* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download There are occasions where changes may need to be
Opto-isolator wikipedia , lookup
Electrical grid wikipedia , lookup
Ground (electricity) wikipedia , lookup
Electrical substation wikipedia , lookup
Surge protector wikipedia , lookup
Fault tolerance wikipedia , lookup
Residual-current device wikipedia , lookup
Electrical wiring in the United Kingdom wikipedia , lookup
In-Service Protection Setting changes and testing – Settings Classification WG B5-01 1 by Pelqim Spahiu, National Grid UK (document 2) Reasons for In-Service Protection Setting changes and testing There are occasions where changes may need to be made to in service relay settings for the following reasons: i) ii) iii) iv) v) vi) When the numeric busbar protection is taken out of service (Central Unit Failure for example). In such a case settings on protection (distance and backup) protecting the circuits connected to the unprotected busbars are changed to provide acceptable protection for busbars while the busbar protection system is out of service. At the request of the supplier to update the settings on the equipment. This could, for example, happen on Current Differential Protection setting following the changes to the telecommunication system characteristics. In such a case non-GPS current differential protection will have to be desensitized to allow for the time difference between ‘’go’’ and ‘’return’’ path signal delay. Following a new, 132 kV and below, connection. In such a case, if the settings of Overcurrent and Earth fault protections on the new connected circuit are higher than the rest of the outgoing circuits then NG backup protection settings will have to changed. NG backup protection settings that will change are those on Supergrid/132 kV and lower voltage levels: TM on the 2-Stage HV 3-phase Overcurrent protection and TM on the LV Earth Fault (and LV Overcurrent, where applied). Following a new generation connection into the Transmission System busbars. Overcurrent settings for example should be changed to cater for new load/fault levels. Following an incident investigation if a relay setting is found to be the cause of an incident. Busbar Protection Central Unit will require setting/configuration change following the introduction of a new circuit (New Bay Unit). In relation to the tests performed to verify/confirm the changes it very much depends whether the relay is electromechanical, electronic or numeric and in what category the setting that has changed belongs to (see 2 below). In general, in case of an electromechanical relay setting changes (for example reach setting change on a distance protection) secondary injection is performed. The injection is done with the trip links removed so that the trip relay that operates the Circuit Breaker is not energized. In case of Numeric relay more attention is focused on checking the readings and alarms (for example ‘’C Diff’’ level reading on the Unit Protection or I1,I2 and I0 readings to see whether their values are as expected knowing IA, IB and IC load that the relay is ‘’seeing’’). It has to be noted that National Grid UK tends to ask Supplier to do comprehensive tests in the Factory before the relay is shipped to site. All of those tests are performed with the actual specific circuit settings loaded into the relay. 2 Settings classification – categories Settings within National Grid UK protection systems are normally categorized as below: Page 1 of 2 04th January 2007 1 Relay Function Selection (eg. O/C, E/F, Distance, DAR etc) 2 Power System Measurement (i.e. V, I, Z, f, t) 3 Selectable Logic Sequence (i.e. DAR link) 4 Communication Selection (i.e. baud rate) 5 Output/Input configuration 6 Fixed Logic Sequence (e.g. DAR sequence which is fixed at the time of Type Registration) Power System Settings Fixed Settings Settings within categories 5 and 6 are normally changed in the Manufacturers Factory and the relay is retested there before shipping it to site (again only readings are taken and recorded on site). Page 2 of 2 04th January 2007