Download PUB‐NLH‐478  Island Interconnected System Supply Issues and Power Outages  Page 1 of 1 Q.  

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Control theory wikipedia , lookup

Control system wikipedia , lookup

Distribution management system wikipedia , lookup

Resilient control systems wikipedia , lookup

Transcript
PUB‐NLH‐478 Island Interconnected System Supply Issues and Power Outages Page 1 of 1 1 Q. Further to the response to PUB‐NLH‐264, Attachment 1, which outlines that for the 2 studied operating conditions, curtailment of the Maritime Link is necessary to avoid 3 low ac voltage and/or instability and/or load shedding, what signal will be used to 4 initiate curtailment or runback of the Maritime Link and what penalties will be 5 incurred when such curtailments occur? 6 7 8 A. 9 The Labrador ‐ Island HVdc Link (LIL) and Maritime HVdc Link (ML) are being designed and integrated into the Island Interconnected System such that issues 10 with the LIL (including temporary and permanent pole and bipole faults) will result 11 in the curtailment of the ML to ensure Island Interconnected System stability. To 12 achieve the necessary control action, the LIL and ML control systems will be 13 connected by redundant fibre optic communication channels so that the LIL control 14 system can initiate high speed commands to the ML control system to ensure Island 15 Interconnected System stability. There are no penalties for runback or curtailment 16 of ML for issues with the LIL.