Download 2. Design, operation and environment

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Variable-frequency drive wikipedia , lookup

Electrical ballast wikipedia , lookup

Power inverter wikipedia , lookup

Power engineering wikipedia , lookup

Relay wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Fault tolerance wikipedia , lookup

Rectifier wikipedia , lookup

Electromagnetic compatibility wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Alternating current wikipedia , lookup

Ground (electricity) wikipedia , lookup

Voltage optimisation wikipedia , lookup

Stray voltage wikipedia , lookup

Surge protector wikipedia , lookup

Distribution management system wikipedia , lookup

Resonant inductive coupling wikipedia , lookup

Rectiverter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Mains electricity wikipedia , lookup

Buck converter wikipedia , lookup

Earthing system wikipedia , lookup

Crossbar switch wikipedia , lookup

Electrical substation wikipedia , lookup

Circuit breaker wikipedia , lookup

Switch wikipedia , lookup

Network analysis (electrical circuits) wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Opto-isolator wikipedia , lookup

Transcript
Specification for Tender
769854833
Specification for Remotely operated
Transfer Switching Equipment (RTSE)
based on 100 to 630 A circuit breakers
General
Design, operation and environment
Endurance
Auxiliaries
RTSE: Remotely operated Transfer Switching Equipment
Last update: 2017-05-11
-1-
Specification for Tender
769854833
Contents:
1. General……………………………………………………………………..……….......................... p. 3
2. Design, operation and environment. ……………………………………………………………… p. 3 - 4
3. Endurance ……………………………………………………………………………….................. p. 4
4. Auxiliaries ………………………………………………………….................................................. p. 4
Last update: 2017-05-11
-2-
Specification for Tender
769854833
1. General
1.1 The Remotely operated Transfer Switching Equipment (RTSE) based on circuit breakers and designed
for power distribution will conform to the requirements of IEC 60947-1 and IEC 60947-6-1 and to the latest
versions of the corresponding national standards in the member countries (VDE 0660-100 and 0660-114, BS
EN 60947-1 and 60947-6-1, NF EN 60947-1 and 60947-6-1).
1.2 The transfer switch will be a derived device. It will use products based on IEC 60947-2, IEC 60947-3
and IEC 60947-4-1.
1.3 The Remotely operated Transfer Switching Equipment (RTSE) will be designed to offer the following
functions under optimum safety conditions: it will either be controlled by an automated device provided by
the customer or by an automated device supplied by the manufacturer.
1.4 The transfer switch will have the following electrical characteristics:
1.4.1 a rated impulse withstand voltage (Uimp=) of 8 kV.
1.4.2 a rated insulation voltage (Ui) of 750 V AC.
1.4.3 a rated operating voltage (Ue) of 550 V AC or 690 V AC.
1.5 The transfer switch will be available in 3-pole and 4-pole versions, and the normal and emergency circuit
breakers must have the corresponding number of poles.
1.6 The transfer switch can be used for frequencies of 50/60 Hz.
1.7 The transfer switch design will incorporate three stable positions:
1.7.1 normal circuit breaker OPEN,
1.7.2 CLOSED,
1.7.3 emergency circuit breaker OPEN.
1.8 The OFF position will be a disconnect position. The transfer switch will be appropriate for disconnection
in accordance with IEC 60947-1 and 60947-2, subclause 7.2.7 and for Overvoltage Category IV and up to
the rated insulation voltage of 690 V in accordance with IEC 60664-1. Each power circuit breaker will also
be lockable in the OPEN position.
1.9 It will also be possible to operate the transfer switch manually if no control voltage is present.
1.10 The transfer switch will be designed to incorporate class II insulation (in accordance with IEC 60664-1)
between the front panel and the internal power circuits.
1.11 The transfer switch will have a control voltage of 48 to 415 V AC (50/60 Hz) or 440 V AC (60 Hz
only) or 24-250 V DC.
1.12 The transfer switch performance operating category will be AC32B in accordance with IEC 60947-6-1.
1.13 The Remotely operated circuit-breaker based Transfer Switching Equipment (RTSE) will incorporate a
mechanical interlock and/or an electrical interlock to prevent any possibility of connecting the normal and
emergency sources.
1.14 It will be possible to combine circuit breakers of different breaking capacities and switches.
1.15 If a switch is used, the upstream safety device must be specified by the manufacturer.
1.16 For all the operating voltages and frequencies allowed, the transfer switch will operate within a
temperature range of –25°C to +70°C.
2. Design, operation and environment
2.1 The production site will comply with the requirements of ISO 9000 and ISO 14001.
2.2 The transfer switch will comply with the Eco-design principles defined by ISO 14062.
2.3 The transfer switch must be fitted with an electrical interlock system.
2.4 The transfer switch will include two circuit breakers (fixed or draw out) installed on a mounting plate. It
will be possible to interlock these circuit breakers mechanically.
2.5 It will be possible to interlock two draw-out or fixed circuit breakers mechanically.
Last update: 2017-05-11
-3-
Specification for Tender
769854833
2.6 The Remotely operated circuit-breaker based Transfer Switching Equipment (RTSE) will provide
protection against overloads, as well as protection against short circuits.
2.7 The transfer switch will also include an earth leakage protection function, via an incorporated or separate
earth leakage protection device.
2.8 To ensure disconnection with positive break indication in accordance with IEC 60947-1 and IEC 609472, subclause 7.2.7:
2.8.1 the mechanism design will ensure that the operating handles will only be in position (O) if the main
contacts are physically separated,
2.8.2 in position (O), the handles will indicate the disconnected position.
2.9 Disconnection will be improved by the main circuit double breaking feature, i.e. the normal and
emergency circuit breakers will be able to open simultaneously.
2.10 The minimum changeover time of the transfer switch contacts will be less than 1 second.
3. Endurance
3.1 The mechanical endurance on the Normal opening – Emergency closing - Emergency opening - Normal
closing cycles (NO-EC-EO-NC) will be as follows:
3.1.1 10,000 cycles, for ratings <= 250 A
3.1.2 8,000 cycles, for higher ratings.
3.2 The electrical endurance on NO-EC-EO-NC cycles for operating voltages <= 440 V will be:
3.2.1 10,000 cycles, for ratings <= 250 A
3.2.2 3000 cycles, for ratings of 400 A-630 A
3.3 The electrical endurance on NO-EC-EO-NC cycles for higher operating voltages will be 1500 cycles.
4. Auxiliaries
4.1 It will be possible to fit the transfer switch with a downstream coupling device to make it easier to
connect the busbars and lugged cables. It will allow same size circuit breakers to be combined and be used
only on fixed versions.
4.2 Each transfer switch circuit breaker will be fitted with auxiliary contacts and alarm contacts (TRIPPED
state indication).
4.3 The transfer switch will be fitted with voltage presence indicators and may be equipped with insulation
control units.
Last update: 2017-05-11