* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download Metasys Integrator Cutler-Hammer Application
Survey
Document related concepts
History of electric power transmission wikipedia , lookup
Current source wikipedia , lookup
Transmission line loudspeaker wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Stray voltage wikipedia , lookup
Opto-isolator wikipedia , lookup
Buck converter wikipedia , lookup
Power electronics wikipedia , lookup
Surge protector wikipedia , lookup
Mains electricity wikipedia , lookup
Voltage optimisation wikipedia , lookup
Network analysis (electrical circuits) wikipedia , lookup
Alternating current wikipedia , lookup
Immunity-aware programming wikipedia , lookup
Transcript
Application Note Issue Date May 25, 2004 APPLICATION NOTE Metasys Integrator® Cutler-Hammer® Application Introduction 3 Application Details 3 Component Requirements 9 Vendor Contact Information 11 Design Considerations 11 Cable Connections 13 Cable Pinouts 13 Connecting the Cable 13 Metasys Integrator Unit Setup 15 Point Mapping Tables 17 IQ 1000 II 17 IQ Data Plus II 19 IQ Data Plus 4000 20 Advantage 21 Advantage Control Module (ACM) 22 IQ Energy Sentinel 23 IQ Generator or Data 23 AEM II/CMU 24 Digitrip II 25 IQ Analyzer 26 Digitrip MV 30 Digitrip RMS 810 31 Digitrip 3000 32 © 2004 Johnson Controls, Inc. Code No. LIT-6295245 1 www.johnsoncontrols.com 2 Metasys Network Setup 33 Mapping to a CS Object 33 Custom Integration 34 Metasys Integrator—Metasys Integrator Cutler-Hammer Application Introduction This document explains Metasys Integrator® Cutler-Hammer® application. Use this document with the Metasys Integrator unit technical bulletins, which provide information on installing and commissioning the Metasys Integrator unit. For information on Cutler-Hammer equipment, see Cutler-Hammer documentation (obtainable from a Cutler-Hammer representative). Note: If you use a Universal Packaging Module (UPM) enclosure, you must install the Metasys Integrator unit 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note. Application Details The Metasys Integrator unit allows Cutler-Hammer equipment to become an integral part of the Metasys® and Metasys Companion™ Networks. Once Cutler-Hammer Integrated, Monitoring, Protection, and Control Communications (IMPACC™) devices are connected to the Metasys or Companion Network via the Metasys Integrator unit, their data is available to the full complement of Metasys Building Automation System (BAS) features, including Change-of-State (COS) monitoring, alarm notification, trend, and totalization. The Metasys Integrator unit allows status information and commands to be transmitted between the IMPACC devices and the Metasys or Companion Network. Cutler-Hammer IMPACC devices may interface with non-Cutler-Hammer devices (such as the Metasys Integrator unit) in three ways: through a Cutler-Hammer Master INCOM Network Translator II (MINT II), through a Personal Computer (PC) running Cutler-Hammer Series III software equipped with Cutler-Hammer MINT II, or through a PC equipped with a Cutler-Hammer Computer Operated Network Interface (CONI) Expansion Card and Series III software. The Metasys Integrator unit supports a direct connection to the following Cutler-Hammer applications: • IQ 1000 II™ • IQ Data Plus II™ • IQ Data Plus 4000 • Advantage™ • Advantage Control Module (ACM) • IQ Energy Sentinel™ Metasys Integrator—Metasys Integrator Cutler-Hammer Application 3 • IQ Generator or Data™ • Assemblies Electronic Monitor (AEM) II with subnetwork devices • Digitrip II • IQ Analyzer • Central Monitoring Unit (CMU) with subnetwork devices • Digitrip MV • Digitrip 810 • Digitrip 3000 The AEM II subnetwork devices that are supported are: • Digitrip II • IQ Data Plus II Note: As a subnetwork, the AEM II can monitor and display up to 40 breakers equipped with Digitrip II RMS 700 or Digitrip II RMS 800 trip units, and up to 8 Data Plus II devices. The CMU subnetwork devices that are supported are: • Advantage • ACM Note: As a subnetwork, the CMU monitors and displays data for up to 99 Advantage starters. Each Metasys Integrator vendor port can connect to one MINT II. Each MINT II can connect to up to 1000 Cutler-Hammer controllers. (However, the Metasys Integrator system has a 255 device limit and is subject to overall N2 point data size limitations. See the Metasys Integrator unit technical bulletins for more information. Figure 1 shows Cutler-Hammer and Metasys Integrator unit integration when using the MINT II. Figure 2 shows Cutler-Hammer and Metasys Companion integration when using the MINT II. Figure 3 shows Cutler-Hammer Series III and Metasys Integrator unit integration when using a CONI card. Figure 4 shows Cutler-Hammer Series III and Metasys Integrator unit integration when using the MINT II. 4 Metasys Integrator—Metasys Integrator Cutler-Hammer Application N1 LAN RS-232 Metasys Integrator Unit Master INCOM Network Translator (MINT II) Standard NCU (Network Control Unit) IQ Generator or Data IQ Energy Sentinel IQ Data Plus II IQ Data Plus 4000 CMU Digitrip MV Digitrip 810 Digitrip 3000 Advantage Starter Advantage Control Module Subnetwork Note: IQ 1000 II Advantage ACM AEM II II Digitrip II IQ Data Plus II Subnetwork westing1 UNT (Unitary Controller) N2 Bus If you use a UPM enclosure, you must install the Metasys Integrator unit 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note. Figure 1: Cutler-Hammer and Metasys System Integration via MINT II Metasys Integrator—Metasys Integrator Cutler-Hammer Application 5 Panel Unit Workstation RS-232 Master INCOM Network Translator (MINT 11) Metasys Integrator Unit N2 Bus IQ Generator or Data IQ Energy Sentinel IQ Data Plus II IQ Data Plus 4000 IQ 1000 II Advantage CMU Digitrip MV Digitrip 810 Digitrip 3000 AEM II ACM Advantage Starter Advantage Control Module Subnetwork Digitrip II IQ Data Plus II Subnetwork Note: A PC version and converter may be substituted for the Panel unit. Note: westcomp UNT If you use a UPM enclosure, you must install the Metasys Integrator unit 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note. Figure 2: Cutler-Hammer and Metasys Companion Integration via MINT II The data from Cutler-Hammer equipment may be graphically analyzed by installing Cutler-Hammer Series III software on a PC, which is equipped with a Cutler-Hammer Computer Operated Network Interface (CONI) Expansion Card or MINT II. The CONI card is connected to IQ Analyzers (or other IMPACC compliant devices) via twisted pair cable. Each Metasys Integrator vendor port can then connect an available serial port (COM1 or COM2) at the PC. See Figure 3 and Figure 4. 6 Metasys Integrator—Metasys Integrator Cutler-Hammer Application N1 LAN PC with CONI Card Running Series III Software Standard NCU RS-232 to COM1 or COM2 Twisted Pair* from CONI Metasys Integrator Unit N2 Bus IQ Generator or Data IQ Energy Sentinel IQ Data Plus II IQ Data Plus 4000 IQ 1000 II Advantage CMU Digitrip MV Digitrip 810 Digitrip 3000 AEM II II ACM Advantage Starter Advantage Control Module Subnetwork Note: Digitrip II IQ Data Plus II Subnetwork *7,500 ft Maximum sys3CONI UNT If you use a UPM enclosure, you must install the Metasys Integrator unit 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note. Figure 3: Cutler-Hammer Series III and Metasys System Integration via CONI Card Metasys Integrator—Metasys Integrator Cutler-Hammer Application 7 N1 LAN PC Running Series III Software Standard NCU RS-232 to COM1 or COM2 RS-232 to COM1 or COM2 MINT II UNT IQ Energy Sentinel IQ Data Plus II IQ Data Plus 4000 CMU Digitrip MV Digitrip 810 Digitrip 3000 Advantage Starter Advantage Control Module Subnetwork Note: IQ 1000 II Digitrip II Advantage AEM II IQ Data Plus II Subnetwork If you use a UPM enclosure, you must install the Metasys Integrator unit 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note. Figure 4: Cutler-Hammer Series III and Metasys System Integration via MINT II 8 Metasys Integrator—Metasys Integrator Cutler-Hammer Application MINT N2 Bus IQ Generator or Data Component Requirements MINT II Series III To integrate Cutler-Hammer equipment using the MINT II, you need the following components: • properly installed Cutler-Hammer Master INCOM Network Translator (MINT II) and Cutler-Hammer IMPACC devices • RS-232 cable (for connecting MINT II to the Metasys Integrator unit) • Metasys Integrator unit • N2 Bus (for connecting Metasys Integrator unit to the Metasys or Companion Network) • portable PC for downloading vendor communication tables (.VCT files) and network setup information into the Metasys Integrator controller, and for running diagnostics • cable for connecting portable PC to Metasys Integrator controller • the correct vendor communication table (.VCT file) to download into Metasys Integrator controller (supplied on Metasys Integrator CD-ROM) To integrate Cutler-Hammer equipment using a PC running the Series III software, you need the following components: • Pentium® PC with properly installed Cutler-Hammer CONI expansion card or MINT II • properly installed Cutler-Hammer IMPACC devices to the PC running Cutler-Hammer Series III software • RS-232 cable (for connecting the PC COM1 port to the Metasys Integrator unit) • Metasys Integrator unit • N2 Bus (for connecting Metasys Integrator unit to the Metasys or Companion Network) • portable PC for downloading vendor communication tables (.VCT files) and network setup information into the Metasys Integrator unit, and for running diagnostics • cable for connecting portable PC to the Metasys Integrator unit • the correct vendor communication table (.VCT file) to download into the Metasys Integrator unit (supplied on Metasys Integrator CD-ROM) This document describes the RS-232 cable and the vendor communication tables. Cutler-Hammer documentation describes their equipment. The remaining components are described in the Metasys Integrator unit technical bulletins. Metasys Integrator—Metasys Integrator Cutler-Hammer Application 9 Metasys Network Release Requirements Metasys Companion Release Requirements Vendor Component Requirements To integrate Cutler-Hammer equipment into the Metasys Network, you need: • Metasys Operator Workstation (OWS) software Release 4.0 or later • Metasys Integrator unit firmware Release 9.0 or later • Metasys Integrator unit software Release 9.3 or later To integrate Cutler-Hammer equipment into the Metasys Companion Network, you need: • Metasys Companion Release 4.0 or later • Metasys Integrator unit firmware Release 9.0 or later • Metasys Integrator unit software Release 9.3 or later Integration between the Metasys Integrator unit and Cutler-Hammer has been tested with the equipment listed in Table 1. Changes to this equipment or integration of Cutler-Hammer products not discussed in this document require additional software development and testing by Systems Products. For information on integrating other products, refer to the Custom Integration section in this document. Table 1: Cutler-Hammer Part and Software Version Numbers Cutler-Hammer Product Style Number Software Version Number MINT II MINTII 6.50 IQ 1000 II IQ1000II E6 IQ Data Plus II IQDPII 7.1 IQ Data Plus 4000 IQDP 4000 Advantage WPONI V16 Advantage Control Module (ACM) Product ID 35, 36, 37, 38, 39 4.30 IQ Energy Sentinel IQESF208 IQESF480 IQESJ208 IQESJ480 IQESK208 IQESK480 (F Frame, 120/208 VAC) (F Frame, 277/480 VAC) (J Frame, 120/208 VAC) (J Frame, 277/480 VAC) (K Frame, 120/208 VAC) (K Frame, 277/480 VAC) IQ Generator or Data IQDATA IQGEN (IQ Data) (IQ Generator) Assemblies Electronic Monitor II 2D78548G01 Series III S320, S3200, S31000 CONI Card 5275C78601 N/A IQ Analyzer IQA 6010 or IQA 6210 1.12 Continued on next page . . . 10 Metasys Integrator—Metasys Integrator Cutler-Hammer Application 6.5 Vendor Contact Information Cutler-Hammer Product (Cont.) Style Number Software Version Number Digitrip II Any Digitrip from the Cutler-Hammer Low Voltage Digitrip RMS 700 or 800 Family Digitrip MV 3D86762G01 3.0 Digitrip 810 7829C08G06 3.0 Digitrip 3000 Product ID 3 4.0 CMU Product ID 29 4.0 or greater Eaton Electrical, Inc./Cutler-Hammer Advanced Products Support Center Phone: 800-809-2772 www.eatonelectrical.com Design Considerations When integrating Cutler-Hammer equipment, keep the following considerations in mind: • Make sure all Cutler-Hammer equipment is set up and running properly before attempting to integrate with the Metasys or Companion Network. (The Cutler-Hammer representative is responsible for operation of MINT II controllers, Series III, and CONI card.) • Make sure the MINT II baud rate is set to 9600 baud. (The Cutler-Hammer representative is responsible for setting the MINT II baud rate.) • Set the DIP switches on the MINT II to the settings listed below. For more detailed information, refer to Instructions for Master Network Translator II (I.L. 17466 Model B) available from your Cutler-Hammer representative. • On the WPONI attached to the Advantage Control Module, make sure the address on rotary dial A-1 is not set to A through F. This will disable the communications watchdog timer. The Cutler-Hammer representative is responsible for setting the address. Metasys Integrator—Metasys Integrator Cutler-Hammer Application 11 Table 2: DIP Switch Settings for the MINT II Setting RS-232 Baud (9600) INCOM Baud (9600) SW 1 SW 2 on off SW 3 SW 4 SW 5 SW 6 SW 7 off Stop Bits (2 Bits) on Modem Control (No RTS/CTS) Ack/Nack Byte (Sent) on off Handshake Byte (Not Sent) • RS-232 cable distance between the Metasys Integrator unit and the MINT II can be a maximum of 50 feet. • Cable distance between the MINT II and the last controller can be a maximum of 7500 feet. • The MINT II is also used in the Ingersoll-Rand® application. Ingersoll-Rand and Cutler-Hammer are in the same vendor family (meaning you can have both applications on the same Metasys Integrator vendor trunk and vendor port). • When integrating Cutler-Hammer equipment through the Series III, configure Series III to function COM1 or COM2, whichever is connected to the Metasys Integrator unit. Configure the Series III as a gateway (set the proper jumper in the CONI card) with the following settings for the communications port: Baud Rate Stop Bits Parity ACK/NACK Handshake Word Length • 12 off 9600 2 None Sent No 8 Distance between devices and the master control unit cannot exceed 7500 feet. Metasys Integrator—Metasys Integrator Cutler-Hammer Application Cable Connections Cable Pinouts Use the cable pinouts in Figure 5 for the RS-232 connection between the Metasys Integrator unit and the Cutler-Hammer Master INCOM Network Translator II. Vendor Port A or B on Metasys Integrator RS-232 Port on MINT II DB-9 Female DB-25 Male Signal Pin Pin Signal 2 3 7 RD TD GND RS-232 TD RD GND 3 2 5 (50 ft maximum) WESTING2 Figure 5: Cable Pinouts on MINT II Vendor Port A or B on Metasys Integrator RS-232 Port on Series III DB-9 Female DB-9 Female Signal Pin DCD TD RD DTR GND 1 2 3 4 5 Pin Signal 1 3 2 4 5 DCD RD TD DTR GND RS-232 (50 ft maximum) cblser3 Figure 6: Cable Pinouts on Series III Connecting the Cable Connect the female end of the RS-232 cable to either Vendor Port A or Vendor Port B on the Metasys Integrator unit. Connect the male end of the cable to the RS-232 Port on the MINT II. Master INCOM Network Translator II Metasys Integrator Vendor Port A or B RS-232 Cable RS-232 Port WESTING3 Figure 7: Port to Port Connection with MINT II Metasys Integrator—Metasys Integrator Cutler-Hammer Application 13 PC with CONI Card Running Series III Software Metasys Integrator Vendor Port A or B RS-232 Cable RS-232 Port Twisted Pair Cutler-Hammer Devices WESTING4 Figure 8: Port to Port Connection with Series III Using CONI Card PC Running Series III Software Metasys Integrator Vendor Port A or B RS-232 Cable RS-232 Port MINT II RS-232 Cable RS-232 Port Twisted Pair Cutler-Hammer Devices WESTING5 Figure 9: Port to Port Connection with Series III Using MINT II 14 Metasys Integrator—Metasys Integrator Cutler-Hammer Application Metasys Integrator Unit Setup To set up the Metasys Integrator unit, use a portable PC connected to the Metasys Integrator Terminal Port. Metasys Integrator unit setup involves: • downloading the correct vendor communication table (.VCT file) • setting up the ports • assigning network addresses to the controllers The following table provides information specific to Cutler-Hammer applications. For detailed procedures, see the Metasys Integrator unit technical bulletins. Table 3: Metasys Integrator Unit Setup for Cutler-Hammer Applications Vendor Communication Table (.VCT File) Advantage iq_adva.vct Advantage Control Module (ACM) iq_acm3x.vct IQ 1000 II iq_1000.vct IQ Energy Sentinel iq_ener.vct IQ Generator iq_gene.vct IQ Data Plus II iq_data.vct IQ Data Plus 4000 iq_dp4k.vct IQ Analyzer iq_analy.vct Digitrip 810 iq_dt810.vct Digitrip 3000 Iq_dt3k.vct Digitrip MV iq_dtmv.vct AEM II Subnetwork Devices Digitrip RMS IQ Data Plus II iq_aem.vct CMU Subnetwork Devices Advantage ACM iq_aem.vct iq_aemdi.vct iq_aemdp.vct iq_cmadv.vct iq_cmacm.vct Port Setup Baud Rate 9600 Word Length 8 Stop Bits 2 Parity None Interface RS-232 Continued on next page . . . Metasys Integrator—Metasys Integrator Cutler-Hammer Application 15 Network Setup (Cont.) Vendor Address Vendor address in the Metasys Integrator unit is the decimal equivalent of the hex address set via the switches on the Cutler-Hammer equipment. Example: When the Cutler-Hammer switch setting is 017, the vendor address is 23. IQ 1000 II 0 to 4095 IQ Data Plus II 0 to 4095 IQ Data Plus 4000 0 to 4095 Advantage 0 to 4095 Advantage Control Module* 0 to 4095 IQ Energy Sentinel 0 to 1024 IQ Generator or Data 0 to 4095 AEM II 0 to 4095 IQ Analyzer 0 to 4095 * Do not use hexadecimal A through F as the last digit of the rotary address of the WPONI attached to the ACM (or starter automatically stops if no communication within 5 seconds). Vendor Address for Subnetwork Devices Subnet vendor address entered in the Metasys Integrator Network Configuration Screen is the decimal equivalent of the hex address set via the switches on the Cutler-Hammer equipment. Example: When the Cutler-Hammer subnet switch setting is 41, the vendor subnet address is 65. Allowable Values at Digitrip II, IQ Data Plus II, Advantage, Advantage Starters Hexadecimal Switches 1-9, 10-19, 20-29, 30-39, 40-49, 50-59, 60-69, 70-79, 80-89, 90-99 Corresponding Decimal Values at the Metasys Integrator Unit: 1-9, 16-25, 32-41, 48-57, 64-73, 80-89, 96-105, 112-121, 128-137, 144-153 To enter the subnetwork vendor address, type the AEMII or CMU address, followed by a comma and the subnetwork device address. For example: 1024,20 Timeout Value MINT II Poll Delay 1500 ms Series III with CONI 6000 ms Series III with MINT II 6000 ms 55 ms 0 0 Mint II Series III Series III 2 seconds 1 second 5 seconds 2 seconds 3 seconds 3 seconds 4 seconds 4 seconds 1 second 1 second 1 second 2 seconds 4 seconds 6 seconds 3 seconds 2 seconds and CONI 15 seconds 1 second 38 seconds 15 seconds 23 seconds 23 seconds 26 seconds 30 seconds 1 second 1 second 1 second 15 seconds 30 seconds 45 seconds 23 seconds 15 seconds and MINT II 22 seconds 1 second 55 seconds 22 seconds 33 seconds 33 seconds 37 seconds 44 seconds 1 second 1 second 1 second 22 seconds 44 seconds 66 seconds 33 seconds 22 seconds Performance Guide Approximate Scan Time (For a single N2 address) Advantage Advantage Control Module (ACM) IQ 1000 II IQ Energy Sentinel IQ Generator/Data IQ Data Plus II IQ Data Plus 4000 IQ Analyzer Digitrip 810 Digitrip 3000 Digitrip MV IQ AEM II / CMU Digitrip II (AEM subnet) IQ DataPlus II (AEM subnet) Advantage (CMU subnet) ACM (CMU subnet) 16 Metasys Integrator—Metasys Integrator Cutler-Hammer Application Point Mapping Tables The following tables (one for each application) show the points available for mapping in the Cutler-Hammer controllers. IQ 1000 II Table 4: IQ 1000 II Multifunction Motor Protective Relay NPT1 To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Phase C Current point is AI3. AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI 1 2 NPA Unit Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Amps Amps Amps Amps DegC DegC DegC DegC DegC DegC DegC DegC DegC DegC DegC Phase A Current Phase B Current Phase C Current Ground Current Winding Temperature 1 Winding Temperature 2 Winding Temperature 3 Winding Temperature 4 Winding Temperature 5 Winding Temperature 6 Motor Bearing Temperature 1 Motor Bearing Temperature 2 Load Bearing Temperature 1 Load Bearing Temperature 2 Auxiliary Temperature 2 Network Point Type Network Point Address Continued on next page . . . Metasys Integrator—Metasys Integrator Cutler-Hammer Application 17 NPT1 (Cont.) BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 2 18 NPA 2 Unit Description Ready to Start Motor Motor is Running Motor Trip Status Motor Alarm Status Instantaneous Over Current Trip I2 T Trip Phase Unbalance Trip Ground Fault Trip Jam Trip Under Load Trip Trip Bypass Remote Trip (via Hardware Input) Motor Bearing Temperature Trip Load Bearing Temperature Trip Winding Temperature Trip Reverse Sequence Trip Incomplete Sequence Trip External Trip (via IMPACC) Differential Trip on AC Input Ambient Temperature Trip Phase Unbalance Alarm Winding Temperature Alarm Motor Bearing Temperature Alarm Load Bearing Temperature Alarm Jam Alarm Under Load Alarm Ambient Temperature Alarm I2 T Alarm/Trip Starts per Hour Alarm/Trip Code Code % Amps DegC 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, Product ID Communications Software Version Operations Count Run Time Remaining Starts Oldest Start Time Percent I2 T Highest Phase Current Highest RTD Temperature Number I2 T Trips Number Instantaneous Over Current Trips Number of Under Load Trips Number of Jam Trips Number of Ground Fault Trips Number of RTD Trips Network Point Type Network Point Address Metasys Integrator—Metasys Integrator Cutler-Hammer Application 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes IQ Data Plus II To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Phase C Current point is AI3. Table 5: IQ Data Plus II Electrical Monitoring Functions (Direct Connection or via an AEM II Subnetwork) NPT1 NPA Unit Description AI AI AI AI AI AI AI AI AI AI AI AI AI AI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Amps Amps Amps Volt Volt Volt Volt Volt Volt kW kW Hz kVA Phase A Current Phase B Current Phase C Current Line-to-Line Voltage VAB Line-to-Line Voltage VBC Line-to-Line Voltage VCA Line-to-Neutral Voltage VAN Line-to-Neutral Voltage VBN Line-to-Neutral Voltage VCN Power Demand Frequency Reactive Power Power Factor BI BI BI BI BI BI BI BI 1 2 3 4 5 6 7 8 ADF ADF ADF 1 2 3 1 2 2 Trip Flag Alarm Flag External Trip Over Voltage Trip Under Voltage Trip Phase Unbalance Trip Phase Loss Trip Phase Reversal Trip Code Code kWh 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes Product ID Communications Software Version Energy Network Point Type Network Point Address Metasys Integrator—Metasys Integrator Cutler-Hammer Application 19 IQ Data Plus 4000 To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Phase C Current point is AI3. Table 6: IQ Data Plus 4000 NPT1 NPA2 Unit Description AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Amps Amps Amps Volt Volt Volt Volt Volt Volt kW kW Hz kVA Phase A Current Phase B Current Phase C Current Line-to-Line Voltage VAB Line-to-Line Voltage VBC Line-to-Line Voltage VCA Line-to-Neutral Voltage VAN Line-to-Neutral Voltage VBN Line-to-Neutral Voltage VCN Power Demand Frequency Reactive Power Power Factor Demand Watts (Window) Demand VARS (Window) Demand Volt-Amps (Window) Peak Demand Watts Peak Demand VARS Peak Demand Volt-Amps BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Trip Flag Alarm Flag Loss of Phase Current Trip Phase Reversal Trip Phase Unbalance Trip Loss of Phase Voltage Trip Under Voltage Trip Over Voltage Trip IMPACC Trip Alarm 1 Active Trip Loss of Phase Current Alarm Phase Reversal Alarm Phase Unbalance Alarm Loss of Phase Voltage Alarm Under Voltage Alarm Over Voltage Alarm IMPACC Alarm Alarm 1 Active Alarm 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes BO BO BO 1 2 3 Reset Demand Window Reset Energy Values Reset Peak Demand 0-no, 0-no, 0-no, 1-yes 1-yes 1-yes ADF ADF ADF 1 2 3 1 2 20 Watts VARS VA Watts VARS VA Code Code kWh Product ID Communications Software Version Energy Network Point Type Network Point Address Metasys Integrator—Metasys Integrator Cutler-Hammer Application Advantage To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Phase C Current point is AI3. Table 7: Advantage Monitoring Unit for Starter or Contactors (Direct Connection or via a CMU Subnetwork) NPT1 NPA Unit Description AI AI AI 1 2 3 Amps Amps Amps Phase A Current Phase B Current Phase C Current BI BI BI BI BI BI BI BI 1 2 3 4 5 6 7 8 ADF ADF ADF 1 2 3 Code Code Code 4 Volt ADF 2 Starter Open Status Starter Closed Status Starter Tripped Status Starter Alarmed Status Overload Start Signal Present Remote Reset Present Local Reset Present 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes Product ID Communications Software Version Trip Type # 1 - Overload 2 - Ground Current Trip 3 - Phase Loss Trip 4 - Phase Unbalance Trip 16 - Ground Current exceeds interrupt capacity 32 - Control Voltage too low -> unit will open 48 - Control Voltage too low to pick up 64 - Control Voltage too high to pick up 80 - Current too low to close 112 - External Trip (via INCOM) Line Voltage 1 Network Point Type 2 Network Point Address Metasys Integrator—Metasys Integrator Cutler-Hammer Application 21 Advantage Control Module (ACM) To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Phase C Current point is AI3. Table 8: Advantage Control Module (ACM) Product ID 35, 36, 37, 38, 39 (Direct Connection or via a CMU Subnetwork) NPT1 NPA2 Unit Description AI AI AI 1 2 3 Amps Amps Amps Phase A Current Phase B Current Phase C Current BI BI BI BI BI BI BI BI BI BI BI BI BI BI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 AO 1 Code Send command*: 0,1,2,3,4,5 0-No Effect 1-Stop 2-Start Fast Forward 3-Start Slow Forward3 4-Start Reverse4 5-Reset Trip/Unit ADF ADF ADF 1 2 3 Code Code Code ADF 4 Volt Product ID Communications Software Version Trip Type # 0 - Normal 1 - Overload 2 - Ground Current Trip 3 - Phase Loss Trip 4 - Phase Unbalance Trip 16 - Ground Current exceeds interrupt capacity 32 - Control Voltage too low -> unit will open 48 - Control Voltage too Low to pick up 64 - Control Voltage too high to pick up 80 - Current too low to close 112 - External Trip (via INCOM) Line Voltage 1 2 3 4 * 22 Starter Open Starter Closed Starter Tripped Starter Alarmed Overload Start Signal Present Remote Reset Present Local Reset Present Stop Forward or Fast Forward Reverse or Slow Forward Off Mode Auto Mode Hand Mode Network Point Type Network Point Address Only for Product ID 37, 38, 39 Only for Product ID 36 Can command only when in Auto mode. Metasys Integrator—Metasys Integrator Cutler-Hammer Application 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes IQ Energy Sentinel To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Alarm Status point is BI3. Table 9: IQ Energy Sentinel Circuit Breaker Monitoring NPT1 NPA Unit Description AI 1 Watts Instantaneous Power BI BI BI BI BI BI 1 2 3 4 5 6 ADF ADF ADF ADF ADF 1 2 3 4 5 1 2 IQ Generator or Data To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Phase C Current point is AI3. 2 Inactive Active Alarm Status Energy for Phase A is Negative Energy for Phase B is Negative Energy for Phase C is Negative Code Code kWh 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes Product ID Communications Software Version Energy 5 Minute Average Power Update Counter 5 Minute Average of Power Network Point Type Network Point Address Table 10: IQ Generator or Data Electrical Monitoring Functions NPT1 NPA Unit Description AI AI AI AI AI AI AI AI AI AI 1 2 3 4 5 6 7 8 9 10 Amps Amps Amps Volt Volt Volt Volt Volt Volt Hz Phase A Current Phase B Current Phase C Current Line-to-Line Voltage VAB Line-to-Line Voltage VBC Line-to-Line Voltage VCA Line-to-Neutral Voltage VAN Line-to-Neutral Voltage VBN Line-to-Neutral Voltage VCN Frequency ADF ADF 1 2 Code Code Product ID Communications Software Version 1 2 2 Network Point Type Network Point Address Metasys Integrator—Metasys Integrator Cutler-Hammer Application 23 AEM II/CMU To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Active point is BI2. 24 Table 11: Assemblies Electronic Monitor (AEM) II--Monitor Display Electrical Central Monitoring Unit (CMU) NPT1 NPA 2 BI BI BI 1 2 3 BI 4 ADF ADF 1 2 1 2 Unit Description Inactive (no devices on subnetwork) Active Tripped (trip occurred and has not been acknowledged) Alarm (Digitrip in high load) Code Code Product ID Communications Software Version Network Point Type Network Point Address Metasys Integrator—Metasys Integrator Cutler-Hammer Application 0-no, 0-no, 1-yes 1-yes 0-no, 0-no, 1-yes 1-yes Digitrip II Digitrip II and IQ Data Plus II are supported on the AEM II subnetwork: Table 12: Digitrip II as a Subnetwork Device of AEM II Use Table 12 and Table 5 to map points to devices in the AEM II subnetwork. To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Phase C Current point is AI3. NPT1 NPA Unit Description AI AI AI AI AI AI AI 1 2 3 4 5 6 7 Amps Amps Amps Amps MW MW WH Phase A Current Phase B Current Phase C Current Ground Current (if trip unit has ground fault) Power Demand Watts Energy BI BI BI BI BI BI BI BI BI BI BI BI BI BI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Long Delay Trip Short Delay Trip Instantaneous Trip Discriminator Trip Ground Fault Trip Breaker Trip External Trip (via INCOM) High Load Alarm Negative Power Reading Override Trip Hertz Flag Long Delay Protection in Progress Ground Test Initiated Status of Breaker 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-60, 0-no, 0-no, 0-closed, 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-50 1-yes 1-yes 1-open BI BI BI BI 15 16 17 18 Plug Trip Inactive Active Tripped (trip occurred and has not been acknowledged) Alarm (Digitrip in High Load) 0-no, 0-no, 0-no, 1-yes 1-yes 1-yes 0-no, 0-no, 1-yes 1-yes 2 BI 19 ADF ADF ADF 1 2 3 1 2 Code Code kWh Product ID Communications Software Version Accumulated Energy AEM II Network Point Type Network Point Address Metasys Integrator—Metasys Integrator Cutler-Hammer Application 25 IQ Analyzer To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Phase C Current point is AI3. Table 13: IQ Analyzer Electrical Monitoring Functions NPT1 NPA2 Unit Description AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Amps Amps Amps Amps Amps Volt Volt Volt Volt Volt Volt Volt Volt Volt kW kVAR kVA # # Hz kW kW kW kW kW Phase A Current Phase B Current Phase C Current Ground Current Average Phase Current Line-to-Line Voltage VAB Line-to-Line Voltage VBC Line-to-Line Voltage VCA Average Line-to-Line Voltage Line-to-Neutral Voltage VAN Line-to-Neutral Voltage VBN Line-to-Neutral Voltage VCN Average Line-to-Neutral Voltage Neutral-to-Ground Real Power 3-phase Reactive Power 3-phase Volt-Amperes 3-phase pf Displacement 3-phase pf Apparent 3-phase Frequency Real Power Phase A Real Power Phase B Real Power Phase C Reactive Power Phase A Reactive Power Phase B 1 2 Network Point Type Network Point Address Continued on next page . . . 26 Metasys Integrator—Metasys Integrator Cutler-Hammer Application NPT1 NPA2 (Cont.) Unit Description AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI kW kVA kVA kVA % % % % % % % % % % % % % % % % Amps Amps Amps Amps Amps Amps Amps Amps kW kVAR kVA kW kVAR kVA Reactive Power Phase C Volt-Amperes Phase A Volt-Amperes Phase B Volt-Amperes Phase C pf Displacement Phase A pf Displacement Phase B pf Displacement Phase C pf Apparent Phase A pf Apparent Phase B pf Apparent Phase C % Total Harmonic Distortion Phase A Current % Total Harmonic Distortion Phase B Current % Total Harmonic Distortion Phase C Current % Total Harmonic Distortion Neutral Current % Total Harmonic Distortion Phase A-B Voltage % Total Harmonic Distortion Phase B-C Voltage % Total Harmonic Distortion Phase C-A Voltage % Total Harmonic Distortion Phase A-N Voltage % Total Harmonic Distortion Phase B-N Voltage % Total Harmonic Distortion Phase C-N Voltage Average (Window) 3-phase Average Peak 3-phase Average Average (Window) Phase A Current Average (Window) Phase A Current Average (Window) Phase A Current Peak Phase A Average Peak Phase B Average Peak Phase C Average Average (Window) Real Power Average (Window) Reactive Power Average (Window) Volt-Amperes Peak Real Power Peak Reactive Power Peak Volt-Amperes 1 2 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 Network Point Type Network Point Address Continued on next page . . . Metasys Integrator—Metasys Integrator Cutler-Hammer Application 27 NPT1 NPA2 (Cont.) BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 ADF ADF ADF ADF ADF 1 2 3 4 5 1 2 Unit Description Program Mode Normal In Alarm and Program Mode Alarm Relay Output 1 Status Relay Output 2 Status Relay Output 3 Status Relay Output 4 Status Digital Input 1 Active Digital Input 2 Active Digital Input 3 Active Digital Output 1 Closed Digital Output 2 Closed Digital Output 3 Closed Digital Output 4 Closed Internal Register Failure Multiplication Failure Division Failure Logic Failure Addition or Subtraction Failure Internal RAM Failure External RAM Failure External ROM Failure EPROM Failure Neutral to Ground Overvoltage Alarm Event Trigger 1 Lock Active Event Trigger 2 Lock Active Event Trigger 3 Lock Active Event Trigger 4 Lock Active Event Trigger 5 Lock Active Event Trigger 6 Lock Active Event Trigger 7 Lock Active Excessive Floating Voltage Warning Synch Internal Overflow Warning Reverse Phase Sequence Relay code code code kWh MWh Product ID Communications Software Version Engineering Unit for ADF04-31 (3-Kilo, 6-Mega) Forward Energy (kWh) Forward Energy (MWh) Network Point Type Network Point Address Continued on next page . . . 28 0-no, 0-no, 0-no, 0-no, 0-open, 0-open, 0-open, 0-open, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, Metasys Integrator—Metasys Integrator Cutler-Hammer Application 1-yes 1-yes 1-yes 1-yes 1-closed 1-closed 1-closed 1-closed 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes NPT1 NPA2 (Cont.) Unit Description ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 GWh TWh kWh MWh GWh TWh kWh MWh GWh TWh kVARh MVARh GVARh TVARh kVARh MVARh GVARh TVARh kVARh MVARh GVARh TVARh kVAh MVAh GVAh TVAh Forward Energy (GWh) Forward Energy (TWh) Reverse Energy (kWh) Reverse Energy (MWh) Reverse Energy (GWh) Reverse Energy (TWh) Net Energy (kWh) Net Energy (MWh) Net Energy (GWh) Net Energy (TWh) Forward VAR Hours (kVARh) Forward VAR Hours (MVARh) Forward VAR Hours (GVARh) Forward VAR Hours (TVARh) Reverse VAR Hours (kVARh) Reverse VAR Hours (MVARh) Reverse VAR Hours (GVARh) Reverse VAR Hours (TVARh) Net VAR Hours (kVARh) Net VAR Hours (MVARh) Net VAR Hours (GVARh) Net VAR Hours (TVARh) Volt-Ampere Hours (kVAh) Volt-Ampere Hours (MVAh) Volt-Ampere Hours (GVAh) Volt-Ampere Hours (TVAh) BO BO BO BO BO BO BO BO BO BO 1 2 3 4 5 6 7 8 9 10 BO BO BO 1 2 * 11 12 13 Reset Peak Demand-Watts* Reset Energy Kilowatt Hours* Reset Peak Demand-Currents* Reset Min/Max Currents* Reset Min/Max L-L Voltages* Reset Min/Max L-N Voltages* Reset Min/Max pf-Apparent* Reset Min/Max pf-Displacement* Reset Min/Max Power* Reset Min/Max Current % Total Harmonic Distortion* Reset Min/Max Voltage % Total Harmonic Distortion* Reset Min/Max per-ph Power* Acknowledge Triggered Events* 0-n/a, 0-n/a, 0-n/a, 0-n/a, 0-n/a, 0-n/a, 0-n/a, 0-n/a, 0-n/a, 1-reset 1-reset 1-reset 1-reset 1-reset 1-reset 1-reset 1-reset 1-reset 0-n/a, 1-reset 0-n/a, 1-reset 0-n/a, 1-reset 0-n/a, 1-ack Network Point Type Network Point Address Do not map these points to Companion BO points. If you map these points to Metasys system BO objects, disable the Auto Restore option in the BO object’s Definition and Focus window. Metasys Integrator—Metasys Integrator Cutler-Hammer Application 29 Table 14: Digitrip MV Digitrip MV To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Phase C Current point is AI3. NPT1 NPA2 Unit Description AI AI AI AI AI AI AI AI 1 2 3 4 5 6 7 8 Amps Amps Amps Amps Amps Amps Amps Amps Phase A Current Phase B Current Phase C Current Ground Current Peak Phase Current IA Peak Phase Current IB Peak Phase Current IC Peak Phase Current Ground BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Tripped Alarmed Long Delay Trip Short Delay Trip Instantaneous Trip Discriminator Trip Ground Fault Breaker Trip Phase Long Delay Interlock IN Ground Long Delay Interlock IN Override Trip External Trip (via INCOM) High Load Alarm Long Delay Protection in Progress Ground Test Initiated Phase Test Initiated Ground Long Delay Has Picked Up Phase Short Delay Has Picked Up Ground Short Delay Has Picked Up Trip Unit Is In Program Mode Trip Unit Is In Test Mode RAM Error EEROM Error Test Initiated Test Timer Started 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes BO BO BO BO 1 2 3 4 Circuit Breaker* Reset Alarm* Reset Trip* Reset (Peak) Demand Currents* 0-open, 0-n/a, 0-n/a, 0-n/a, 1-closed 1-reset 1-reset 1-reset ADF ADF 1 2 1 2 * 30 Code Code Product ID Communications Software Version Network Point Type Network Point Address Do not map these points to Companion BO points. If you map these points to Metasys system BO objects, disable the Auto Restore option in the BO object’s Definition and Focus window. Metasys Integrator—Metasys Integrator Cutler-Hammer Application Digitrip RMS 810 To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Phase C Current point is AI3. Table 15: Digitrip RMS 810 NPT1 NPA2 Unit Amps Amps Amps Amps kW kW kWh Description Phase A Current Phase B Current Phase C Current Ground Current Power Power Demand Energy Power Factor Total Energy AI AI AI AI AI AI AI AI AI 1 2 3 4 5 6 7 8 9 BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Tripped Alarmed (Long Delay Pickup) Tripped or Opened via INCOM Trip Bar in Trip Position Long Delay Trip Short Delay Trip Instantaneous Trip Discriminator Trip OverrideTrip Over Temperature Trip Plug Trip Breaker Trip Request-DTA Energized Open as a Result of INCOM Shed Cmd Ground Fault High Load Alarm Negative Power Reading Long Delay Protection in Progress Unit Under a Test Condition Test Started Phase Test Initiated Ground Test Initiated EEROM Error BD 1 Hertz Flag BO BO BO BO 1 2 3 4 Circuit Breaker3 Reset Trip* Reset Energy* Reset Peak Demand* ADF ADF 1 2 1 2 3 * kWh Code Code 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 0-open, 0-n/a, 0-n/a, 0-n/a, 1-closed 1-reset 1-reset 1-reset Product ID Communications Software Version Network Point Type Network Point Address The circuit breaker can only be closed after resetting the trip. This command is not supported on the R-frame breaker. Do not map these points to Companion BO points. If you map these points to Metasys system BO objects, disable the Auto Restore option in the BO object’s Definition and Focus window. Metasys Integrator—Metasys Integrator Cutler-Hammer Application 31 Digitrip 3000 To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Phase C Current point is AI3. Table 16: Digitrip 3000 NPT1 NPA2 Unit Description Phase A Current Phase B Current Phase C Current Ground Current Phase A Peak Demand Current Phase B Peak Demand Current Phase C Peak Demand Current Ground Peak Demand Current 1 2 3 4 5 6 7 8 BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Tripped Alarmed (Long Delay Pickup) Tripped or Opened via INCOM Long Delay Trip Short Delay Trip Instantaneous Trip Discriminator Trip OverrideTrip External Trip via INCOM Ground Fault High Load Alarm Long Delay Protection in Progress Unit Under a Test Condition Test Started Phase Test Initiated Ground Test Initiated EEROM Error 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 0-no, 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes 1-yes BO BO BO BO 1 2 3 4 Circuit Breaker3 Reset Trip* Reset Alarm* Reset Peak Demand* 0-open, 0-n/a, 0-n/a, 0-n/a, 1-closed 1-reset 1-reset 1-reset ADF ADF 1 2 1 2 3 * 32 Amps Amps Amps Amps Amps Amps Amps Amps AI AI AI AI AI AI AI AI Code Code Product ID Communications Software Version Network Point Type Network Point Address The circuit breaker can only be closed after resetting the trip. This command is not supported on the R-frame breaker. Do not map these points to Companion BO points. If you map these points to Metasys system BO objects, disable the Auto Restore option in the BO object’s Definition and Focus window. Metasys Integrator—Metasys Integrator Cutler-Hammer Application Metasys Network Setup Metasys Network Setup is described in the Metasys Integrator unit technical bulletins. This section contains details specific to Cutler-Hammer applications. Mapping to a CS Object Table 17: Software Model and CS Object Definition Application Software Model (on Tables and Models CD-ROM) Display Attribute NT Command Attribute (recommended) (recommended) AI1 Phase A Current BI3 Starter Trip Status Advantage IQ_ADVA.DDL Advantage Control Module (ACM) IQ_ACM3X.DDL IQ 1000 II IQ_1000.DDL IQ Energy Sentinel IQ.ENER.DDL IQ Generator IQ.GENE.DDL IQ Data Plus II IQ_DATA.DDL IQ Data Plus 4000 IQ_DP4K.DDL BO1 Reset Demand IQ Analyzer IQ_ANALY.DDL BO13 Acknowledge Triggered Events Digitrip 810 IQ_DT810.DDL BI1 Tripped* Digitrip 3000 IQ_DT3K.DDL BO4 Reset Peak Demand Digitrip MV IQ_DTMV.DDL IQ Generator or Data IQ_GENE.DDL Digitrip II (for AEM subnetwork) IQ_AEMDI.DDL BI1 Long Delay Trip* IQ Data Plus II (for AEM subnetwork) IQ_AEMDP.DDL BI2 Alarm Flag* Assemblies Electronic Monitor II/CMU IQ_AEM.DDL * BI3 Starter Tripped AI1 Instantaneous Power BI2 Ready* BI2 Active* AI10 Frequency* BI1 Trip Flag* BI1 Inactive BI4 Alarm* Since none of the points are commandable, you cannot command the attribute from the NT. (This must be defined because the NT Command attribute cannot be null.) Metasys Integrator—Metasys Integrator Cutler-Hammer Application 33 Custom Integration For information on integrating products that are not discussed in this document, first refer to the Metasys Compatible Products online list of released connectivity products. If this list does not provide the information you require, consider using the Systems Integration Services (SIS) Request Custom Engineered Solutions process to request a custom contract from System Integration Team. Access both the Metasys Compatible Products and the Request Custom Engineered Solutions process from The Advisor by performing the following steps: 1. Click on the Products Focus link, located at the top of The Advisor home page. 2. Under Products, click on the Systems Integration Services link. 3. For the searchable database, click on Metasys Compatible Products. 4. Select Metasys Compatible Products Database. 5. Click Online Search Tool. 6. After the search in completed, return to the Systems Integration Services home page as instructed in Steps 1-2. 7. Select Custom Engineered Solutions to view the process used for requesting all types of SIS engineered solutions and services. 8. Select Requesting an Engineered Solution or Service. 9. Click Online Request Page. If you need further assistance, contact the Johnson Controls Field Support Center. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 34 Metasys Integrator—Metasys Integrator Cutler-Hammer Application www.johnsoncontrols.com Published in U.S.A.