Document Number: ECP 11-0310 Date: 12/12/2016 HIGH IMPEDANCE DIFFERENTIAL BUSBAR PROTECTION TEST FORM Substation Name Substation Number Circuit General Data Manufacturer CT Ratios V dc Trip Supply Wiring Insulation resistance (see test form ECP 11-0301) Inter relay and cubicle wiring checked to: Circuit diagram number ………………………………………. () Wiring diagram number ……………………………………….. () Measure and record lead resistances, using where necessary a leadresistance diagram (see test form ECP 11-0304) Isolator auxiliary switches () () Check continuity of closed auxiliary switches either visually, or, if not possible, by electrical test methods () Check auxiliary switches are silver plated () Check that two auxiliary switches in parallel are provided for all auxiliary switches in CT and relay paralleling circuits, except where the auxiliary switches have been specifically approved for the purpose, in which case one only need be used* () * The correct setting of auxiliary switches is checked in ECP 11-0303 or ECP 11-0304 as appropriate. Mechanical Inspection Mechanical inspection of the all ac and dc relays is to be recorded on the secondary injection test sheet, or test form ECP 11-0305, as appropriate () DC Relays All dc tripping, auxiliary and timing relays checked as part of the composite scheme in accordance with test form ECP 11-0305 and the results obtained are to be recorded therein () THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Version: 3.0 High Impedance Differential Busbar Protection Test Form Document Number: ECP 11-0310 Version: 3.0 Date: 12/12/2016 Secondary Injection Test – Supervision Timing Relay Note, the operating time at the setting voltage, of certain supervision timing relays, may be considerably in excess of the declared minimum time Operating Time Reset Setting Measured Secondary Injection Test – Check and Discriminating Relays and Supervision Relays Using single phase injection, measure and record at the recommended setting the minimum voltage at which all Check and Discriminating relays and Supervision relays operate. Injection to be made across relay and associated stabilising or setting resistors as appropriate. Enter results on the secondary injection test sheet. Record reset by tick only © UK Power Networks 2017 All rights reserved 2 of 7 High Impedance Differential Busbar Protection Test Form Document Number: ECP 11-0310 Version: 3.0 Date: 12/12/2016 Secondary Injection Test – Fault Setting Test This test need only be carried out if it is impracticable to ascertain the fault setting by primary injection. Minimum operating current at recommended setting. Injection to be made across the appropriate relay buswires. All check and discriminating relays are to be checked. Enter results on the secondary injection test sheet Actual Voltage Fault Setting Setting Zone or Recomcircuit Current to produce Serial Relay Mech mended and Phase relay operation No. Type Check Voltage Relay Setting Operate Reset Function Equivalent Secondary Primary (A) (A) Primary circuits connected during test R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B © UK Power Networks 2017 All rights reserved 3 of 7 High Impedance Differential Busbar Protection Test Form Document Number: ECP 11-0310 Version: 3.0 Date: 12/12/2016 Primary Injection Tests The details and results of all primary injection tests are to be recorded on test form ECP 11-0303 Local Primary Injection Tests Ratio and polarity of Discriminating CTs as a group () Ratio and polarity of Check CTs as a group () Overall Primary Injection Tests Balance tests to prove correct interconnections between CT groups () The busbar protection comparison test form is to be used for these tests. Note that when the secondary currents associated with Local primary injections for different primary circuits are measured at a common point, and the integrity of the associated main and reserve busbar isolator auxiliary switches and secondary wiring is therefore proved, it will normally only be necessary to compare the CTs of one phase, to prove the correct polarity of the CT group under test with respect to the reference CTs. In all other cases comparison tests are to be carried out on all three phases () Primary Injection – Fault Setting Test If it is impracticable to carry out this test, the fault setting is to be ascertained by secondary injection. Measure and record the earth-fault setting for each Check and Discriminating relay in each zone or circuit (as applicable). Measure and record also the setting of the supervision relays Fault Setting Circuit or Zone Relay Primary Current (A) R Y B © UK Power Networks 2017 All rights reserved Buswire Voltage (V) R Y Primary Circuits connected during Test B 4 of 7 High Impedance Differential Busbar Protection Test Form Document Number: ECP 11-0310 Version: 3.0 Date: 12/12/2016 Primary Injection – Main Bar With the circuits selected to Main Bar measure and record CT currents and relay currents, setting resistor currents, or buswire voltages Remarks B Discrim R… Y R Setting Resistor Currents / Relay Currents / Buswire Voltage B Discrim M… Y R B Check Y R N Discrim Y R ………. Circuit N Check CT Secondary Current (measured at test links) B B Y R N Discrim B Y R ………. Circuit N Check B Y R Phase Injected R-R Reverse Y-Y Reverse B-B Reverse Primary Current (Amps) © UK Power Networks 2017 All rights reserved 5 of 7 High Impedance Differential Busbar Protection Test Form Document Number: ECP 11-0310 Version: 3.0 Date: 12/12/2016 Primary Injection – Reserve Bar With the circuits selected to Reserve Bar Measure and record CT currents and relay currents, setting resistor currents, or buswire voltage Remarks B Discrim R… Y R Setting Resistor Currents / Relay Currents / Buswire Voltage B Discrim M… Y R B Check Y R N Discrim Y R ………. Circuit N Check CT Secondary Current (measured at test links) B B Y R N Discrim B Y R ………. Circuit N Check B Y R Phase Injected R-R Reverse Y-Y Reverse B-B Reverse Primary Current (Amps) © UK Power Networks 2017 All rights reserved 6 of 7 High Impedance Differential Busbar Protection Test Form Document Number: ECP 11-0310 Version: 3.0 Date: 12/12/2016 Comments Test Equipment Purpose Make/Type Serial Number Certification () All tests have been completed satisfactorily Contractor Commissioning Engineer (if applicable) Organisation Name Date Signature UK Power Networks Commissioning Engineer Name © UK Power Networks 2017 All rights reserved Signature Date 7 of 7