Download PUB‐NLH‐547  Island Interconnected System Supply Issues and Power Outages  Page 1 of 8   

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power factor wikipedia , lookup

Three-phase electric power wikipedia , lookup

Rectifier wikipedia , lookup

Mechanical filter wikipedia , lookup

Audio power wikipedia , lookup

Islanding wikipedia , lookup

Power over Ethernet wikipedia , lookup

Electrification wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Decibel wikipedia , lookup

Power inverter wikipedia , lookup

Voltage optimisation wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Earthing system wikipedia , lookup

Electric power system wikipedia , lookup

Fault tolerance wikipedia , lookup

Distributed element filter wikipedia , lookup

History of electric power transmission wikipedia , lookup

Power electronics wikipedia , lookup

Analogue filter wikipedia , lookup

Alternating current wikipedia , lookup

Buck converter wikipedia , lookup

Distribution management system wikipedia , lookup

Electrical substation wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Power engineering wikipedia , lookup

AC adapter wikipedia , lookup

Mains electricity wikipedia , lookup

Switched-mode power supply wikipedia , lookup

HVDC converter wikipedia , lookup

High-voltage direct current wikipedia , lookup

Transcript
PUB‐NLH‐547 Island Interconnected System Supply Issues and Power Outages Page 1 of 8 1 Q. 2 Please provide the minimum Effective Short Circuit Capacity (“ESCC”) at Soldiers Pond at which the LIL will be expected to deliver: 3 
Maximum power 4 
50% of maximum power 5 
Minimum power 6 7 required operating conditions. 8 9 10 In the response state whether the appropriate ESCC will always be available for the A.
The Short Circuit Level (SCL) is a measure of electrical current that can be delivered 11 into a solid three phase fault at a specific point in an ac transmission network. As 12 such, the SCL is a good indicator of ac system strength. Table 1 outlines the SCLs 13 that have been calculated for determining equipment and performance ratings of 14 the HVdc scheme. 15 Table 1: Soldiers Pond Short Circuit Levels (3Φ MVA) System Configuration Maximum Foreseeable Maximum Minimum Extreme Minimum 16 SCL Results Purpose Equipment Rating Performance Performance Equipment Rating SCL (3Φ MVA) 4208 4208 3462 2849 17 Typically when considering the location of an HVdc infeed, the Short Circuit Ratio 18 (SCR) is calculated to determine the strength of the ac network as a ratio of the SCL 19 and the power rating of the HVdc scheme. CIGRE TB‐681 defines three categories of 20 ac/dc systems; a high SCR, low SCR and very low SCR. A strong ac network 21 connection with a high SCR is considered having an SCR >3, whereas systems with 1
CIGRE Technical Brochure 68 ‐ Guide for Planning DC Links Terminating at ac Systems Locations Having Low Short‐ Circuit Capacities – Part I: AC/DC Interaction Phenomena, June 1992 PUB‐NLH‐547 Island Interconnected System Supply Issues and Power Outages Page 2 of 8 1 low SCR are those with SCR between 2 and 3. Very low or weak ac/dc system 2 interconnections have an SCR <2.0. The SCR gives an indication of the impact the 3 transmitted power will have on the converter bus voltage. As the SCR is used in the 4 early design phase of an HVdc system and does not take into account the impact of 5 the shunt harmonic filter banks, the Effective Short Circuit Ratio (ESCR) is typically 6 used in detailed design following filter design. 7 8 The SCR is defined as: 9 SCR = SCL/Pdc 10 11 Table 2 outlines the SCR for each SCL defined in Table 1 using a Pdc of 900 MW. 12 13 Table 2: Soldiers Pond Short Circuit Ratio System Configuration Maximum Foreseeable Maximum Minimum Extreme Minimum SCL Results Purpose Equipment Rating HVdc Performance HVdc Performance Equipment Rating SCL (3Φ MVA) 4208 4208 3462 2849 SCR 4.68 4.68 3.85 3.17 14 15 In addition to the SCR, the Effective Short Circuit Ratio (ESCR) is used to determine 16 the impact of the shunt harmonic filter banks installed at the local converter bus 17 and subsequent interactions between the dc and ac systems. As the voltage at the 18 converter ac bus changes, the reactive power provided by the filter banks change 19 by the square of the voltage change. The ESCR is calculated by subtracting the 20 MVAR rating of the harmonic filters online at nominal voltage for a particular power 21 order on the HVdc. The Effective Short Circuit Ratio (ESCR) is defined as: 22 23 ESCR = (SCL‐Qf)/Pdc PUB‐NLH‐547 Island Interconnected System Supply Issues and Power Outages Page 3 of 8 1 The LIL HVdc scheme has been designed to meet performance specifications (rated 2 power) down to the “Minimum Fault Level” which has been determined as 3 3462 3Φ MVA at the Soldiers Pond (SOP) 230 kVac bus. For the purposes of the 4 HVdc contract (CD0501), the control system will be tested for reduced short circuit 5 levels down to an ESCR of 2.52 at the inverter. 6 7 The minimum three phase fault level at SOP was calculated using the following 8 assumptions: 9 • All NLH thermal generation (diesel and combustion turbine) offline; 10 • NLH hydro units at minimum dispatch; 11 • All customer hydro generation online; 12 • All NUGs in service; 13 • Two SOP synchronous condensers (SC) in service; 14 • Holyrood G3 in service as SC, G1 and G2 are out of service; 15 • Holyrood CT in service as SC; 16 • Stephenville G1 in service as SC; 17 • Hardwoods G1 in service as SC; 18 • Granite Canal G1 in service; 19 • Upper Salmon G1 in service; 20 • Bay d’Espoir G3 and G7 online; 21 • Cat Arm G2 out of service; 22 • Hinds Lake G1 out of service; and 23 • Maritime Link offline. 2
Supply and Install Converters and Transition Compounds – Performance Requirements, Section 7.3, bullet k, doc# ILK‐SN‐CD‐8000‐EL‐DC‐0001‐01 PUB‐NLH‐547 Island Interconnected System Supply Issues and Power Outages Page 4 of 8 1 General Electric (GE) Grid3 has determined that the ac harmonic filter design at SOP 2 shall involve the switching of five 230 kV 75 MVAR shunt filter banks to absorb 3 harmonics generated by the converter station switching dynamics and provide 4 reactive power support for the converter and connected ac system. A spare filter 5 bank will be installed at the Soldiers Pond Converter Station (SOPCS), for a total of 6 six filters to allow operation of the LIL with one filter bank out of service. 7 8 The SOPCS will have a total of three 75 MVAR 3/12/23 triple tuned filters 9 considered as “Type A” and three 75 MVAR 11/24/36 triple tuned filters considered 10 as “Type B”. Table 3 outlines the proposed filter switching strategy for the SOPCS 11 under nominal dc voltage operation in balanced bipole configuration. It should be 12 noted that all power orders are referenced at the rectifier dc terminals (MFACS). 13 14 Table 3: Filter Switching Strategy ‐ Nominal DC Voltage – Normal Bipole Operation Number of AC Filter Banks Online (75 MVAR) 2 3 4 5 LIL Power Order (MW) @ MFACS Switch‐In Switch‐Out Scheme De‐Block Scheme De‐Block 324 279 549 504 765 720 15 16 Given the switching points as defined in Table 3, the Effective Short Circuit Ratio 17 (ESCR) is calculated in Table 4 and Table 5. 3
Formerly Alstom Grid. PUB‐NLH‐547 Island Interconnected System Supply Issues and Power Outages Page 5 of 8 1 Table 4: SOP ESCR for Bipole Operation – Filter Switch‐In – Minimum SCL HVdc Power Order (MW) Harmonic Filters Online ESCR 0 90 314 315 584 585 764 765 900 2 2 2 3 3 4 4 5 5 N/A 36.80 10.55 10.28 5.54 5.41 4.14 4.04 3.43 2 3 Table 5: SOP ESCR for Bipole Operation – Filter Switch‐Out – Minimum SCL 4 HVdc Power
Order (MW) Harmonic Filters Online ESCR 900 721 720 505 504 280 279 90 0 5 5 4 4 3 3 2 2 0 3.43 4.28 4.39 6.26 6.42 11.56 11.87 36.80 N/A 5 The Effective Short Circuit Ratio (ESCR) for all key operating points from HVdc 6 scheme de‐block to rated power are well above 3 which indicates a strong ac/dc 7 interconnection with the Island Interconnected System. PUB‐NLH‐547 Island Interconnected System Supply Issues and Power Outages Page 6 of 8 1 If the same calculations are completed for the “extreme minimum” SCL of 2 2849 3Φ MVA using the switching points in Table 3, we have the resultant ESCRs 3 shown in Table 6 and Table 7. 4 5 The extreme minimum 3Φ SCL at SOP was calculated using the following 6 assumptions: 7 
All NLH thermal generation (diesel and combustion turbine) off; 8 
NLH hydro units at minimum dispatch; 9 
All customer hydro generation on; 10 
All NUGs in service; 11 
One Soldiers Pond synchronous condenser in service; 12 
Holyrood G3 in service, G1 and G2 are out of service; 13 
Holyrood CT in service; 14 
Hardwoods G1 in service; 15 
Granite Canal G1 in service; 16 
Upper Salmon G1 in service; 17 
Bay d’Espoir G3 and G7 online; 18 
Cat Arm G2 out of service; 19 
Hinds Lake G1 out of service; and 20 
Maritime Link offline. PUB‐NLH‐547 Island Interconnected System Supply Issues and Power Outages Page 7 of 8 1 Table 6: SOP ESCR for Bipole Operation – Filter Switch‐In – Extreme Minimum SCL HVdc Power
Order (MW) 0 90 314 315 584 585 764 765 825 900 Harmonic Filters Online 2 2 2 3 3 4 4 5 5 5 ESCR N/A 29.99 8.60 8.33 4.49 4.36 3.34 3.23 3.00 2.75 2 3 Table 7: SOP ESCR for Bipole Operation – Filter Switch‐Out – Extreme Minimum SCL HVdc Power
Order (MW) 900 825 721 720 505 504 280 279 90 0 Harmonic Filters Online 5 5 5 4 4 3 3 2 2 0 ESCR 2.75 3.00 3.43 3.54 5.05 5.21 9.37 9.67 29.99 N/A 4 5 The Effective Short Circuit Ratio (ESCR) for key operating points from 825 MW to 6 scheme blocking are (above) 3, indicating a strong ac/dc interconnection with the 7 Island Interconnected System. However, it should be noted that operating the LIL at 8 a power order exceeding 825 MW will result in an ESCR less than 3. Operation at 9 SCLs and ESCRs below the minimum fault level (HVdc performance) may result in 10 the reduction of maximum dc power transmission over the HVdc link. The PUB‐NLH‐547 Island Interconnected System Supply Issues and Power Outages Page 8 of 8 1 equipment, however, will be rated for the electrical stresses at SCLs down to the 2 extreme minimum fault level.