Download Fault Tolerant Intelligent Access Control System

Document related concepts

Alternating current wikipedia , lookup

Power over Ethernet wikipedia , lookup

Control theory wikipedia , lookup

PID controller wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Ground (electricity) wikipedia , lookup

Mains electricity wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Earthing system wikipedia , lookup

Fault tolerance wikipedia , lookup

Transcript
Fault Tolerant Intelligent Access Control System
Installation Manual
33-10068-001
REV: A
PCSC
3541 Challenger Street
Torrance, CA 90503
Phone: (310) 303-3600
FAX: (310) 303-3600
www.1pcsc.com
First Edition: January 2010
Information in this manual is subject to change without notice and does not represent a commitment on
the part of PCSC. The software described in this manual is furnished under a license agreement or
nondisclosure agreement. The software may be used or copied only in accordance with the terms of the
agreement. No part of this document may be reproduced or transmitted in any form or by any means,
electronic or mechanical, including photocopying, recording, or information storage and retrieval
systems, for any purpose other than specified in the agreement, without the express written permission
of PCSC.
 2010 PCSC. All Rights Reserved.
Printed in the United States of America.
Published by PCSC
3541 Challenger Street
Torrance, CA 90503
(310) 303-3600 ph/fax
Publication Number: 33-10068-001-A-Pre
Page 2 of 90
Fault Tolerant Controller Manual
33-10068-001-A
0.1 Board Diagrams
0.1.1 The FTC Printed Circuit Board Wiring Diagram
Page 3 of 90
Fault Tolerant Controller Manual
33-10068-001-A
0.1.2 The FTC – Rack-Mounted
Page 4 of 90
Fault Tolerant Controller Manual
33-10068-001-A
0.1.3 The DDM Printed Circuit Board Wiring Diagram
Page 5 of 90
Fault Tolerant Controller Manual
33-10068-001-A
0.1.4 The SDM Printed Circuit Board Wiring Diagram
Page 6 of 90
Fault Tolerant Controller Manual
33-10068-001-A
0.2 Table of Contents
0.1 Board Diagrams................................................................................................................................. 3
0.1.1 The FTC Printed Circuit Board Wiring Diagram ......................................................................... 3
0.1.2 The FTC – Rack-Mounted .......................................................................................................... 4
0.1.3 The DDM Printed Circuit Board Wiring Diagram ........................................................................ 5
0.1.4 The SDM Printed Circuit Board Wiring Diagram ........................................................................ 6
1.0 Introduction ......................................................................................................................................... 10
1.1 Theory of Operation ........................................................................................................................ 11
1.1.1.
Redundancy ...................................................................................................................... 12
2.0 Installing Power ................................................................................................................................... 13
2.1 Installing Power to the FTC and DDM ............................................................................................. 13
2.1.1 Installing Power- 3.0 Amp ......................................................................................................... 13
2.1.2 PCSC 3.0 Amp Power Supply .................................................................................................. 14
2.2 Installing Power SDM ...................................................................................................................... 15
2.2.1 Installing Power- 3.0 Amp ......................................................................................................... 15
2.2.2 PCSC 3.0 Amp Power Supply .................................................................................................. 16
2.3 Resetting a Panels to Default Values .............................................................................................. 17
3.0 Wiring the Readers ............................................................................................................................. 18
3.1 Grounding the Readers ................................................................................................................... 19
3.2 Properly Routing the Cables ........................................................................................................... 19
3.3 Grounding the Power and Data Lines ............................................................................................. 19
3.3.1 Procedure ................................................................................................................................. 19
3.4 Grounding the Pin Pad or Reader ................................................................................................... 20
3.4.1 Procedure ................................................................................................................................. 20
3.4.2 Grounding the Reader Mullion Mount ....................................................................................... 20
4.0 Reader Connections to the DDM ........................................................................................................ 21
4.0.1. Reader Disconnect Resistors .................................................................................................. 21
4.1 Reader Connections: PR233 MiniProx / PR-733/732 ..................................................................... 22
4.2 Reader Connections: PR-234 / PRK-234 ProxPro / PR736 / PRK-736 .......................................... 23
4.3 Reader Connections: PR-235 MaxiProx / PR-735 .......................................................................... 24
4.4 Reader Connections: Sensor Wiegand ........................................................................................... 25
4.5 Reader Connections: VeriProx / V-Pass/ ........................................................................................ 26
4.6 Reader Connections: iClass ............................................................................................................ 27
4.7 Reader Connections: Xceed ID SP632/SP632M/SP633/SP635/SPK635 ...................................... 28
4.8 Reader Connections: Biometric....................................................................................................... 29
5.0 Wiring the Door(s) ............................................................................................................................... 30
Page 7 of 90
Fault Tolerant Controller Manual
33-10068-001-A
5.1 Wiring the Panel in a Fail-Safe Environment .................................................................................. 32
5.1.1 Fail Safe - DDM ........................................................................................................................ 32
5.1.1 Fail Safe - SDM ........................................................................................................................ 33
5.2 Wiring Panel in a Fail-Secure Environment .................................................................................... 34
5.2.1 Fail-Secure - DDM .................................................................................................................... 34
5.2.2 Fail-Secure - SDM .................................................................................................................... 35
5.3 LED Arrays ...................................................................................................................................... 36
5.3.1 Using the Seven Segment LED Array ...................................................................................... 36
5.3.2 Status Chart for All LED Arrays ................................................................................................ 36
5.4 Installing Noise Suppression Devices ............................................................................................. 36
5.4.1 Procedure ................................................................................................................................. 36
5.5 Reset button .................................................................................................................................... 37
5.5.1 Reset button on the FTC and DDM .......................................................................................... 37
5.5.2 Reset Button on the SDM ......................................................................................................... 38
6.0 Communicating with the FTC, DDM and SDM through TCP/IP ......................................................... 39
6.0.1 Connecting to a Panel via TCP/IP ............................................................................................ 39
6.1 Programming the FTC ..................................................................................................................... 40
6.1.1 Connecting to a FTC ................................................................................................................. 40
6.1.2 Setting the Name and IP Address of a FTC ............................................................................. 42
6.1.3 Configure a Network of Connected FTCs ................................................................................. 44
6.1.4 Setting the Time Zone for a Particular Panel............................................................................ 46
6.1.5 Changing the Password............................................................................................................ 48
6.1.6 Specifying the IP Address to Allow FT configuration access ................................................... 50
6.2 Programming the Dual Door Module ............................................................................................... 53
6.2.1 Connecting to the DDM ............................................................................................................ 53
6.2.2 Setting the Name and IP Address of a DDM ............................................................................ 55
6.2.3 Configure the DDM’s Primary FTC and Secondary FTCs ........................................................ 57
6.2.4 Setting the Time Zone for a Particular Panel............................................................................ 59
6.2.5 Changing the Password............................................................................................................ 61
6.2.6 Specifying the allowable Hosts and Workstations within a network ......................................... 63
6.3 Programming the Single Door Module ............................................................................................ 65
6.3.1 Connecting to the SDM............................................................................................................. 65
6.3.2 Setting the Name and IP Address of a SDM ............................................................................ 67
6.3.3 Configure the SDM’s Primary FTC and Secondary FTCs ........................................................ 68
6.3.4 Changing the Password............................................................................................................ 70
6.3.5 Setting the Time Zone for a Particular Panel............................................................................ 72
6.3.6 Setting the Panel Number for the SDM .................................................................................... 74
6.3.7 Specifying the allowable Hosts and Workstations within a network ......................................... 76
6.4 DIPswitch Addressing ..................................................................................................................... 78
Page 8 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.4.1 Location of the DIPswitch on the FTC and DDM ...................................................................... 78
7.4.2 DIPswitching the Panel Address (1-63) .................................................................................... 79
7.4.3 Software Addressing of the SDM ............................................................................................. 80
8.0 Status Lights and Dealing with Communication Errors....................................................................... 81
8.1 LED and 7 Segment LED Communication ...................................................................................... 81
8.2 Communication Errors ..................................................................................................................... 81
8.2.1 Communication Errors – FTC ................................................................................................... 81
8.2.2 Communication Errors - DDM .................................................................................................. 81
8.2.3 Communication Errors - SDM ................................................................................................... 82
8.3 Sense Inputs for the DDM and SDM ............................................................................................... 82
8.4 User Selectable Options .................................................................................................................. 83
9.0 Appendix A - FTC Specifications ........................................................................................................ 84
9.1 Fault Tolerant Controller Features – FTC ....................................................................................... 84
9.1.1 System Capacities .................................................................................................................... 84
9.1.2 Electrical Ratings ...................................................................................................................... 84
9.2 Fault Tolerant Controller Features – Dual Door Module ................................................................. 85
9.2.1 Electrical Ratings ...................................................................................................................... 85
9.3 Fault Tolerant Controller Features – Single Door Module .............................................................. 86
9.3.1 Electrical Ratings ...................................................................................................................... 86
9.4 Cable Requirements and Maximum Lengths .................................................................................. 87
9.4.1 Communication- ........................................................................................................................ 87
9.4.1 Readers .................................................................................................................................... 87
9.5 Tool Requirements .......................................................................................................................... 88
9.6 Controller Specifications .................................................................................................................. 88
9.7 Maintenance Requirements ............................................................................................................ 89
9.7.2 Back-Up Memory Battery Replacement ................................................................................... 89
9.7.3 Power Supply Back Battery Replacement ................................................................................ 89
Page 9 of 90
Fault Tolerant Controller Manual
33-10068-001-A
1.0 Introduction
Welcome to the PCSC Fault Tolerant Controller, the newest generation of intelligent access control
systems from PCSC. This manual explains the Fault Tolerant Controller installation and connection to a
network and other Fault Tolerant Controllers. The Fault Tolerant Controller Manual is divided up into six
steps:






Unpacking the Panels
Installing Power
Wiring the Readers
Connecting the Readers to the Dual Door Module (DDM) and Single Door Module (SDM)
Wiring the Door(s)
Communicating with the Fault Tolerant Controller (FTC) and DDM through TCP/IP
Before powering the Fault Tolerant Controller, take a moment to read through this manual. It has been
designed to allow you to move through the installation and programming phase with a minimum of
difficult. Should you require additional guidance during the installation process, call PCSC Technical
Support at (310) 303-3600.
Page 10 of 90
Fault Tolerant Controller Manual
33-10068-001-A
1.1 Theory of Operation
The PCSC Fault Tolerant system is designed differently from the standard access control system in
which PCSC has excelled for 25 years. A standard Host -> Controller -> Reader/Door setup has always
been reliant on each device preceding it to function properly in order to maintain the integrity of the
system. For example, if a controller is to “fail” (lose power or be disconnected from the network), the
readers or door controls connected to those panels will fail to activate. The system can be increasingly
problematic if multiple panels are daisy-chained together via RS-485 or standard LAN network. If a
panel within the chain goes off-line, it will disrupt the connection to the network. Although this
occurrence is rare, it is a weakness within the standard access control architecture.
The Fault Tolerant system was designed with a LAN-based “Active/Active” or “Active/Inactive” system
architecture which compensates for the possibility that a controller may go off-line. If, for any reason, a
primary controller fails, an alternate controller shall automatically take over the duties of the failed
controller. The progression of successors to a faulty controller shall continue to provide security without
any degradation in system operations.
This secure method of operation was accomplished by dividing the duties of the standard panel into two
distinct panel types. The intelligence of a standard controller that is able to function independently from
the Host computer has been assigned to the Fault Tolerant Controller or FTC within the Fault Tolerant
system. The FTC, connected to the network via a LAN connection, performs as the functional brain for
all its subsidiary door modules. There are two types of FTC within the Fault Tolerant system. The first is
a standard independent panel. The second is a rack-mounted FTC which incorporates two FTCs within
its design.
The second type of panel within the Fault Tolerant system is the Door Module. The Fault Tolerant
system has two types of door modules: the Single Door Module (SDM) and the Dual Door Module
(DDM). The door module is a dumb device that communicates all door and reader activity to the FTC
and executes any instructions commanded. FTCs and door modules are connected via the network, not
a hard-wired cable, so that the architecture of the Fault Tolerant system can respond immediately to any
panel failure.
Page 11 of 90
Fault Tolerant Controller Manual
33-10068-001-A
1.1.1. Redundancy
The key to the FTC within a Fault Tolerant network is redundancy. No FTC should function
independently within a PCSC Fault Tolerant system. Multiple FTCs within a network allow a secondary
FTC to “fill-in” if a door module’s primary FTC goes off-line. Therefore, a Fault Tolerant system will only
ever fail at the level of a single door module, and not affect the system as a whole.
This can be illustrated by the following scenario. Assume four panels (FTCs 1 – 4) are connected via the
network. Each panel is able to see the connected FTCs on the network, and will display a constant scroll
of the panels to which it is connected. Also connected to the network is DDM 26, which has been
assigned to FTC 1. Within the scroll of FTC 1, DDM 26 will also appear. Other FTC panels will not see
DDM 26, as DDM 26 will only being attempt to connect to FTC 1.
If FTC 1 goes off-line, the system needs to adapt. In a standard access control scenario, FTC 1 would
go off-line, as would DDM 26, and the readers/doors connected to it. Within the Fault Tolerant system,
DDM 26 will immediately search out the secondary FTC within its programming, in this case, FTC 2. The
FTC 2 scroll will show that it is now connected to DDM 26. Additionally, FTC 1 will no longer appear on
the scroll on the other FTCs.
Page 12 of 90
Fault Tolerant Controller Manual
33-10068-001-A
2.0 Installing Power
2.1 Installing Power to the FTC and DDM
The Fault Tolerant Controller (FTC) and Dual Door Module (DDM) can be powered via two different
methods:


Power Over Ethernet (POE), or
PCSC Power Supply
Shown below are the 3.0A PCSC power supplies.
2.1.1 Installing Power- 3.0 Amp
Should the FTC or DDM be powered by a PCSC power supply, the panel will be connected to a 12VDC
power supply at P2 at midlevel along the board. Wiring will be set at the factory. Disconnect power
mains from the supply before making any adjustments to the wiring.
For installation, refer to the ESD SPS-3.6M2E Power Supply installation instructions (P/N: SPS36
Instructions Rev: 04/15/02).
NOTE: Power supply cable connections are non power-limited outputs. For more information,
please refer to the power supply installation manual.
Page 13 of 90
Fault Tolerant Controller Manual
33-10068-001-A
2.1.2 PCSC 3.0 Amp Power Supply
Page 14 of 90
Fault Tolerant Controller Manual
33-10068-001-A
2.2 Installing Power SDM
The SDM can be powered via two different methods:


Power Over Ethernet (POE)
PCSC Power Supply
Shown below are the 3.0A PCSC power supplies.
2.2.1 Installing Power- 3.0 Amp
Should the SDM be powered by an independent power supply, the panel will be connected to a 12VDC
power supply at P2 at midlevel along the board. Wiring will be set at the factory. Disconnect power
mains from the supply before making any adjustments to the wiring.
For installation, refer to the ESD SPS-3.6M2E Power Supply installation instructions (P/N: SPS36
Instructions Rev: 04/15/02).
NOTE: Power supply cable connections are non power-limited outputs. For more information,
please refer to the power supply installation manual.
Page 15 of 90
Fault Tolerant Controller Manual
33-10068-001-A
2.2.2 PCSC 3.0 Amp Power Supply
Page 16 of 90
Fault Tolerant Controller Manual
33-10068-001-A
2.3 Resetting a Panels to Default Values
This feature will be available in the future.
Page 17 of 90
Fault Tolerant Controller Manual
33-10068-001-A
3.0 Wiring the Readers
PCSC has designed its products to withstand most inductive voltage spikes without effect. However,
some noise found in power supplies and door strikes, in addition to static discharge, may cause the
control unit to momentarily shut down, lockup, or in extreme cases, to become damaged. Unexplained
lockups and intermittent system behavior are common symptoms of static or noise problems. If cycling
power will remedy your problem, carefully follow these instructions:
1. Install Metal Oxide Varistors (MOVs) (Siemens S10K30 or equivalent) at each Door Strike. When
installed, they will suppress the feedback coming from door strikes, and limit most errors.
2. Readers should be properly earth-grounded for uninterrupted reads. Please be aware that operation
is affected by the amount of static present during certain times of the year.
3. Properly grounding all readers and hardware, in addition to suppressing noise in the peripheral
equipment, should allow for many problem free years of use with PCSC products.
4. In addition, PCSC recommends using a separate filtered, electronically regulated output, switchable
power supply for door strikes.
5. Before installing the reader, please read the following instructions. Damage may occur if this is
disregarded.
6. Installation must meet all local, state, and federal regulations and codes for electrical installation. If
these codes conflict with the installation methods described in this manual, please call your service
representative.
Page 18 of 90
Fault Tolerant Controller Manual
33-10068-001-A
3.1 Grounding the Readers
Do not route data and power cables in the same conduit. Crosstalk and transmission of electrical noise
may result. The controller will become damaged if the power cable grounds to the data cable.
NOTE: High Voltage and Low Voltage wiring must be routed separately and
maintain a minimum spacing of 0.25 inches.
3.2 Properly Routing the Cables
Each cable has a set of drain lines that can be attached on the Host or controller end of the cable to any
screws mounted in the optional enclosures. If other non-metallic enclosures are used for controller
housing, ensure that an alternative source for earth grounding is available.
3.3 Grounding the Power and Data Lines
Each cable has a set of drain lines that can be attached on the Host or controller end of the cable to any
screws mounted in the optional enclosures. If other non-metallic enclosures are used for controller
housing, ensure that an alternative source for earth grounding is available.
3.3.1 Procedure
1. At the Reader side, it is important to be aware of both the static generated from the user end as well
as electrical grounding from the data and power cabling. If at all possible, the reader mounting plate
should be attached to a grounded junction box or to another source, if the junction box is nonmetallic. This alleviates the possible damage caused by static electricity.
NOTE Leave the drain line taped back and floating at the reader site.
2. If grounding locally is not possible, connect drain wires to the provided Electro Static Discharge
(ESD) hardware at the Controller side (enclosure) or to earth grounded conduit. As each reader port
is progressively farther away from the ESD hardware location, allow for enough drain line to reach
the ESD hardware on the controller end of the cable. Allow enough strain relief to avoid
touching other circuitry or creating excessive tension.
NOTE: High Voltage and Low Voltage wiring must be routed separately and
maintain a minimum spacing of 0.25 inches.
3. On a permanently connected product, a terminal intended solely for the connection of an equipment
grounding conductor shall be capable of securing a conductor of the size suitable for the particular
application in accordance with the National Electrical Code, ANSI/NFPA 70-1993.
4. On a permanently connected product, a wire binding screw intended for the connection of an
equipment grounding conductor shall have a green colored head that is hexagonal, slotted, or both.
A pressure wire connector intended for connection of such a conductor shall be plainly identified
such as by being marked “G” “GR,” “GROUND,” or “GROUNDING,” or the like, or by a marking on a
wiring diagram provided on the product. The wire binding screw or pressure wire connector shall be
secured to the frame or enclosure of the product and shall be located so that it is unlikely to be
Page 19 of 90
Fault Tolerant Controller Manual
33-10068-001-A
removed during service operations such as replacing fuses, resetting manual-reset devices, or the
like.
5. If a pressure wire connector intended for grounding is located where it could be mistaken for a
neutral conductor of a ground supply, it shall be identified by a marking ”EQUIPMENT GROUND“ or
with a green color identification, or both.
6. On a permanently connected product, the surface of an insulated lead intended solely for the
connection of an equipment grounding conductor shall be finished in a continuous green color or a
continuous green color with one or more yellow stripes, and no other lead shall be so identified.
3.4 Grounding the Pin Pad or Reader
3.4.1 Procedure
1. Orient the mounting plate so that the protruding ears are on top and facing the back of the reader or
PIN Pad. Attach the mounting plate to the junction box using two screws. The mounting plate should
be earth ground either to a ground junction box or directly to an earth ground source (especially if
the junction box is not metal).
2. Connect the cable to the rear of the reader. Secure the shield drain lines to one of the grounding
screws in the Fault Tolerant Controller enclosure or other appropriate location.
3. Place mounting holes on the back of the reader over the latches on the mounting plate, and then
position the unit so that the cover is flush with the mounting plate.
4. Secure the unit to the mounting plate by inserting the special security fastener through the hole in
the bottom of the reader. Tighten it using the security driver.
3.4.2 Grounding the Reader Mullion Mount
The reader may be attached to a glass or door mullion separator (either vertically or horizontally) by
using the Mullion Bracket Adapter Kits (04-10170-001 for horizontal mounting or 04-10171-001 for
vertical mounting).
3.4.2.1 Procedure
1. At the Fault Tolerant Controller end, secure the drain lines to one of the ESD grounding screws in
the Fault Tolerant Controller box. At the reader end, leave the drain line floating. It is recommended
that the mullion adapter be affixed to an earth ground or to the incoming conduit.
2. Mount the reader to the J-box or mullion bracket.
Page 20 of 90
Fault Tolerant Controller Manual
33-10068-001-A
4.0 Reader Connections to the DDM
4.0.1. Reader Disconnect Resistors
If an external power supply and a reader disconnect feature is required, place an appropriately sized
resistor (not supplied) at the reader. However, if the reader is using an external power supply, then the
resistor should be installed at the reader port on the panel.
If an external power supply is required, a resistor can be placed at the reader port to eliminate the
Reader Disconnect message in the logger.
NOTE: For use in the following diagrams, resistors are shown connected to the boards.
However, for best operation, resistors should be placed where they are the most
effective.
NOTE: A second reader is not available with the SDM at this time.
Page 21 of 90
Fault Tolerant Controller Manual
33-10068-001-A
4.1 Reader Connections: PR233 MiniProx / PR-733/732
NOTE: The AWID readers (PR733
and PRK732) have a brown
LED wire.
Page 22 of 90
Fault Tolerant Controller Manual
33-10068-001-A
4.2 Reader Connections: PR-234 / PRK-234 ProxPro / PR736 / PRK-736
NOTE: The AWID readers (PR736
and PRK736) have a brown
LED wire.
Page 23 of 90
Fault Tolerant Controller Manual
33-10068-001-A
4.3 Reader Connections: PR-235 MaxiProx / PR-735
NOTE: The AWID readers (PR735)
have a brown LED wire.
Page 24 of 90
Fault Tolerant Controller Manual
33-10068-001-A
4.4 Reader Connections: Sensor Wiegand
Page 25 of 90
Fault Tolerant Controller Manual
33-10068-001-A
4.5 Reader Connections: VeriProx / V-Pass/
Page 26 of 90
Fault Tolerant Controller Manual
33-10068-001-A
4.6 Reader Connections: iClass
Page 27 of 90
Fault Tolerant Controller Manual
33-10068-001-A
4.7 Reader Connections: Xceed ID SP632/SP632M/SP633/SP635/SPK635
Page 28 of 90
Fault Tolerant Controller Manual
33-10068-001-A
4.8 Reader Connections: Biometric
Page 29 of 90
Fault Tolerant Controller Manual
33-10068-001-A
5.0 Wiring the Door(s)
Step 1.
When power is interrupted from the Fault Tolerant Controller, the door relay de-energizes and
continuity (conduction path) exists between the Common (Com.) and Normally Closed (N.C.)
relay contacts. Should this loss-of-power situation arise, it must be determined whether the
door(s) controlled by the Fault Tolerant Controller will become unlocked (or a Fail-Safe
environment), or locked (or a Fail-Secure environment).
Step 2.
Refer to the two types of door hardware below and the circuit conditions that coincide with the
state of the locks.
Step 3.
Case A.
Door Strike hardware requires continuity to unlock (for strikes that require power to
lock, follow the outline given for maglocks). This is provided by a closed circuit
condition (Normally Closed [N.C.]).
Case B.
Door Strike hardware does NOT require continuity to lock (for strikes that require
power to lock, follow the outline given for maglocks). This is provided by an open
circuit condition (Normally Open [N.O.]).
Case C.
Magnetic lock hardware requires continuity to lock. This is provided by a closed
circuit condition (Normally Closed [N.C.]).
Case D.
Magnetic lock hardware does NOT require continuity to unlock.
This is provided by an open circuit condition (Normally Open [N.O.]).
For Fail-Safe operation, wire the appropriate door lock hardware to accommodate an
unlocked condition upon interruption of Fault Tolerant Controller power. This is implemented
by:


For door strikes, wire between the Common and Normally Closed Door Relay contacts.
For Magnetic Locks, wire between the Common and Normally Open Door Relay
contacts.
For Fail-Secure operation, wire the appropriate door lock hardware to accommodate a locked
condition upon interruption of Fault Tolerant Controller power. This is implemented by:


For door strikes, wire between the Common and Normally Open Door Relay contacts.
For Magnetic Locks, wire between the Common and Normally Closed Door Relay
contacts.
NOTE For both conditions (Fail Safe and Fail Secure) it is presumed that Lock Power is battery
backed.
Step 4. Next page
Page 30 of 90
Fault Tolerant Controller Manual
33-10068-001-A
Step 4.
Program the quiescent (INACTIVE) state of the door output relay to provide a locked door
state. For Fail-Safe environments, the quiescent state of the door output relay should be
ENERGIZED. For Fail-Secure environments, it should be DE-ENERGIZED.
Consult the LiNC-NXG User Manual’s Door Overview/Hardware section for programming
information.
Open Collector Output: Open collector outputs are designed to drive an external relay. This
technique can be used to control devices which exceed the relay capacity of those on board the Fault
Tolerant Controller. The open collector outputs are capable of 100 mA current @ 12VDC.
Page 31 of 90
Fault Tolerant Controller Manual
33-10068-001-A
5.1 Wiring the Panel in a Fail-Safe Environment
5.1.1 Fail Safe - DDM
Page 32 of 90
Fault Tolerant Controller Manual
33-10068-001-A
5.1.1 Fail Safe - SDM
Page 33 of 90
Fault Tolerant Controller Manual
33-10068-001-A
5.2 Wiring Panel in a Fail-Secure Environment
5.2.1 Fail-Secure - DDM
Page 34 of 90
Fault Tolerant Controller Manual
33-10068-001-A
5.2.2 Fail-Secure - SDM
Page 35 of 90
Fault Tolerant Controller Manual
33-10068-001-A
5.3 LED Arrays
5.3.1 Using the Seven Segment LED Array
TBD
5.3.2 Status Chart for All LED Arrays
TBD
5.4 Installing Noise Suppression Devices
To install a MOV to suppress noise and avoid problems related to spikes, follow the instructions below
and refer to the diagrams on the following pages.
5.4.1 Procedure
The most effective location for a suppression device is at the source; in this case, at the door strike.
1. Remove the strike-locking device and find the wire connector that attaches the lock wires to the
lock.
2. Install an MOV (Siemens S10K30 or equivalent) in parallel with the load. The MOV is a nonpolarized device and will work with both AC and DC locks.
NOTE Use an additional MOV if you experience further noise at the strike.
NOTE For further protection on DC units, a reverse biased diode may be installed
(We suggest types 1N4004 to 1N4007 be used) also in parallel with the load.
3. Note the wiring set-up of your particular system. Connections can be made either to the
“normally open” (fail secure) contact or to the “normally-closed” (fail-safe) configuration
whereby an isolation relay is used and a MOV is added for noise suppression.
Page 36 of 90
Fault Tolerant Controller Manual
33-10068-001-A
5.5 Reset button
In situations where a panel is malfunctioning or a panel has been re-programmed, (see Section 7.0) it
may be necessary to reset a panel to return it to its programmed state.
5.5.1 Reset button on the FTC and DDM
Page 37 of 90
Fault Tolerant Controller Manual
33-10068-001-A
5.5.2 Reset Button on the SDM
Page 38 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.0 Communicating with the FTC, DDM and SDM through TCP/IP
Communication with each Fault Tolerant Controller is based on three forms of identification:
 The panels name (optional)
 The panel’s unique IP Address
 The panel’s DIPswitch number
6.0.1 Connecting to a Panel via TCP/IP
Programming of the FTC, DDM and SDM controllers is done directly through the TCP/IP and a standard
internet browser. When communicating with a panel via TCP/IP, it is possible to do the following:
 Set IP Address and Name
 Configure a network of connected FTCs
 Specify a primary FTC (DDM and SDM only)
 Specify secondary FTCs (DDM and SDM only)
 Specifying the allowable Hosts and Workstations within a network
 Set the panel’s Time Zone
 Set the DIPswitch number (SDM Only)
 Changing the password
Page 39 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.1 Programming the FTC
6.1.1 Connecting to a FTC
All FTCs are factory set with an IP Address of 192.168.168.42 as the default IP.
NOTE: Default NTP server IP Address is 192.168.168.20.
1.
2.
3.
4.
5.
Connect a computer to a network switch via a CAT5 cable.
Connect the panel to a switch via a CAT5 cable.
Open an internet browser, such as Internet Explorer.
Type 192.168.168.42 into the address bar.
A security window will appear. The defaults are:
 User Name:
admin
 Password:
PYMTF
6. Press the OK button.
Page 40 of 90
Fault Tolerant Controller Manual
33-10068-001-A
7. The PCSC FTController screen will appear. All necessary programming options will be available
from this screen.
NOTE: Not all features listed are for standard usage. Only those that are
discussed in this section are for standard use.
Page 41 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.1.2 Setting the Name and IP Address of a FTC
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.42 into the address bar. The PCSC FTController screen will appear.
4. From the PCSC FTController screen, select Configure Primary Networks. The following screen
will appear.
5. In the Host Name text box, insert the proper name for the panel.
6. In the IP address text box, insert the proper IP address.
7. In the Gateway IP, Subnet address, NTP server IP, TFTP server IP, insert the proper IP
Addresses.
8. Press the Apply button to set up.
Page 42 of 90
Fault Tolerant Controller Manual
33-10068-001-A
9. A Saving configuration page will appear. Press the home link to return to the main PCSC
FTController page.
NOTE: All panels within a network must have separate IP addresses. It is recommended
that panels within the same clique have IP addresses that are in some way
aligned.
NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4
for proper resetting procedures.
Page 43 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.1.3 Configure a Network of Connected FTCs
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.42 into the address bar. The PCSC FTController screen will appear.
4. From the PCSC FTController screen, select Edit Configuration Files. The following screen will
appear.
5. Select Hydra configuration from the drop-down menu.
6. Press the Edit button.
Page 44 of 90
Fault Tolerant Controller Manual
33-10068-001-A
Within the Hydra configuration screen, it is possible to edit which FTCs the current panel will be able to
see on the network. Only FTCs can see other FTCs. It is not necessary for an FTC to see DDM or an
SDM.
7. Change or add the IP address of the peer FTCs on the network. All FTCs that can see each
other will form a “clique”.
8. Once all FTCs have been entered, press the Save File button.
NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4
for proper resetting procedures.
NOTE: A panel’s own IP address must be listed within the Hydra configuration screen.
Page 45 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.1.4 Setting the Time Zone for a Particular Panel
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.42 into the address bar. The PCSC FTController screen will appear.
4. From the PCSC FTController screen, select Edit Configuration Files. The following screen will
appear.
5. Select Time zone from the drop-down menu.
6. Press the Edit button.
Page 46 of 90
Fault Tolerant Controller Manual
33-10068-001-A
The established time zone for the panel will be listed.
7. Change the time zone of the panel, if necessary.
8. Once the range has been entered, press the Save File button.
NOTE: A network can have multiple cliques with independent ranges that allow for
additional growth without impacting on its neighbors.
NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4
for proper resetting procedures.
6.1.4.1 North American Time Zones
NST3NDT
AST4ADT
EST5EDT
CST6CDT
MST7MDT
PST8PDT
AKST9AKDT
HAST10HADT
Page 47 of 90
Newfoundland Standard Time/ Newfoundland Daylight Time
Atlantic Standard Time/ Atlantic Daylight Time
Eastern Standard Time/ Eastern Daylight Time
Central Standard Time/ Central Daylight Time
Mountain Standard Time/ Mountain Daylight Time
Pacific Standard Time/ Pacific Daylight Time
Alaska Standard Time/ Alaska Daylight Time
Hawaii-Aleutian Standard Time/ Hawaii-Aleutian Daylight Time
Fault Tolerant Controller Manual
33-10068-001-A
6.1.5 Changing the Password
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.42 into the address bar. The PCSC FTController screen will appear.
4. From the PCSC FTController screen, select Change password.
Page 48 of 90
Fault Tolerant Controller Manual
33-10068-001-A
The following screen will appear.
5. Enter the new username.
6.
7.
8.
9.
Enter the old password.
Enter the new password.
Confirm the new password.
Press the Apply button. The system will store the updated username and password until
NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4
for proper resetting procedures.
Page 49 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.1.6 Specifying the IP Address to Allow FT configuration access
10. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
11. Open an internet browser, such as Internet Explorer.
12. Type 192.168.168.42 into the address bar. The PCSC FTController screen will appear.
13. From the PCSC FTController screen, select Edit Configuration Files. The following screen will
appear.
14. Select /etc/hosts.allow from the drop-down menu.
15. Press the Edit button.
Page 50 of 90
Fault Tolerant Controller Manual
33-10068-001-A
The Hosts Allow screen allow access of the IE computer to edit the FT configuration.. The default is for
ALL : ALL, which would allow any networked computer to edit configuration.
NOTE: Only CPUs with a NIC card can access the LiNC-NXG as a host or workstation.
16. To limit the number of computers that can change the FT configuration add the IP address of
each PC.
Page 51 of 90
Fault Tolerant Controller Manual
33-10068-001-A
17. Once the IP Address(es) has been entered, press the Save File button.
NOTE: All changes to the panel are temporary until the panel is RESET. Push Reset
Button as seenin Section 5.4.
Page 52 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.2 Programming the Dual Door Module
6.2.1 Connecting to the DDM
All Dual Door Modules are factory set with an IP Address of 192.168.168.52 as the default IP.
1.
2.
3.
4.
5.
Connect a computer to a network switch via a CAT5 cable.
Connect the panel to a switch via a CAT5 cable.
Open an internet browser, such as Internet Explorer.
Type 192.168.168.52 into the address bar.
A security window will appear. The defaults are:
 User Name:
admin
 Password:
PYMTF
6. Press the OK button.
Page 53 of 90
Fault Tolerant Controller Manual
33-10068-001-A
7. The PCSC DualDoorModule screen will appear. All necessary programming options will be
available from this screen.
NOTE: Not all features listed are for standard usage. Only those that are
discussed in this section are for standard use.
Page 54 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.2.2 Setting the Name and IP Address of a DDM
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.52 into the address bar. The PCSC DualDoorModule screen will appear.
4. From the PCSC DualDoorModule screen, select Configure Primary Networks. The following
screen will appear.
5. In the Host Name text box, insert the proper name for the panel.
6. In the IP address text box, insert the proper IP address.
7. In the Gateway IP, Subnet address, NTP server IP, TFTP server IP, insert the proper IP
Addresses.
8. Press the Apply button to set up.
Page 55 of 90
Fault Tolerant Controller Manual
33-10068-001-A
9. A Saving configuration page will appear. Press the home link to return to the main PCSC
DualDoorModule page.
NOTE: All panels within a network must have separate IP addresses. It is recommended
that panels within the same clique have IP addresses that are in some way
aligned.
NOTE: All changes to the panel are temporary until the panel is RESET. Push the Reset
button as seen on Section 5.4.
Page 56 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.2.3 Configure the DDM’s Primary FTC and Secondary FTCs
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.52 into the address bar. The PCSC DualDoorModule screen will appear.
4. From the PCSC DualDoorModule screen, select Edit Configuration Files. The following screen
will appear.
5. Select Hydra configuration from the drop-down menu.
6. Press the Edit button.
Page 57 of 90
Fault Tolerant Controller Manual
33-10068-001-A
The following screen will appear. Each DDM must have a Primary server (FTC). Additionally, a DDM
should have one (or more) Secondary server(s) in order of listed hierarchy. A DDM will only look for
the expected FTCs and will never look for the other DDMs and SDMs on the network.
7. Change the IP Address for the Primary server.
8. Change or add the IP Address(es) for the Secondary server.
9. Once all IP Addresses of the appropriate FTCs have been entered, press the Save File button.
NOTE: All changes to the panel are temporary until the panel is RESET. Push the reset
button as seen in Section 5.4.
Page 58 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.2.4 Setting the Time Zone for a Particular Panel
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.52 into the address bar. The PCSC DualDoorModule screen will appear.
4. From the PCSC DualDoorModule screen, select Edit Configuration Files. The following screen
will appear.
5. Select Time zone from the drop-down menu.
6. Press the Edit button.
Page 59 of 90
Fault Tolerant Controller Manual
33-10068-001-A
The established time zone for the panel will be listed.
7. Change the time zone of the panel, if necessary.
8. Once the range has been entered, press the Save File button.
NOTE: A network can have multiple cliques with independent ranges that allow for
additional growth without impacting on its neighbors.
NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4
for proper resetting procedures.
6.2.4.1 North American Time Zones
NST3NDT
AST4ADT
EST5EDT
CST6CDT
MST7MDT
PST8PDT
AKST9AKDT
HAST10HADT
Page 60 of 90
Newfoundland Standard Time/ Newfoundland Daylight Time
Atlantic Standard Time/ Atlantic Daylight Time
Eastern Standard Time/ Eastern Daylight Time
Central Standard Time/ Central Daylight Time
Mountain Standard Time/ Mountain Daylight Time
Pacific Standard Time/ Pacific Daylight Time
Alaska Standard Time/ Alaska Daylight Time
Hawaii-Aleutian Standard Time/ Hawaii-Aleutian Daylight Time
Fault Tolerant Controller Manual
33-10068-001-A
6.2.5 Changing the Password
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.52 into the address bar. The PCSC DualDoorModule screen will appear.
4. From the PCSC DualDoorModule screen, select Change password.
Page 61 of 90
Fault Tolerant Controller Manual
33-10068-001-A
The following screen will appear.
5. Enter the new username.
6.
7.
8.
9.
Enter the old password.
Enter the new password.
Confirm the new password.
Press the Apply button. The system will store the updated username and password until
NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4
for proper resetting procedures.
Page 62 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.2.6 Specifying the allowable Hosts and Workstations within a network
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.52 into the address bar. The PCSC DualDoorModule screen will appear.
4. From the PCSC DualDoorModule screen, select Edit Configuration Files. The following screen
will appear.
5. Select /etc/hosts.allow from the drop-down menu.
6. Press the Edit button.
Page 63 of 90
Fault Tolerant Controller Manual
33-10068-001-A
The Hosts Allow screen will give the range of all CPUs allowed to access the LiNC-NXG panels as hosts
or workstations. The default is for ALL : ALL, which would allow any networked computer to function as
a host or workstation.
NOTE: Only CPUs with a NIC card can access the LiNC-NXG as a host or workstation.
7. To limit the number of computers that can function as hosts or workstations, change or add the
IP address of each CPU.
8. Once the IP Address(es) has been entered, press the Save File button.
NOTE: A network can have multiple cliques with independent ranges that allow for
additional growth without impacting its neighbors.
NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4
for proper resetting procedures.
Page 64 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.3 Programming the Single Door Module
6.3.1 Connecting to the SDM
All Dual Door Modules are factory set with an IP Address of 192.168.168.62 as the default IP.
1.
2.
3.
4.
5.
Connect a computer to a network switch via a CAT5 cable.
Connect the panel to a switch via a CAT5 cable.
Open an internet browser, such as Internet Explorer.
Type 192.168.168.62 into the address bar.
A security window will appear. The defaults are:
 User Name:
admin
 Password:
PYMTF
6. Press the OK button.
Page 65 of 90
Fault Tolerant Controller Manual
33-10068-001-A
7. The PCSC SingleDoorModule screen will appear. All necessary programming options will be
available from this screen.
NOTE: Not all features listed are for standard usage. Only those that are
discussed in this section are for standard use.
Page 66 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.3.2 Setting the Name and IP Address of a SDM
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.62 into the address bar. The PCSC SingleDoorModule screen will appear.
4. From the PCSC SingleDoorModule screen, select Configure Primary Networks. The following
screen will appear.
5. In the Host Name text box, insert the proper name for the panel.
6. In the IP address text box, insert the proper IP address.
7. Press the Apply button to set up.
NOTE: All panels within a network must have separate IP addresses. It is recommended
that panels within the same clique have IP addresses that are in some way
aligned.
NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4
for proper resetting procedures.
NOTE: It is not recommended to change the NTP and TFTP server IP address without
specific knowledge.
Page 67 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.3.3 Configure the SDM’s Primary FTC and Secondary FTCs
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.62 into the address bar. The PCSC SingleDoorModule screen will appear.
4. From the PCSC SingleDoorModule screen, select Edit Configuration Files. The following
screen will appear.
5. Select Hydra configuration from the drop-down menu.
6. Press the Edit button.
Page 68 of 90
Fault Tolerant Controller Manual
33-10068-001-A
The Hydra Configuration screen will appear. Each SDM must have a Primary server (FTC).
Additionally, a SDM should have one (or more) Secondary server(s) in order of listed hierarchy. An
SDM will only look for the expected FTCs and will never look for the other DDMs and SDMs on the
network.
7. Change the IP address for the Primary server.
8. Change or add the IP Address(es) for the Secondary server.
9. Once all IP addresses of the appropriate FTCs have been entered, press the Save File
button.
NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4
for proper resetting procedures.
Page 69 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.3.4 Changing the Password
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.62 into the address bar. The PCSC SingleDoorModule screen will appear.
4. From the PCSC SingleDoorModule screen, select Change password.
Page 70 of 90
Fault Tolerant Controller Manual
33-10068-001-A
The following screen will appear.
5. Enter the new username.
6.
7.
8.
9.
Enter the old password.
Enter the new password.
Confirm the new password.
Press the Apply button. The system will store the updated username and password until
NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4
for proper resetting procedures.
Page 71 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.3.5 Setting the Time Zone for a Particular Panel
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.62 into the address bar. The PCSC SingleDoorModule screen will appear.
4. From the PCSC SingleDoorModule screen, select Edit Configuration Files. The following
screen will appear.
5. Select Time zone from the drop-down menu.
6. Press the Edit button.
The established time zone for the panel will be listed.
7. Change the time zone of the panel, if necessary.
8. Once the range has been entered, press the Save File button.
NOTE: A network can have multiple cliques with independent ranges that allow for
additional growth without impacting on its neighbors.
NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4
for proper resetting procedures.
Page 72 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.3.5.1 North American Time Zones
NST3NDT
AST4ADT
EST5EDT
CST6CDT
MST7MDT
PST8PDT
AKST9AKDT
HAST10HADT
Page 73 of 90
Newfoundland Standard Time/ Newfoundland Daylight Time
Atlantic Standard Time/ Atlantic Daylight Time
Eastern Standard Time/ Eastern Daylight Time
Central Standard Time/ Central Daylight Time
Mountain Standard Time/ Mountain Daylight Time
Pacific Standard Time/ Pacific Daylight Time
Alaska Standard Time/ Alaska Daylight Time
Hawaii-Aleutian Standard Time/ Hawaii-Aleutian Daylight Time
Fault Tolerant Controller Manual
33-10068-001-A
6.3.6 Setting the Panel Number for the SDM
Because there is no DIPswitch within the SDM, a Panel number (separate from the IP Address) needs
to be assigned to the SDM for use with NXG.
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type 192.168.168.62 into the address bar. The PCSC SingleDoorModule screen will appear.
4. From the PCSC SingleDoorModule screen, select Change Unit number. The following screen
will appear.
5. A Unit configuration screen for the panel will appear. Select the proper Unit (or Panel)
number for use with NXG.
6. Press the Apply button.
Page 74 of 90
Fault Tolerant Controller Manual
33-10068-001-A
7. A confirmation screen will appear. If it is correct, press the Save File button.
NOTE: All changes to the panel are temporary until the panel is RESET. See Section 5.4
for proper resetting procedures.
Page 75 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.3.7 Specifying the allowable Hosts and Workstations within a network
1. Confirm that the computer and the appropriate panel are connected through a functioning
switch.
2. Open an internet browser, such as Internet Explorer.
3. Type192.168.168.62 into the address bar. The PCSC SingleDoorModule screen will appear.
4. From the PCSC SingleDoorModule screen, select Edit Configuration Files. The following
screen will appear.
5. Select /etc/hosts.allow from the drop-down menu.
6. Press the Edit button.
Page 76 of 90
Fault Tolerant Controller Manual
33-10068-001-A
The Hosts Allow screen will give the range of all CPUs allowed to access the LiNC-NXG panels as hosts
or workstations. The default is for ALL : ALL, which would allow any networked computer to function as
a host or workstation.
NOTE: Only CPUs with a NIC card can access the LiNC-NXG as a host or workstation.
1. To limit the number of computers that can function as hosts or workstations, change or add the
IP address of each CPU.
2. Once the IP Address(es) has been entered, press the Save File button.
NOTE: A network can have multiple cliques with independent ranges that allow for
additional growth without impacting its neighbors.
NOTE: All changes to the panel are temporary until the panel is RESET. See Section 6.4
for proper resetting procedures.
Page 77 of 90
Fault Tolerant Controller Manual
33-10068-001-A
6.4 DIPswitch Addressing
Panels will also need to have a unique DIPswitch address to function properly with the LiNC-NXG
network. It should be noted that the SDM does not have a DIPswitch. It is necessary to program the
DIPswitch via the TCP/IP programming as noted in Section 6.3.6.
6.4.1 Location of the DIPswitch on the FTC and DDM
Page 78 of 90
Fault Tolerant Controller Manual
33-10068-001-A
7.4.2 DIPswitching the Panel Address (1-63)
The dipswitch is located at SW1, on the left of the board. There are eight switches. For the binary
number one (1), flip the switch to the left. For zero (0), flip the switch to the right. The address in 10+ will
be in Hexadecimal format.
Page 79 of 90
Fault Tolerant Controller Manual
33-10068-001-A
7.4.3 Software Addressing of the SDM
As the SDM does not have a DIPswitch, the SDM Address must be set via the TCP/IP setup. Please
refer to Section 6.3.6 for proper configuration.
Page 80 of 90
Fault Tolerant Controller Manual
33-10068-001-A
8.0 Status Lights and Dealing with Communication Errors
8.1 LED and 7 Segment LED Communication
TDB
8.2 Communication Errors
8.2.1 Communication Errors – FTC
Message at the PC
What to Do
FTC is not responsive
Verify the following:
1. The red DC Power Indicator LED is ON.
2. Verify that the ID number corresponds to the correct panel.
(Check settings of switches at SW1).
3. Check LAN connection.
4. Remove the Battery for 5 minutes. Reinsert battery and
reset panel.
8.2.1.1 LED Fatal Error Display Codes
TBD
8.2.2 Communication Errors - DDM
DDM is not responsive
Verify the following:
1. The red DC Power Indicator LED is ON.
2. Verify that the ID number corresponds to the correct panel.
(Check settings of switches at SW1).
3. Check LAN connection.
4. Remove the Battery for 5 minutes. Reinsert battery and
reset panel.
8.2.2.1 LED Fatal Error Display Codes
TBD
Page 81 of 90
Fault Tolerant Controller Manual
33-10068-001-A
8.2.3 Communication Errors - SDM
SDM is not responsive
Verify the following:
1. The red DC Power Indicator LED is ON.
2. Verify that the ID number corresponds to the correct panel.
(Check settings of switches at SW1).
3. Check LAN connection.
4. Remove the Battery for 5 minutes. Reinsert battery and
reset panel.
8.2.3.1 LED Fatal Error Display Codes
TBD
8.3 Sense Inputs for the DDM and SDM
TBD
Page 82 of 90
Fault Tolerant Controller Manual
33-10068-001-A
8.4 User Selectable Options
TBD
Page 83 of 90
Fault Tolerant Controller Manual
33-10068-001-A
9.0 Appendix A - FTC Specifications
9.1 Fault Tolerant Controller Features – FTC
2 Auxiliary Powered Outputs
1 Supervised Tamper Sense Input & 1 Battery Sense
LINUX Operating System
Battery Backed Clock Calendar
Flash RAM
8MB (64SDRAM)
Battery Backed SRAM
2MB (up to 16MB)
LEDs for:
Power, alarm, on-line diagnostics
Tamper detect (S13)
Electrical Ratings
Type of Communications
160 mA @ +12 Vdc
LAN
9.1.1 System Capacities
Cardholder Capacity:
History Transactions:
20,000 – 200,000
20,000 – 200,000
9.1.2 Electrical Ratings
Power:
Draw:
12VDC
160mA @ 12V
Page 84 of 90
Fault Tolerant Controller Manual
33-10068-001-A
9.2 Fault Tolerant Controller Features – Dual Door Module
2 Auxiliary Powered Outputs
1 Supervised Tamper Sense Input & 1 Battery Sense
2 Reader Ports:
-5-wire Wiegand interface
2 Form C Door Strike Outputs (continuous power)
2 Door Left Open Outputs (or 2 External Shunt Options)
2 Supervised Door Senses
2 Supervised Request to Exit Inputs
4 User Configured Sense Inputs
Battery Backed Clock Calendar
Flash RAM
8MB
SDRAM
16MB
LEDs for:
Power, alarm, on-line diagnostics
Reader Data [Error code, door status]
Tamper detect
Electrical Ratings
Type of Communications
160 mA @ +12 Vdc
LAN
9.2.1 Electrical Ratings
Power:
Draw:
Relay Contacts
12VDC
160mA @ 12V
2 A @ 24 VDC
Card Reader Draw:
100mA @ 12 VDC Max
Page 85 of 90
Fault Tolerant Controller Manual
33-10068-001-A
9.3 Fault Tolerant Controller Features – Single Door Module
2 Auxiliary Powered Outputs
1 Supervised Tamper Sense Input & 1 Battery Sense
1 Reader – 5 Wire Wiegand Reader
1 Form C Door Strike Output
1 Door Left Open Outputs (or 2 External Shunt Options)
1 Supervised Door Senses
1 Request to Exit Input
Battery Backed Clock Calendar
Flash RAM
8MB
SDRAM
32MB
Electrical Ratings
1A @ +12 Vdc
Type of Communications
LAN
9.3.1 Electrical Ratings
Power:
Draw:
Relay Contacts
12VDC
160mA @ 12V
2 A @ 30VDC
Card Reader Draw:
600mA @ 12 VDC
Page 86 of 90
Fault Tolerant Controller Manual
33-10068-001-A
9.4 Cable Requirements and Maximum Lengths
9.4.1 CommunicationType of
Technology
Type of 22awg
Stranded Wire
Maximum Distance
Ethernet
Category 5 cable
To Fault Tolerant Controller
300 feet (100m)
Input Circuits
2-pair, twisted, w/
overall shield
To the DDM or the SDM
500 ft (150m)
Input Circuits
2-pair, twisted, w/
overall shield
To the DDM or the SDM
500 ft (150m)
9.4.1 Readers
5-wire WiegandType of Models
Technology
Type of 22awg
Stranded Wire
Maximum Distance
Max. Distance w/PIN Pad
Reader
3-pair, twisted, w/
overall shield
500 ft.
(192 m)
500 ft.
(192 m)
Use PCSC Cable CBLCOMP (Access Control Composite Cable) for all reader connects.
NOTE All data communications cables must reside in a separate electrical conduit.
Absolutely NO high voltage or AC power cables allowed within data conduits.
Page 87 of 90
Fault Tolerant Controller Manual
33-10068-001-A
9.5 Tool Requirements
Cable Connection Tool
On the FTC or DDM circuit board, a standard screwdriver is required for securing cabling connections.
9.6 Controller Specifications
LEDs and Dipswitches
TBD
Two Seven-Segment LED Display
Error codes are displayed in Hexadecimal format. Refer to the
error code section for listing of codes and their meanings.
Real Time Clock
A real time clock (DS1302) with battery backup is provided for
time of day information.
Power Supply
The FTC and DDM may use either a power supply or be
powered directly via Power Over Ethernet (POE).
If using a power supply the FTC or DDM require +12VDC for all
logic. Relays, output drivers, etc. require a +12VDC power
supply. An on-board DC-DC converter accepts an external
voltage source of 10-26VDC, and converts this unregulated
source to the required +5VDC. For an input voltage range of
10-15 volts, the “+12VDC” converts this voltage source to the
required +12VDC. For more information, please refer to the
ESD power supply installation manual.
Battery Back-up Requirements
Should the FTC or the DDM be installed within an enclosure, a
12 AH battery is recommended as a back-up to the power
supply, because it is the largest battery that will fit in the
enclosure. The battery should be connected to the power
supply charger in accordance with the manufacturer’s
instructions. Refer to ESD SPS-3.6M2E, or SPS-6.5M4 Power
Supply installation instructions (P/N: SPS36instructions Rev:
04/15/02) for determining battery backup size.
NOTE: The Single Door Module is powered directly via Power Over Ethernet
(POE).
Factory Settings
The Fault Tolerant Controller is set at the factory as FTC #1
with an IP Address of 192.168.168.42.
Page 88 of 90
Fault Tolerant Controller Manual
33-10068-001-A
9.7 Maintenance Requirements
The following items require testing and/or maintenance to be performed on the Fault Tolerant Controller
at least once a year.


PCB Back Up Memory Battery Replacement
Power Supply Back Battery Replacement.
9.7.2 Back-Up Memory Battery Replacement
Use an R2032 3V or equivalent battery.
WARNING:
Replacing with the incorrect battery may cause damage to the PCB, and void
warranty.
9.7.3 Power Supply Back Battery Replacement
1. Check battery condition at least once a year.
2. Replace every 3-5 years with UL-recognized sealed lead acid batteries, 12 VDC.
Page 89 of 90
Fault Tolerant Controller Manual
33-10068-001-A
End of Manual
January 2010
Page 90 of 90
Fault Tolerant Controller Manual
33-10068-001-A