* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download ECE4762007_Lect19
Electric machine wikipedia , lookup
Electrical ballast wikipedia , lookup
Power engineering wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Stepper motor wikipedia , lookup
Immunity-aware programming wikipedia , lookup
History of electric power transmission wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Three-phase electric power wikipedia , lookup
Resistive opto-isolator wikipedia , lookup
Voltage optimisation wikipedia , lookup
Power MOSFET wikipedia , lookup
Two-port network wikipedia , lookup
Current source wikipedia , lookup
Buck converter wikipedia , lookup
Surge protector wikipedia , lookup
Protective relay wikipedia , lookup
Circuit breaker wikipedia , lookup
Ground (electricity) wikipedia , lookup
Opto-isolator wikipedia , lookup
Mains electricity wikipedia , lookup
Rectiverter wikipedia , lookup
Stray voltage wikipedia , lookup
Electrical substation wikipedia , lookup
Alternating current wikipedia , lookup
Network analysis (electrical circuits) wikipedia , lookup
ECE 476 POWER SYSTEM ANALYSIS Lecture 19 Fault Analysis Professor Tom Overbye Department of Electrical and Computer Engineering Announcements Homework 9 is 7.1, 7.17, 7.20, 7.24, 7.27 – you do not need to turn it in, but should do it before the exam Second exam is Tuesday Nov 13 in class Design Project 2 from the book (page 345 to 348) was due on Nov 15, but I have given you an extension to Nov 29. The Nov 29 date is firm! 1 Fault Analysis The cause of electric power system faults is insulation breakdown This breakdown can be due to a variety of different factors – – – – lightning wires blowing together in the wind animals or plants coming in contact with the wires salt spray or pollution on insulators 2 Fault Types There are two main types of faults – – symmetric faults: system remains balanced; these faults are relatively rare, but are the easiest to analyze so we’ll consider them first. unsymmetric faults: system is no longer balanced; very common, but more difficult to analyze The most common type of fault on a three phase system by far is the single line-to-ground (SLG), followed by the line-to-line faults (LL), double lineto-ground (DLG) faults, and balanced three phase faults 3 Lightning Strike Event Sequence 1. Lighting hits line, setting up an ionized path to ground 2. 30 million lightning strikes per year in US! a single typical stroke might have 25,000 amps, with a rise time of 10 s, dissipated in 200 s. multiple strokes can occur in a single flash, causing the lightning to appear to flicker, with the total event lasting up to a second. Conduction path is maintained by ionized air after lightning stroke energy has dissipated, resulting in high fault currents (often > 25,000 amps!) 4 Lightning Strike Sequence, cont’d 3. Within one to two cycles (16 ms) relays at both ends of line detect high currents, signaling circuit breakers to open the line 4. Circuit breakers open to de-energize line in an additional one to two cycles 5. nearby locations see decreased voltages breaking tens of thousands of amps of fault current is no small feat! with line removed voltages usually return to near normal Circuit breakers may reclose after several seconds, trying to restore faulted line to service 5 Fault Analysis Fault currents cause equipment damage due to both thermal and mechanical processes Goal of fault analysis is to determine the magnitudes of the currents present during the fault – – need to determine the maximum current to insure devices can survive the fault need to determine the maximum current the circuit breakers (CBs) need to interrupt to correctly size the CBs 6 RL Circuit Analysis To understand fault analysis we need to review the behavior of an RL circuit v(t ) 2 V cos( t ) Before the switch is closed obviously i(t) = 0. When the switch is closed at t=0 the current will have two components: 1) a steady-state value 2) a transient value 7 RL Circuit Analysis, cont’d 1. Steady-state current component (from standard phasor analysis) iac (t ) where Z I ac 2V cos(t ) Z R 2 ( L)2 R 2 X 2 V Z 8 RL Circuit Analysis, cont’d 2. Exponentially decaying dc current component idc (t ) C1e t T where T is the time constant, T L R The value of C1 is determined from the initial conditions: t 2V i (0) 0 i ac (t ) i dc (t ) cos(t Z ) C1e T Z 2V C1 cos( Z ) which depends on Z 9 Time varying current 10 RL Circuit Analysis, cont’d Hence i(t) is a sinusoidal superimposed on a decaying dc current. The magnitude of i dc (0) depends on when the switch is closed. For fault analysis we're just 2V concerned with the worst case: C1 Z i (t ) i ac (t ) i dc (t ) i (t ) 2V 2V t T cos(t ) e Z Z t 2V (cos(t ) e T ) Z 11 RMS for Fault Current t 2V The function i(t) (cos(t ) e T ) is not periodic, Z so we can't formally define an RMS value. However, as an approximation define I RMS (t ) 2 2 iac (t ) idc (t ) 2 I ac 2t 2 T 2 I ac e This function has a maximum value of 3 I ac Therefore the dc component is included simply by multiplying the ac fault currents by 3 12 Generator Modeling During Faults During a fault the only devices that can contribute fault current are those with energy storage Thus the models of generators (and other rotating machines) are very important since they contribute the bulk of the fault current. Generators can be approximated as a constant voltage behind a time-varying reactance ' Ea 13 Generator Modeling, cont’d The time varying reactance is typically approximated using three different values, each valid for a different time period: X"d direct-axis subtransient reactance X 'd direct-axis transient reactance Xd direct-axis synchronous reactance 14 Generator Modeling, cont’d For a balanced three-phase fault on the generator terminal the ac fault current is (see page 245) iac (t ) 1 1 1 ' e X Xd Xd ' d 2Ea t " 1 1 Td e X " X ' d d t Td' sin( t ) where Td" direct-axis subtransient time constant ( 0.035sec) ' Td direct-axis transient time constant ( 1sec) 15 Generator Modeling, cont'd The phasor current is then 1 1 1 ' e X Xd Xd ' d I ac Ea t " 1 1 Td X " X ' e d d t Td' The maximum DC offset is 2 Ea' I DC (t ) e " Xd t TA where TA is the armature time constant ( 0.2 seconds) 16 Generator Short Circuit Currents 17 Generator Short Circuit Currents 18 Generator Short Circuit Example A 500 MVA, 20 kV, 3 is operated with an internal voltage of 1.05 pu. Assume a solid 3 fault occurs on the generator's terminal and that the circuit breaker operates after three cycles. Determine the fault current. Assume X d" 0.15, X d' 0.24, X d 1.1 (all per unit) Td" 0.035 seconds, Td' 2.0 seconds TA 0.2 seconds 19 Generator S.C. Example, cont'd Substituting in the values 1 t 2.0 1 1 e 1.1 0.24 1.1 I ac (t ) 1.05 1 1 e t 0.035 0.15 0.24 I ac (0) 1.05 7 p.u. 0.15 I base 500 106 14,433 A I ac (0) 101,000 A 3 3 20 10 I DC (0) 101 kA 2 e t 0.2 143 k A IRMS (0) 175 kA 20 Generator S.C. Example, cont'd Evaluating at t = 0.05 seconds for breaker opening 1 0.05 2.0 1 1 e 1.1 0.24 1.1 I ac (0.05) 1.05 0.05 1 1 e 0.035 0.15 0.24 I ac (0.05) 70.8 kA I DC (0.05) 143 e 0.05 0.2 kA 111 k A I RMS (0.05) 70.82 1112 132 kA 21 Network Fault Analysis Simplifications To simplify analysis of fault currents in networks we'll make several simplifications: 1. 2. 3. 4. 5. Transmission lines are represented by their series reactance Transformers are represented by their leakage reactances Synchronous machines are modeled as a constant voltage behind direct-axis subtransient reactance Induction motors are ignored or treated as synchronous machines Other (nonspinning) loads are ignored 22 Network Fault Example For the following network assume a fault on the terminal of the generator; all data is per unit except for the transmission line reactance generator has 1.05 terminal voltage & supplies 100 MVA with 0.95 lag pf Convert to per unit: X line 19.5 0.1 per unit 2 138 100 23 Network Fault Example, cont'd Faulted network per unit diagram To determine the fault current we need to first estimate the internal voltages for the generator and motor For the generator VT 1.05, SG 1.018.2 * I Gen 1.018.2 0.952 18.2 1.05 ' Ea 1.1037.1 24 Network Fault Example, cont'd The motor's terminal voltage is then 1.050 - (0.9044 - j 0.2973) j 0.3 1.00 15.8 The motor's internal voltage is 1.00 15.8 (0.9044 - j 0.2973) j 0.2 1.008 26.6 We can then solve as a linear circuit: 1.1037.1 1.008 26.6 If j 0.15 j 0.5 7.353 82.9 2.016 116.6 j 9.09 25 Fault Analysis Solution Techniques Circuit models used during the fault allow the network to be represented as a linear circuit There are two main methods for solving for fault currents: 1. 2. Direct method: Use prefault conditions to solve for the internal machine voltages; then apply fault and solve directly Superposition: Fault is represented by two opposing voltage sources; solve system by superposition – first voltage just represents the prefault operating point – second system only has a single voltage source 26 Superposition Approach Faulted Condition Exact Equivalent to Faulted Condition Fault is represented by two equal and opposite voltage sources, each with a magnitude equal to the pre-fault voltage 27 Superposition Approach, cont’d Since this is now a linear network, the faulted voltages and currents are just the sum of the pre-fault conditions [the (1) component] and the conditions with just a single voltage source at the fault location [the (2) component] Pre-fault (1) component equal to the pre-fault power flow solution Obvious the pre-fault “fault current” is zero! 28 Superposition Approach, cont’d Fault (1) component due to a single voltage source at the fault location, with a magnitude equal to the negative of the pre-fault voltage at the fault location. I g I (1) I g(2) g I m I m(1) I m(2) (2) (2) I f I (1) I 0 I f f f 29 Two Bus Superposition Solution Before the fault we had E f 1.050, I (1) 0.952 18.2 and I m(1) 0.952 18.2 g Solving for the (2) network we get Ef 1.050 (2) Ig j7 j0.15 j0.15 E f 1.050 (2) Im j 2.1 j0.5 j0.5 I (2) f j 7 j 2.1 j 9.1 I g 0.952 18.2 j 7 7.35 82.9 This matches what we calculated earlier 30 Extension to Larger Systems The superposition approach can be easily extended to larger systems. Using the Ybus we have Ybus V I For the second (2) system there is only one voltage source so I is all zeros except at the fault location 0 I I f 0 However to use this approach we need to first determine If 31 Determination of Fault Current Define the bus impedance matrix Z bus as Z bus Z11 Then Z n1 1 Ybus V Z busI (2) V 1 (2) Z1n 0 V2 I f Z nn 0 V (2) n 1 (2) Vn For a fault a bus i we get -If Zii V f Vi (1) 32 Determination of Fault Current Hence Vi(1) If Zii Where Zii driving point impedance Zij (i j ) transfer point imepdance Voltages during the fault are also found by superposition Vi Vi(1) Vi(2) Vi(1) are prefault values 33