* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download Generator Performance Standards
Power factor wikipedia , lookup
Ground (electricity) wikipedia , lookup
Fault tolerance wikipedia , lookup
Resistive opto-isolator wikipedia , lookup
Power over Ethernet wikipedia , lookup
Audio power wikipedia , lookup
Power inverter wikipedia , lookup
Pulse-width modulation wikipedia , lookup
Opto-isolator wikipedia , lookup
Utility frequency wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Electric power system wikipedia , lookup
Electrical substation wikipedia , lookup
Power MOSFET wikipedia , lookup
Voltage regulator wikipedia , lookup
Electrification wikipedia , lookup
Amtrak's 25 Hz traction power system wikipedia , lookup
Stray voltage wikipedia , lookup
Three-phase electric power wikipedia , lookup
Power engineering wikipedia , lookup
Surge protector wikipedia , lookup
Buck converter wikipedia , lookup
History of electric power transmission wikipedia , lookup
Power electronics wikipedia , lookup
Voltage optimisation wikipedia , lookup
Switched-mode power supply wikipedia , lookup
APPLICATION FOR REGISTRATION AS A GENERATOR GENERATOR PERFORMANCE STANDARDS Introduction The following table outlines the information AEMO requires to assess compliance with the performance standards for the generating unit/system. If the connection agreement for the facility provides this level of detail, a copy of the connection agreement (with the commercial terms removed) may be submitted in place of this document. If the technical aspects of the connection agreement do not contain at least this level of detail, it is necessary for the Generator and Network Service Provider to jointly complete this document and submit it with the registration application. AEMO allows Network Service Providers to use this table for drafting connection agreements. All technical enquiries on this form should be directed to [email protected] Applicants should complete columns three and four in the following tables to describe the performance standards. Indicate in the third column whether the generating unit or generating system meets the automatic (A), negotiated (N) or minimum (M) performance standard. The fourth column provides details of the performance standard corresponding to the automatic access standard as a guide. Amend the performance standards as necessary to reflect the agreed access standard, and respond to the comments provided in square brackets ([]). Name of person applying for registration as a Generator: ABN: [insert company name] [insert ABN] Network Service Provider: [insert company name and ABN of NSP] Name of generating system: [insert name of power station, wind farm or other generating system] Generating unit designations: [insert unit designations eg Units 1 to 4] Connection point: [insert connection point] Connection point voltage: [insert connection point voltage] Nameplate rating: [Insert the value of unit “nameplate rating” as defined in the Glossary of the Rules] Maximum capacity: [Insert maximum dispatchable MW quantity] Registered capacity: [Insert registered capacity] National Electricity Rules version: Version [Insert version number] 582732416 13 MAY 2013 PAGE 1 APPLICATION FOR REGISTRATION AS A GENERATOR Date of Finalisation: RULES REFERENCE DESCRIPTION S5.2.5.1 Reactive Power Capability Date Generator Performance Standards Agreed AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES Rated active power = [Insert MW value] Each generating system, While operating at any level of active power output; and Any voltage at the connection point within the limits as shown in the graph below should not vary by more than ±10% of its normal voltage, continuously at the connection point, without a contingency event, is capable of: Supplying at its connection point an amount of reactive power of at least the product of the rated active power of the generating system and 0.395; Absorbing at its connection point an amount of reactive power of at least the product of the rated active power of the generating system and 0.395. Each generating unit, while not supplying or absorbing reactive power under an ancillary services agreement will draw electricity with a power factor in the range [Insert value, lead/lag] to [Insert value, lead/lag]. 582732416 13 MAY 2013 PAGE 2 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES 1.35 Voltage in per unit 1.3 1.25 1.2 1.15 1.1 1.05 0 0.5 1 1.5 2 Tim e period (seconds) S5.2.5.2 582732416 Quality of Electricity Generated Each generating system when generating and when not generating must not produce at its connection points for generation: Voltage fluctuation greater than [Insert the limits allocated by the NSP in accordance with S5.1.5(a)]; Harmonic voltage distortion greater than [Insert the limits] allocated by 13 MAY 2013 PAGE 3 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES the NSP in accordance with S5.1.6(a)]; and S5.2.5.3 Generating Unit Response to Frequency Disturbance Voltage unbalance greater than [Insert the limits allocated by the NSP in accordance with S5.1.7(c)]. Each generating unit is capable of continuous uninterrupted operation for frequencies in the following ranges: For mainland regions [delete table if not applicable to your facility] Frequency range (Hz) Duration 47 to 49 2 minutes 51 to 52 2 minutes 47 to 49.5 10 minutes 50.5 to 52 10 minutes 49.5 to 50.5 continuous For Tasmania [delete table if not applicable to your facility]: 582732416 13 MAY 2013 PAGE 4 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE S5.2.5.4 582732416 DESCRIPTION Generating System Response to Voltage Disturbances AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES Frequency range (Hz) Duration 47 to 48 2 minutes 52 to 55 2 minutes 48 to 49 10 minutes 51 to 52 10 minutes 49 to 51 continuous This generating system and each of its generating units is capable of continuous uninterrupted operation within the following range of voltages for the given duration at its connection point: Voltages over 110% for the duration as permitted in the graph below 13 MAY 2013 PAGE 5 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES 1.35 Voltage in per unit 1.3 1.25 1.2 1.15 1.1 1.05 0 0.5 1 1.5 2 Tim e period (seconds) 90% to 110% of normal voltage continuously; 80% to 90% of normal voltage for a period of at least 10 seconds; and 70% to 80% of normal voltage for a period of at least 2 seconds. [Insert applicable access standard for any operational arrangements necessary to ensure the generating system and each of its generating units will meet its 582732416 13 MAY 2013 PAGE 6 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES agreed performance levels under abnormal network or generating system conditions]. S5.2.5.5 Generating System Response to Disturbances following Contingency Events Transmission system fault clearance time: Primary protection system, [Insert time in milliseconds]; Breaker fail protection system, [Insert time in milliseconds]. Distribution system fault clearance time: Primary protection system, [Insert time in milliseconds]; Breaker fail protection system, [Insert time in milliseconds]. This generating system and each of its generating units remains in continuous uninterrupted operation for a disturbance caused by an event that is: i. A credible contingency event other than a fault in the distribution network; ii. A three phase fault in a transmission system cleared by all relevant primary protection systems; iii. A two phase to ground, phase to phase or phase to ground fault in the transmission system cleared in: (A) the longest time expected to be taken for a relevant breaker fail 582732416 13 MAY 2013 PAGE 7 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES protection system to clear the fault; or (B) if breaker fail protection system is not installed then the greater of the time specified in the table below Nominal voltage at fault location (kV) Time (milliseconds) 400kV and above 175 At least 250kV but less than 400kV 250 More than 100kV but less than 250kV 430 Less than or equal to 100kV 430 [delete (A) or (B) and insert values] and the longest time expected to be taken for all relevant primary protection systems to clear the fault; and iv. a three phase, two phase to ground, phase to phase or phase to phase to ground fault in the distribution system cleared in: (A) the longest time expected to be taken for a relevant breaker fail protection system to clear the fault; or (B) if breaker fail protection system is not installed, the greater of 430 milliseconds and the longest time expected to be taken for all 582732416 13 MAY 2013 PAGE 8 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES relevant primary protection systems to clear the fault. [delete (A) or (B) and insert values] The above requirements exclude faults that disconnect the generating unit from the power system by removing network elements from service. Each generating unit, in respect of fault types described in (ii) to (iv), will supply or absorb from the network [Specify any changed power system conditions or energy source availability conditions to be excluded]: capacitive reactive current of at least the greater of its pre-disturbance reactive current and 4% of the maximum continuous current of the generating system including all generating units (in the absence of a disturbance) for each 1% reduction (from its pre-fault level) of connection point voltage during the fault; after disconnection of the faulted element, reactive power sufficient to ensure that the connection point voltage is within the range for continuous uninterrupted operation under the performance standard for clause S5.2.5.4; and from 100 milliseconds after disconnection of the faulted element, active power of at least 95% of the level existing just prior to the fault. [Insert applicable access standard for any operational arrangements necessary to ensure the generating system and each of its generating units will meet its 582732416 13 MAY 2013 PAGE 9 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES agreed performance levels under abnormal network or generating system conditions]. S5.2.5.6 582732416 Quality of Electricity Generated and Continuous Uninterrupted Operation The generating system including each of its operating generating units and reactive plant, will maintain continuous uninterrupted operation for voltage fluctuation, harmonic voltage distortion and voltage unbalance at the connection point up to and including the following limits: (i) Voltage fluctuations at the connection point up to the "compatibility levels" set out in Table 1 of Australian Standard AS/NZS 61000.3.7:2001. (ii) Harmonic voltage distortion at the connection point up to the “compatibility levels” defined in Table 1 of Australian Standard AS/NZS 61000.3.6:2001. (iii) A negative sequence voltage at the connection point up to an agreed % level measured over a 30 minute average. (iv) A negative sequence voltage at the connection point up to agreed % level measured over a 1 minute average and occurring at most once per hour. 13 MAY 2013 PAGE 10 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES S5.2.5.7 Partial Load Rejection Each generating unit is capable of continuous uninterrupted operation during and following a power system load reduction of 30% from its predisturbance level or equivalent impact from separation of part of the power system in less than 10 seconds, provided that the loading level remains above minimum load, PMIN = [insert value for minimum load]. S5.2.5.8 Protection of Generating Units from Power System Disturbances [Specify protection schemes and corresponding settings and also address “General requirements” as outlined in clause S5.2.5.8 of the Rules]. S5.2.5.9 Protection Systems that Impact on Power System Security Each generating unit has primary protection systems to disconnect from the power system any faulted element within the protection zones that include the connection point, the generating unit stator winding or any plant connected between them, within the following fault clearance times, [insert fault clearance times determined under clause S5.1.9(a)(1), but subject to clauses S5.1.9(k) and S5.1.9(l)]. Each primary protection system has sufficient redundancy to ensure that a faulted element within its protection zone is disconnected from the power system within the applicable fault clearance time with any single protection element (including any communications facility upon which that protection system depends) out of service. Breaker fail protection systems are provided to clear faults that are not cleared 582732416 13 MAY 2013 PAGE 11 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES by the circuit breakers controlled by the primary protection system, within the following fault clearance times, [insert fault clearance times determined under clause S5.1.9(a)(1)] [Address “General requirements” as outlined in clause S5.2.5.9 in the Rules] S5.2.5.10 Protection to Trip Plant for Unstable Operation [Delete standard that is not applicable] Each synchronous generating unit has a protection system to disconnect it promptly when a condition that would lead to pole slipping is detected in order to prevent pole slipping or other conditions where a generating unit causes active power, reactive power or voltage at the connection point to become unstable. [Specify the type of protection system installed, eg. loss of field, reverse power, etc.] Each asynchronous generating unit has a protection system to disconnect it promptly for conditions where the active power, reactive power or voltage at the connection point becomes unstable. [Specify the type of protection system installed and the corresponding operating time.] S5.2.5.11 Frequency Control Maximum operating level = [Insert MW value]; Minimum operating level = [Insert MW value]. pre-disturbance level means in relation to a generating unit and a frequency 582732416 13 MAY 2013 PAGE 12 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES disturbance, the generating unit's level of output just before the system frequency first exceeds the upper or lower limit of the normal operating frequency band during the frequency disturbance. system frequency means the frequency of the transmission system or distribution system to which the generating unit or generating system is connected. This generating system’s active power transfer to the power system will not: (i) increase in response to a rise in system frequency; or (ii) decrease in response to a fall in system frequency. This generating system is capable of automatically reducing its active power transfer to the power system: (i) whenever the system frequency exceeds the upper limit of the normal operating frequency band; (ii) by an amount that equals or exceeds the least of: (A) 20% of its maximum operating level times the frequency difference between system frequency and the upper limit of the normal operating frequency band; (B) 10% of its maximum operating level; and 582732416 13 MAY 2013 PAGE 13 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES (C) the difference between the generating unit's pre-disturbance level and minimum operating level, but zero if the difference is negative; and (iii) sufficiently rapidly for the Generator to be in a position to offer measurable amounts of lower services to the spot market for market ancillary services. This generating system is capable of automatically increasing its active power transfer to the power system: (i) whenever the system frequency falls below the lower limit of the normal operating frequency band; (ii) by the amount that equals or exceeds the least of: (A) 20% of its maximum operating level times the percentage frequency difference between the lower limit of the normal operating frequency band and system frequency; (B) 5% of its maximum operating level; and (C) one third of the difference between the generating unit's maximum operating level and pre-disturbance level, but zero if the difference is negative; and (iii) sufficiently rapidly for the Generator to be in a position to offer 582732416 13 MAY 2013 PAGE 14 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES measurable amounts of raise services to the spot market for market ancillary services. Each control system used to satisfy this performance standard (for Frequency control) will be adequately damped. The amount of relevant market ancillary service for which the plant is registered will not exceed the amount that would be consistent with this performance standard. S5.2.5.12 Impact on Network Capability This generating system has plant capabilities and control systems that are sufficient so that when connected to the power system it does not reduce any inter-regional or intra-regional power transfer capability below the level that would apply if the generating units were not connected. S5.2.5.13 Voltage and Reactive Power Control rise time means in relation to a step response test or simulation of a control system, the time taken for an output quantity to rise from 10% to 90% of the maximum change induced in that quantity by a step change of an input quantity. settling time means in relation to a step response test or simulation of a control system, the time measured from initiation of a step change in an input quantity to the time when the magnitude of error between the output quantity and its final settling value remains less than 10% of: (1) if the sustained change in the quantity is less than half of the maximum change in that output quantity, the maximum change induced in that 582732416 13 MAY 2013 PAGE 15 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES output quantity; or (2) the sustained change induced in that output quantity. static excitation system means in relation to a synchronous generating unit, an excitation control system that does not use rotating machinery to produce the field current. This generating system has plant capabilities and control systems sufficient to ensure that: (i) power system oscillations, for the frequencies of oscillation of the generating unit against any other generating unit, are adequately damped; (ii) operation of the generating system does not degrade the damping of any critical mode of oscillation of the power system; and (iii) operation of the generating system does not cause instability (including hunting of tap-changing transformer control systems) that would adversely impact other Registered Participants; (2) the control system used with this generating system has: (i) for the purposes of disturbance monitoring and testing, permanently installed and operational, monitoring and recording facilities for key variables including each input and output; and 582732416 13 MAY 2013 PAGE 16 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES (ii) facilities for testing the control system sufficient to establish its dynamic operational characteristics; (3) each synchronous generating unit has an excitation control system that [delete this requirement (3) if it is not applicable]: (i) regulates voltage at the connection point or another agreed location in the power system (including within the generating system) to within 0.5% of the setpoint; (ii) is able to operate the stator continuously at 105% of nominal voltage with rated active power output; (iii) regulates voltage in a manner that helps to support network voltages during faults and does not prevent the Network Service Provider from achieving the requirements of clause S5.1a.3 and S5.1a.4; (iv) allows the voltage setpoint to be continuously controllable in the range of at least 95% to 105% of normal voltage at the connection point or the agreed location in the power system, without reliance on a tap-changing transformer; (v) has limiting devices to ensure that a voltage disturbance does not cause the generating unit to trip at the limits of its operating capability; (vi) has an excitation ceiling voltage of at least: 582732416 13 MAY 2013 PAGE 17 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES (A) for a static excitation system, 2.3 times; or (B) for other excitation control systems, 1.5 times, the excitation required to achieve generation at the nameplate rating for rated power factor, rated speed and nominal voltage; (vii) has settling times for a step change of voltage setpoint or voltage at the location agreed in (3)(i) above of: (A) generated voltage less than 2.5 seconds for a 5% voltage disturbance with the generating unit not synchronised; (B) active power, reactive power and voltage less than 5.0 seconds for a 5% voltage disturbance with the generating unit synchronised, from an operating point where the voltage disturbance would not cause any limiting device to operate; and (C) in respect of each limiting device, active power, reactive power and voltage less than 7.5 seconds for a 5% voltage disturbance with the generating unit synchronised, when operating into a limiting device from an operating point where a voltage disturbance of 2.5% would just cause the limiting device to operate; (viii) is able to increase field voltage from rated field voltage to the excitation ceiling voltage in less than: 582732416 13 MAY 2013 PAGE 18 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES (A) 0.05 second for a static excitation system; or (B) 0.5 second for other excitation control systems; (ix) has a power system stabiliser with sufficient flexibility to enable damping performance to be maximised, with characteristics as described in paragraph (a) below; and (x) has reactive current compensation settable for boost or droop; and (4) this generating system, other than one comprised of synchronous generating units, has a voltage control system that [delete this requirement (4) if it is not applicable]: (i) regulates voltage at the connection point or [Specify an agreed location] in the power system (including within the generating system) to within 0.5% of its setpoint; (ii) regulates voltage in a manner that helps to support network voltages during faults and does not prevent the Network Service Provider from achieving the requirements of clauses S5.1a.3 and S5.1a.4; (iii) allows the voltage setpoint to be continuously controllable in the range of at least 95% to 105% of normal voltage at the connection point or [Specify agreed location] in the power system, without reliance on a tap 582732416 13 MAY 2013 PAGE 19 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES changing transformer; (iv) has limiting devices to ensure that a voltage disturbance does not cause the generating unit to trip at the limits of its operating capability; (v) with the generating system connected to the power system, has settling times for active power, reactive power and voltage due to a step change of voltage setpoint or voltage at the location agreed under (i) above, of less than: (A) 5.0 seconds for a 5% voltage disturbance with the generating system connected to the power system, from an operating point where the voltage disturbance would not cause any limiting device to operate; and (B) 7.5 seconds for a 5% voltage disturbance with the generating system connected to the power system, when operating into any limiting device from an operating point where a voltage disturbance of 2.5% would just cause the limiting device to operate; (vi) has reactive power rise time, for a 5% step change in the voltage setpoint, of less than 2 seconds; (vii) has a power system stabiliser with sufficient flexibility to enable damping performance to be maximised, with characteristics as described in (a); and 582732416 13 MAY 2013 PAGE 20 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES (viii) has reactive current compensation. (a) The power system stabiliser has: (1) for a synchronous generating unit, measurements of rotor speed and active power output of the generating unit as inputs, and otherwise, measurements of power system frequency and active power output of the generating unit as inputs; (2) two washout filters for each input, with ability to bypass one of them if necessary; (3) sufficient (and not less than two) lead-lag transfer function blocks (or equivalent number of complex poles and zeros) with adjustable gain and time-constants, to compensate fully for the phase lags due to the generating plant; (4) an output limiter, which for a synchronous generating unit is continually adjustable over the range of –10% to +10% of stator voltage; (5) monitoring and recording facilities for key variables including inputs, output and the inputs to the lead-lag transfer function blocks; and (6) facilities to permit testing of the power system stabiliser in isolation from the power system by injection of test signals, sufficient to establish the transfer function of the power system stabiliser. 582732416 13 MAY 2013 PAGE 21 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES [Address “General requirements” as outlined clause S5.2.5.13 of the Rules] S5.2.5.14 Active Power Control [This requirement is not applicable if the generating system comprised of generating units with a nameplate rating is less than 30 MW] This scheduled generating system or scheduled generating unit has an active power control system capable of: (i) maintaining and changing its active power output in accordance with its dispatch instructions; and (ii) ramping its active power output linearly from one dispatch level to another. Subject to the energy source availability, the non-scheduled generating unit or non-scheduled generating system has an active power control system capable of: (i) automatically reducing or increasing its active power output within 5 minutes, at a constant rate, to or below the level specified in an instruction electronically issued by a control centre, subject to (iii), (ii) automatically limiting its active power output, to below the level specified in (i) above; and (iii) not changing its active power output within 5 minutes by more than the raise and lower amounts specified in an instruction electronically issued by 582732416 13 MAY 2013 PAGE 22 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES a control centre. Subject to energy source availability, the semi-scheduled generating unit or the semi-scheduled generating system has an active power control system capable of: (i) automatically reducing or increasing its active power output within 5 minutes at a constant rate, to or below the level specified in an instruction electronically issued by a control centre; (ii) automatically limiting its active power output, to or below the level specified in subparagraph (i); (iii) not changing its active power output within 5 minutes by more than the raise and lower amounts specified in an instruction electronically issued by a control centre; and (iv) ramping its active power output linearly from one level of dispatch to another. Each control system used to satisfy this performance standard (for active power control) will be adequately damped. S5.2.6.1 and 582732416 Remote Amend performance standard as appropriate. 13 MAY 2013 PAGE 23 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION 4.11.1 Monitoring AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES The following quantities will be transmitted to AEMO’s control centre in realtime in accordance with clause 4.11 of the Rules. (1) in respect of a scheduled generating system or non-scheduled generating unit with a nameplate rating of 30 MW or more: (i) current, voltage, active power and reactive power in respect of generating unit stators or power conversion systems (as applicable); (ii) the status of all switching devices that carry the generation, tapchanging transformer tap position; (iii) aggregate active power if subject to aggregation approved by AEMO under clause 3.8.3 of the Rules; and (iv) active power and reactive power for the generating system (2) in respect of a generating system that includes a generating unit with a nameplate rating of less than 30 MW: (i) its connected status, tap-changing transformer tap position and voltages; (ii) active power and reactive power aggregated for groups of identical generating units; and 582732416 13 MAY 2013 PAGE 24 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES (iii) either the numbers of identical generating units operating or the operating status of each non-identical generating unit; (3) in respect of an auxiliary supply system with a capacity of 30 MW or more associated with a generating unit or generating system, active power and reactive power; (4) in respect of reactive power equipment that is part of a generating system but not part of a particular generating unit, its reactive power; (5) in respect of a wind farm type of generating system: (i) wind speed; (ii) wind direction; and (iii) ambient temperature; and (6) any other quantity that AEMO reasonably requires to discharge its market and power system security functions as set out in Chapters 3 and 4 of the Rules [Liaise with AEMO]. S5.2.6.2 and 4.11.3 582732416 Communications Equipment This Generator will: (1) provide and maintain two separate telephone facilities using independent telecommunications service providers, for the purposes of operational communications between the Generator's responsible 13 MAY 2013 PAGE 25 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES operator under clause 4.11.3(a) and AEMO’s control centre; and (2) provide electricity supplies for remote monitoring equipment and remote control equipment installed in relation to its generating system capable of keeping such equipment available for at least 3 hours following total loss of supply at the connection point for the relevant generating unit. S5.2.7 Power Station Auxiliary Supplies [If applicable specify performance standard using clause S5.3.5 of the Rules as if the Generator were a Market Customer] S5.2.8 Fault Current The generating system limits its contribution to the fault current at the connection point to: a) three phase fault current, [Insert value] kA; b) single phase to ground fault current, [Insert value] kA; c) phase to phase to ground fault current, [Insert value] kA, calculated at 1.0 per unit voltage. The generating system’s connected plant is capable of withstanding fault current through the connection point up to: a) three phase fault current, [Insert value] kA; b) single phase to ground fault current, [Insert value] kA; 582732416 13 MAY 2013 PAGE 26 APPLICATION FOR REGISTRATION AS A GENERATOR RULES REFERENCE DESCRIPTION AGREED ACCESS STANDARD IS AUTOMATIC, NEGOTIATED OR MINIMUM STANDARD (A / N / M) DETAIL DESCRIPTION OF PROPOSED PERFORMANCE STANDARD INCLUDING VALUES c) phase to phase to ground fault current, [Insert value] kA, for the duration of [Insert time] milliseconds. The circuit breaker provided to isolate the generating unit or generating system from the network is capable of breaking, without damage or restrike, the maximum fault current of [Insert value] kA, expected to flow through the circuit breaker for any fault in the network or in the generating unit or generating system. 582732416 13 MAY 2013 PAGE 27