loaded
grid. Notice in Figure 3 the parasitic capacitance 𝐢 which has no influence as long as the
circuit breaker S is closed.
Figure 3: Inductive loaded grid
In case of a short circuit between a and b in Figure 3, a short circuit current will flow which is
only limited by 𝐿1 . The large short circuit current 𝑖𝐢𝐢 (𝑑) also lags an angle πœ‹β„2 with respect
to the grid voltage 𝑒(𝑑). More precisely,
𝑖𝐢𝐢 (𝑑) =
Μ‚
π‘ˆ
πœ‹
𝑠𝑖𝑛 (πœ”π‘‘ βˆ’ ) .
πœ”πΏ1
2
The normal load current 𝑖(𝑑) is flowing during hours (or more). As the short circuit occurs,
the short circuit current is flowing during for instance 0.5 seconds (notice 0.5 seconds
contains 25 periods of 20 milliseconds). The short circuit current, which is flowing during a
number of periods of the grid voltage, is visualized in Figure 4. This short circuit is detected
and at an arbitrary 𝑑 = 𝑑0 , the contacts of the circuit breaker will open.
Figure 4: Interrupting an inductive short circuit current
After 𝑑 = 𝑑0 , due to the electric arc, the short circuit current is still flowing. As the
instantaneous value of the short circuit current passes zero, the arc extinguishes (at 𝑑 = 𝑑1 in
Figure 4). The circuit breaker avoids re-ignition of the arc implying the current remains zero.
As long as the circuit breaker is closed, there is no voltage across the closed contacts.
Between 𝑑0 and 𝑑1 , the contacts are open but the voltage across the contacts (across the arc) is
limited. From 𝑑 = 𝑑1 , a voltage appears across the open contacts of the circuit breaker. Notice
however, this voltage is not a sinusoidal voltage having a frequency of 50 Hz as it is the case
when considering an ohmic loaded grid.
At 𝑑 = 𝑑1 , the grid voltage is not zero (the grid voltage attains a maximum) but due to the
parasitic capacitor 𝐢 the voltage across the contacts does not change immediately. Notice the
high resonance frequency due to 𝐢 and 𝐿1 giving, across the contacts of the circuit breaker, a
voltage
𝑑 βˆ’ 𝑑1
Μ‚ π‘π‘œπ‘ (πœ”(𝑑 βˆ’ 𝑑1 )) βˆ’ π‘ˆ
Μ‚ π‘π‘œπ‘  (
𝑒𝑆 (𝑑) = π‘ˆ
).
√𝐿1 𝐢
Due to the high resonance frequency, the voltage across the circuit breaker S changes very
fast and becomes almost twice the grid peak voltage. Since this voltage across S changes very
fast and becomes almost twice the grid peak voltage, it is not obvious to avoid re-ignition of
the arc. Indeed, interrupting an inductive current is much more difficult than interrupting an
ohmic current.
3.1: Voltage across the circuit breaker
The voltage across the open circuit breaker will be calculated for all 𝑑 β‰₯ 𝑑1. Due to the short
circuit, the evolution of the voltage across the circuit breaker S can be modeled as visualized
in Figure 5. When opening the circuit breaker, the parasitic capacitor 𝐢 across the contacts of
the circuit breaker is important.
Define 𝑑 β€² = 𝑑 βˆ’ 𝑑1 . At 𝑑 β€² = 0, 𝑒𝐢 (𝑑 β€² = 0) = 0 and 𝑖𝐿1 (𝑑 β€² = 0) = 𝑖𝐢 (𝑑 β€² = 0) = 0 and the
behavior is described by the differential equation
Μ‚ π‘π‘œπ‘ (πœ”π‘‘β€²) = 𝐿1
π‘ˆ
𝑑 𝑖𝐿1 (𝑑′)
+ 𝑒𝐢 (𝑑′)
𝑑𝑑′
and
𝑑′
𝑒𝐢 (𝑑′) = 𝑒𝐢
(𝑑 β€²
𝑑′ (𝜏)
𝑖𝐿1 (𝜏)
𝑖𝐢
β€²
= 0) + ∫
π‘‘πœ = 𝑒𝐢 (𝑑 = 0) + ∫
π‘‘πœ.
𝐢
𝐢
0
0
Figure 5: Modeling the open circuit breaker in case of a short circuit
By taking the Laplace transform,
Μ‚
π‘ˆ
𝑠
= 𝐿1 𝑠 𝐼𝐿1 (𝑠) βˆ’ 𝐿1 𝑖𝐿1 (𝑑 β€² = 0) + π‘ˆπΆ (𝑠)
𝑠2 + πœ”2
and
π‘ˆπΆ (𝑠) =
1 1
(𝐼 (𝑠) + 0)
𝐢 𝑠 𝐿1
giving
Μ‚
π‘ π‘ˆ
1
(𝑠)
=
𝑠
𝐿
𝐼
+
𝐼 (𝑠)
1
𝐿1
𝑠2 + πœ”2
𝑠 𝐢 𝐿1
or equivalently
𝐼𝐿1 (𝑠) =
Μ‚
π‘ π‘ˆ
𝑠𝐢
.
𝑠 2 + πœ” 2 1 + 𝑠 2 𝐿1 𝐢
This implies
π‘ˆπΆ (𝑠) =
Μ‚
𝐼𝐿1 (𝑠)
π‘ π‘ˆ
1
= 2
.
𝑠𝐢
𝑠 + πœ” 2 1 + 𝑠 2 𝐿1 𝐢
Using partial fraction decomposition, one obtains
π‘ˆπΆ (𝑠) =
Μ‚
π‘ˆ
𝑠
𝑠
(
βˆ’
)
1 βˆ’ πœ” 2 𝐿1 𝐢 𝑠 2 + πœ” 2 𝑠 2 + 1
𝐿1 𝐢
and taking the inverse Laplace transform (πœ” β‰ͺ (1⁄𝐿1 𝐢 ))
𝑒𝐢 (𝑑′) =
Μ‚
π‘ˆ
𝑑′
𝑑′
Μ‚ π‘π‘œπ‘ (πœ”π‘‘β€²) βˆ’ π‘ˆ
Μ‚ π‘π‘œπ‘  (
(π‘π‘œπ‘ (πœ”π‘‘β€²)
βˆ’
π‘π‘œπ‘ 
(
))
β‰ˆ
π‘ˆ
).
1 βˆ’ πœ” 2 𝐿1 𝐢
√𝐿1 𝐢
√𝐿1 𝐢
Since 𝑑 β€² = 𝑑 βˆ’ 𝑑1 and 𝑒𝐢 (𝑑) = 𝑒𝑆 (𝑑) one obtains that
𝑑 βˆ’ 𝑑1
Μ‚ π‘π‘œπ‘ (πœ”(𝑑 βˆ’ 𝑑1 )) βˆ’ π‘ˆ
Μ‚ π‘π‘œπ‘  (
𝑒𝑆 (𝑑) = π‘ˆ
).
√𝐿1 𝐢
Notice at 𝑑 = 𝑑1 , the voltage across the circuit breaker S equals zero but a fast increase of this
Μ‚ is reached. Due to this voltage rise, no re-ignition of
voltage occurs and almost a voltage 2π‘ˆ
the voltage is allowed.
4: An ohmic inductive loaded current
In case the grid impedance and the load are ohmic inductive, the transient voltage across the
circuit breaker S after 𝑑1 contains
-
a 50 Hz voltage component due to the grid voltage,
a damped high frequent oscillation due to 𝐢 and 𝐿1 .
5: Interrupting the current
Until now, the zero crossing of the current is used to extinguish the arc in the circuit breaker
(or the load switch) implying it is mainly the task of the circuit breaker to avoid this arc does
not re-ignite. In other cases, the current is interrupted without the use of the zero crossings of
the current. Figure 6 visualizes an example of such a situation.
Figure 6: Interrupting the primary current of a transformer
Figure 6 visualizes the sinusoidal grid voltage source 𝑒(𝑑) and the grid impedance containing
a resistive part 𝑅 and an inductive part 𝐿. Notice the parasitic capacitances 𝐢1 and 𝐢2 . Notice
the circuit breaker S having a voltage 𝑒𝑆 (𝑑) across its contacts. The load is the primary
winding of a transformer having an unloaded secondary winding. The current consumed by
the transformer at primary side is ohmic inductive (mainly inductive).
Due to a voltage across the parasitic capacitor 𝐢1 , energy is stored in this capacitor. In case
the capacitor voltage equals 𝑒𝐢1 , the stored energy equals
𝐸(𝐢1 ) = 𝐢1
2
𝑒𝐢1
.
2
Notice the inductance 𝐿1 of the primary winding of the transformer. Due to a current 𝑖𝐿1 , the
energy stored in 𝐿1 equals
𝐸(𝐿1 ) = 𝐿1
2
𝑖𝐿1
.
2
Figure 7 visualizes the evolution of the voltage 𝑒𝑆 (𝑑) across the circuit breaker (or load
switch) and the evolution of the current 𝑖𝑆 (𝑑). Originally, the circuit breaker S is closed and
the 50 Hz current consumed by the primary winding of the transformer (by 𝐿1 ) is flowing
through S (the current through 𝐢1 is very small and can be neglected). This current lags
approximately an angle πœ‹β„2 with respect to the applied voltage 𝑒𝑆 (𝑑) which is visualized by
dotted lines.
The circuit breaker opens which forces 𝑖𝑆 (𝑑) to zero. There is energy stored in 𝐿1 and this
energy will be transported to 𝐢1 . The voltage across 𝐢1 increases rapidly implying a large
voltage across the circuit breaker (𝐢1 is small implying a high voltage is needed to store some
energy). Due to the large voltage across the circuit breaker, an arc appears. Due to this arc,
electrical charges are drained which discharges 𝐢1 implying the voltage across S decreases.
Due to this decreased voltage, the arc extinguishes.
Figure 7: Evolution of the circuit breaker current and voltage
When the arc extinguishes, the current through 𝐿1 is not zero (although already smaller). The
energy stored in 𝐿1 will be transported to 𝐢1 . The voltage across 𝐢1 increases rapidly implying
a large voltage across the circuit breaker. Due to this second voltage peak across the circuit
breaker, a second arc appears. Also this second arc drains electrical charges from 𝐢1 implying
the voltage decreases and the arc extinguishes a second time.
The phenomenon where:
-
energy is transported from 𝐿1 to 𝐢1 ,
an arc appears and 𝐢1 is discharged,
the arc extinguishes,
repeats itself several times until the energy stored in 𝐿1 is sufficiently small. The voltage
across 𝐢1 remains sufficiently small implying no new arc appears.
Finally, an oscillatory behavior due to 𝐿1 and 𝐢1 appears. No current is flowing through the
circuit breaker anymore since no new arc appears. Due to resistances (implying losses), the
oscillation is damped. Once the high frequent oscillation has disappeared, only the 50 Hz grid
voltage appears across the circuit breaker.
6: DC voltages and DC currents
It is obvious in case of an AC current, the zero crossings of the current help to interrupt the
current. In case a DC current will be interrupted, there are no zero crossings. Interrupting a
DC current is much more difficult than interrupting an AC current (especially if the load is
inductive). Due to this reason, there are dedicated DC fuses, DC contactors and DC circuit
breakers available on the market. Due to the rise of photovoltaic installations and battery
storage installations, the use of DC fuses, DC circuit breakers and DC contactors is rising.
References
Van Dommelen D., Productie, transport en distributie van elektriciteit, Acco, Leuven, 2001.
Weedy B.M., Cory B.J., Electric Power Systems, Wiley & Sons, New York, 2001.