* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download Solving the above equation we get
Integrating ADC wikipedia , lookup
Valve RF amplifier wikipedia , lookup
Schmitt trigger wikipedia , lookup
Operational amplifier wikipedia , lookup
Josephson voltage standard wikipedia , lookup
Resistive opto-isolator wikipedia , lookup
Current source wikipedia , lookup
Opto-isolator wikipedia , lookup
Power MOSFET wikipedia , lookup
Power electronics wikipedia , lookup
Voltage regulator wikipedia , lookup
Two-port network wikipedia , lookup
Current mirror wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Standing wave ratio wikipedia , lookup
CHAPTER 2 TRANSMISSION LINE MODELS As we have discussed earlier in Chapter 1 that the transmission line parameters include series resistance and inductance and shunt capacitance. In this chapter we shall discuss the various models of the line. The line models are classified by their length. These classifications are Short line approximation for lines that are less than 80 km long. Medium line approximation for lines whose lengths are between 80 km to 250 km. Long line model for lines that are longer than 250 km. These models will be discussed in this chapter. However before that let us introduce the ABCD parameters that are used for relating the sending end voltage and current to the receiving end voltage and currents. 2.1 ABCD PARAMETSRS Consider the power system shown in Fig. 2.1. In this the sending and receiving end voltages are denoted by VS and VR respectively. Also the currents IS and IR are entering and leaving the network respectively. The sending end voltage and current are then defined in terms of the ABCD parameters as VS AVR BI R I S CVR DI R (2.1) (2.2) From (2.1) we see that A VS VR (2.3) I R 0 This implies that A is the ratio of sending end voltage to the open circuit receiving end voltage. This quantity is dimension less. Similarly, B VS IR (2.4) VR 0 i.e., B, given in Ohm, is the ratio of sending end voltage and short circuit receiving end current. In a similar way we can also define C IS VR mho I R 0 (2.5) 1.31 D IS IR (2.6) VR 0 The parameter D is dimension less. Fig. 2.1 Two port representation of a transmission network. 2.2 SHORT LINE APPROXIMATION The shunt capacitance for a short line is almost negligible. The series impedance is assumed to be lumped as shown in Fig. 2.2. If the impedance per km for an l km long line is z0 = r + jx, then the total impedance of the line is Z = R + jX = lr + jlx. The sending end voltage and current for this approximation are given by VS VR ZI R (2.7) (2.8) IS IR Therefore the ABCD parameters are given by A D 1, B Z and C 0 (2.9) Fig. 2.2 Short transmission line representation. 2.2 MEDIUM LINE APPROXIMATION Medium transmission lines are modeled with lumped shunt admittance. There are two different representations nominal- and nominal-T depending on the nature of the network. These two are discussed below. 2.2.1 Nominal- Representation In this representation the lumped series impedance is placed in the middle while the shunt admittance is divided into two equal parts and placed at the two ends. The nominal- representation is shown in Fig. 2.3. This representation is used for load flow studies, as we shall see later. Also a long transmission line can be modeled as an equivalent -network for load flow studies. 1.32 Fig. 2.3 Nominal- representation. Let us define three currents I1, I2 and I3 as indicated in Fig. 2.3. Applying KCL at nodes M and N we get I s I1 I 2 I1 I 3 I R Y Y Vs VR I R 2 2 (2.10) Again Y Vs ZI 2 VR Z VR I R VR 2 YZ 1VR ZI R 2 (2.11) Substituting (2.11) in (2.10) we get Is Y Y YZ 1VR ZI R VR I R 2 2 2 YZ YZ Y 1VR 1 I R 4 2 (2.12) Therefore from (2.11) and (2.12) we get the following ABCD parameters of the nominal- representation YZ A D 1 2 BZ YZ C Y 1 mho 4 (2.13) (2.14) (2.15) 2.2.1 Nominal-T Representation In this representation the shunt admittance is placed in the middle and the series impedance is divided into two equal parts and these parts are placed on either side of the shunt admittance. The nominal-T representation is shown in Fig. 2.4. Let us denote the midpoint voltage as VM. Then the application of KCL at the midpoint results in 1.33 Fig. 2.4 Nominal-T representation. VS VM V VR YVM M Z 2 Z 2 Rearranging the above equation can be written as VM 2 VS VR YZ 4 (2.16) Now the receiving end current is given by IR VM VR Z 2 (2.17) Substituting the value of VM from (2.16) in (2.17) and rearranging we get YZ YZ Vs 1VR Z 1 I R 2 4 (2.18) Furthermore the sending end current is I S YVM I R (2.19) Then substituting the value of VM from (2.16) in (2.19) and solving YZ I R YVR 1 I R 2 (2.20) Then the ABCD parameters of the T-network are YZ A D 1 2 YZ B Z 1 4 C Y mho (2.21) (2.22) (2.23) 1.34 2.3 LONG LINE MODEL For accurate modeling of the transmission line we must not assume that the parameters are lumped but are distributed throughout line. The single-line diagram of a long transmission line is shown in Fig. 2.5. The length of the line is l. Let us consider a small strip x that is at a distance x from the receiving end. The voltage and current at the end of the strip are V and I respectively and the beginning of the strip are V + V and I + I respectively. The voltage drop across the strip is then V. Since the length of the strip is x, the series impedance and shunt admittance are zx and yx. It is to be noted here that the total impedance and admittance of the line are Z z l and Y y l (2.24) Fig. 2.5 Long transmission line representation. From the circuit of Fig. 2.5 we see that V Iz x V Iz x (2.25) Again as x 0, from (2.25) we get dV Iz dx (2.26) Now for the current through the strip, applying KCL we get I V V y x Vy x Vy x (2.27) The second term of the above equation is the product of two small quantities and therefore can be neglected. For x 0 we then have dI Vy dx (2.28) Taking derivative with respect to x of both sides of (2.26) we get d dV dx dx dI z dx 1.35 Substitution of (2.28) in the above equation results d 2V yzV 0 dx 2 (2.29) The roots of the above equation are located at (yz). Hence the solution of (2.29) is of the form V A1e x yz A2e x yz (2.30) Taking derivative of (2.30) with respect to x we get dV A1 yz e x dx yz A2 yz e x yz (2.31) Combining (2.26) with (2.31) we have 1 dV I z dx A1 x e z y yz A2 x e z y yz (2.32) Let us define the following two quantities ZC z which is called the characteristic impedance y yz which is called the propagation constant (2.33) (2.34) Then (2.30) and (2.32) can be written in terms of the characteristic impedance and propagation constant as V A1ex A2ex A A I 1 ex 2 e x ZC ZC (2.35) (2.36) Let us assume that x = 0. Then V = VR and I = IR. From (2.35) and (2.36) we then get VR A1 A2 A A IR 1 2 ZC ZC (2.37) (2.38) Solving (2.37) and (2.38) we get the following values for A1 and A2. A1 VR Z C I R V ZC I R and A2 R 2 2 1.36 Also note that for l = x we have V = VS and I = IS. Therefore replacing x by l and substituting the values of A1 and A2 in (2.35) and (2.36) we get VR Z C I R l VR Z C I R l e e 2 2 V Z I R l VR Z C I R l IS R C e e 2 2 VS (2.39) (2.40) Noting that el el el el sinh l and cosh l 2 2 We can rewrite (2.39) and (2.40) as VS VR cosh l ZC I R sinh l sinh l I S VR I R cosh l ZC (2.41) (2.42) The ABCD parameters of the long transmission line can then be written as A D cosh l B ZC sinh l sinh l C mho ZC (2.43) (2.44) (2.45) Example 2.1: Consider a 500 km long line for which the per kilometer line impedance and admittance are given respectively by z = 0.1 + j0.5145 and y = j3.1734 106 mho. Therefore ZC z y 0.1 j 0.5145 0.524179 0.5241 79 90 6 6 6 j3.1734 10 3.1734 10 90 3.1734 10 2 406.4024 5.5 and 79 90 2 l yz l 0.5241 3.1734 10 6 500 0.644884.5 0.0618 j 0.6419 We shall now use the following two formulas for evaluating the hyperbolic forms cosh j cosh cos j sinh sin sinh j sinh cos j cosh sin Application of the above two equations results in the following values 1.37 cosh l 0.8025 j 0.037 and sinh l 0.0495 j 0.5998 Therefore from (2.43) to (2.45) the ABCD parameters of the system can be written as A D 0.8025 j 0.037 B 43.4 j 240.72 C 2.01 10 5 j 0.0015 2.3.1 Equivalent- Representation of a Long Line The -equivalent of a long transmission line is shown Fig. 2.6. In this the series impedance is denoted by Z while the shunt admittance is denoted by Y. From (2.21) to (2.23) the ABCD parameters are defined as YZ A D 1 2 B Z YZ C Y 1 mho 4 (2.46) (2.47) (2.48) Fig. 2.6 Equivalent representation of a long transmission line. Comparing (2.44) with (2.47) we can write Z ZC sinh l z sinh l sinh l sinh l zl Z y l l yz (2.49) where Z = zl is the total impedance of the line. Again comparing (2.43) with (2.46) we get cosh l YZ Y 1 Z C sinh l 1 2 2 (2.50) Rearranging (2.50) we get Y 1 cosh l 1 1 tanh l 2 2 Z C sinh l ZC Y tanh l 2 2 l 2 y yl tanh l 2 tanh l 2 z 2 l 2 yz (2.51) 1.38 where Y = yl is the total admittance of the line. Note that for small values of l, sinh l = l and tanh (l/2) = l/2. Therefore from (2.49) we get Z = Z and from (2.51) we get Y = Y. This implies that when the length of the line is small, the nominal- representation with lumped parameters is fairly accurate. However the lumped parameter representation becomes erroneous as the length of the line increases. The following example illustrates this. Example 2.2: Consider the transmission line given in Example 2.1. The equivalent system parameters for both lumped and distributed parameter representation are given in Table 2.1 for three different line lengths. It can be seen that the error between the parameters increases as the line length increases. Table 2.1 Variation in equivalent parameters as the line length changes. Length of the line (km) Lumped parameters Distributed parameters Z () Y (mho) Z Y (mho) 100 52.4179 3.1710490 52.2779 3.1710489.98 250 131.03279 7.9310490 128.8179.2 8.010489.9 500 262.06479 1.5810390 244.6179.8 1.6410389.6 2.4 CHARACTERIZATION OF A LONG LOSSLESS LINE For a lossless line, the line resistance is assumed to be zero. The characteristic impedance then becomes a pure real number and it is often referred to as the surge impedance. The propagation constant becomes a pure imaginary number. Defining the propagation constant as = j and replacing l by x we can rewrite (2.41) and (2.42) as V VR cos x jZC I R sin x sin x I jVR I R cos x ZC (2.52) (2.53) The term surge impedance loading or SIL is often used to indicate the nominal capacity of the line. The surge impedance is the ratio of voltage and current at any point along an infinitely long line. The term SIL or natural power is a measure of power delivered by a transmission line when terminated by surge impedance and is given by SIL Pn V02 ZC (2.54) where V0 is the rated voltage of the line. At SIL ZC = VR/IR and hence from equations (2.52) and (2.53) we get V VR e x VR e jx (2.55) 1.39 I I R ex I R e jx (2.56) This implies that as the distance x changes, the magnitudes of the voltage and current in the above equations do not change. The voltage then has a flat profile all along the line. Also as ZC is real, V and I are in phase with each other all through out the line. The phase angle difference between the sending end voltage and the receiving end voltage is then = l. This is shown in Fig. 2.7. Fig. 2.7 Voltage-current relationship in naturally loaded line. 2.4.1 Voltage and Current Characteristics of an SMIB System For the analysis presented below we assume that the magnitudes of the voltages at the two ends are the same. The sending and receiving voltages are given by VS VS and VR VR 0 (2.57) where is angle between the sources and is usually called the load angle. As the total length of the line is l, we replace x by l to obtain the sending end voltage from (2.39) as VS VS VR ZC I R j VR ZC I R j e e VR cos jZC I R sin 2 2 (2.58) Solving the above equation we get IR VS VR cos jZC sin (2.59) Substituting (2.59) in (2.52), the voltage equation at a point in the transmission line that is at a distance x from the receiving end is obtained as V VR cos x VS VR cos V sin x VR sin x jZC sin x S jZC sin sin (2.60) In a similar way the current at that point is given by I j VS cos x VR cos x ZC sin (2.61) 1.40 Example 2.3: Consider a 500 km long line given in Example 2.1. Neglect the line resistance such that the line impedance is z = j0.5145 per kilometer. The line admittance remains the same as that given in Example 2.1. Then ZC z y j 0.5145 402.6524 j 3.1734 10 6 and yz j j 0.5145 3.1734 106 j 0.0013 rad/km Therefore = l = 0.6380 rad. It is assumed that the magnitude of the sending and receiving end voltages are equal to 1.0 per unit with the line being unloaded, i.e., VS = VR = 10 per unit. The voltage and current profiles of the line for this condition is shown in Fig. 2.8. The maximum voltage is 1.0533 per unit, while the current varies between –0.3308 per unit to 0.3308 per unit. Note that 1 per unit current is equal to 1/ZC. Fig. 2.8 Voltage and current profile over a transmission line. When the system is unloaded, the receiving end current is zero (IR = 0). Therefore we can rewrite (2.58) as VS VS VR cos (2.62) Substituting the above equation in (2.52) and (2.53) we get the voltage and current for the unloaded system as V VS cos x cos (2.63) 1.41 I j VS sin x Z C cos (2.64) Example 2.4: Consider the system given in Example 2.3. It is assumed that the system is unloaded with VS = VR = 10 per unit. The voltage and current profiles for the unloaded system is shown in Fig. 2.9. The maximum voltage of 1.2457 per unit occurs at the receiving end while the maximum current of 0.7428 per unit is at the sending end. The current falls monotonically from the sending end and voltage rises monotonically to the receiving end. This rise in voltage under unloaded or lightly loaded condition is called Ferranti effect. Fig. 2.9 Voltage and current profile over an unloaded transmission line. 2.4.2 Mid Point Voltage and Current of Loaded Lines The mid point voltage of a transmission line is of significance for the reactive compensation of transmission lines. To obtain an expression of the mid point voltage, let us assume that the line is loaded (i.e., the load angle is not equal to zero). At the mid point of the line we have x = l/2 such that x = /2. Let us denote the midpoint voltage by VM. Let us also assume that the line is symmetric, i.e., VS = VR = V. We can then rewrite equation (2.60) to obtain VM V V sin 2 sin Again noting that V V V cos j sin 1 sin V 2 2 cos tan 1 2V cos 2 2 1 cos 1.42 we obtain the following expression of the mid point voltage VM V cos 2 2 cos 2 (2.65) The mid point current is similarly given by IM j V V cos 2 V sin 2 Z sin 2 2 Z C sin C (2.66) The phase angle of the mid point voltage is half the load angle always. Also the mid point voltage and current are in phase, i.e., the power factor at this point is unity. The variation in the magnitude of voltage with changes in load angle is maximum at the mid point. The voltage at this point decreases with the increase in . Also as the power through a lossless line is constant through out its length and the mid point power factor is unity, the mid point current increases with an increase in . Example 2.5: Consider the transmission line discussed in Example 2.4. Assuming the magnitudes of both sending and receiving end voltages to be 1.0 per unit, we can compute the magnitude of the mid point voltage as the load angle ( ) changes. This is given in Table 2.2. The variation in voltage with is shown in Fig. 2.10. Table 2.2 Changes in the mid point voltage magnitude with load angle in degree 20 25 30 VM in per unit 1.0373 1.0283 1.0174 It is of some interest to find the Thevenin equivalent of the transmission line looking from the mid point. It is needless to say that the Thevenin voltage will be the same as the mid point voltage. To determine the Thevenin impedance we first find the short circuit current at the mid point terminals. This is computed through superposition principle, as the short circuit current will flow from both the sources connected at the two ends. From (2.52) we compute the short circuit current due to source VS (= V) as I SC1 V jZC sin 2 (2.67) Similarly the short circuit current due to the source VR (= V) is I SC 2 Thus we have V jZ C sin 2 (2.68) 1.43 Fig. 2.10 Variation in voltage profile for a loaded line I SC I SC1 I SC 2 2V cos 2 V V 2 jZ C sin 2 jZ C sin 2 (2.69) The Thevenin impedance is then given by Z TH jX TH Z VM j C tan 2 I SC 2 (2.70) 2.4.3 Power in a Lossless Line The power flow through a lossless line can be given by the mid point voltage and current equations given in (2.66) and (2.67). Since the power factor at this point is unity, real power over the line is given by Pe V M I M V2 sin Z C sin (2.71) If V = V0, the rated voltage we can rewrite the above expression in terms of the natural power as Pe Pn sin sin (2.72) For a short transmission line we have ZC sin ZC l lc l X c (2.73) 1.44 where X is the total reactance of the line. Equation (2.71) then can be modified to obtain the well known power transfer relation for the short line approximation as Pe V2 sin X (2.74) In general it is not necessary for the magnitudes of the sending and receiving end voltages to be same. The power transfer relation given in (2.72) will not be valid in that case. To derive a general expression for power transfer, we assume VS VS and VR VR 0 If the receiving end real and reactive powers are denoted by PR and QR respectively, we can write from (2.52) VS VS cos j sin V R cos jZ C PR jQR sin VR Equating real and imaginary parts of the above equation we get V S cos V R cos Z C QR sin VR (2.75) and V S sin Z C PR sin VR (2.76) Rearranging (2.76) we get the power flow equation for a losslees line as Pe PS PR VS VR Z C sin sin (2.77) To derive expressions for the reactive powers, we rearrange (2.75) to obtain the reactive power delivered to the receiving end as V S V R cos V R cos 2 QR Z C sin (2.78) Again from equation (2.61) we can write IS j V S cos V R ZC sin The sending end apparent power is then given by (2.79) 1.45 VS cos VS VR j VS cos VR PS jQS VS I VS j j ZC sin Z C sin Z C sin 2 S Equating the imaginary parts of the above equation we get the following expression for the reactive generated by the source V S cos V S V R cos 2 QS (2.80) Z C sin The reactive power absorbed by the line is then QL QS QR V 2 S VR 2 cos 2V S V R cos Z C sin (2.81) It is important to note that if the magnitude of the voltage at the two ends is equal, i.e., VS = VR = V, the reactive powers at the two ends become negative of each other, i.e., QS = QR. The net reactive power absorbed by the line then becomes twice the sending end reactive power, i.e., QL = 2QS. Furthermore, since cos 1for small values of , the reactive powers at the two ends for a short transmission line are given by QS V 2 cos V 2 cos V 2 1 cos QR Z C sin X (2.82) The reactive power absorbed by the line under this condition is given by 2V 2 1 cos QL X (2.83) Example 2.5: Consider a short, lossless transmission line with a line reactance of 0.5 per unit. We assume that the magnitudes of both sending and receiving end voltages to be 1.0 per unit. The real power transfer over the line and reactive power consumed by the line are shown in Fig. 2.11. The maximum real power is 2.0 per unit and it occurs for = 90. Also the maximum reactive power consumed by the line occurs at = 180 and it has a value of 8 per unit. 1.46 Fig. 2.11 Real power flow and reactive power consumed by a transmission line.