Download Generator Loading, Harmonics Monitoring and

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Electric machine wikipedia , lookup

Audio power wikipedia , lookup

Electromagnetic compatibility wikipedia , lookup

Utility frequency wikipedia , lookup

Ground (electricity) wikipedia , lookup

Stepper motor wikipedia , lookup

War of the currents wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Electric power system wikipedia , lookup

Electrical ballast wikipedia , lookup

Ohm's law wikipedia , lookup

Power factor wikipedia , lookup

Rectifier wikipedia , lookup

Transformer wikipedia , lookup

Electrical substation wikipedia , lookup

Voltage regulator wikipedia , lookup

Surge protector wikipedia , lookup

Single-wire earth return wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Electrification wikipedia , lookup

Power MOSFET wikipedia , lookup

Tube sound wikipedia , lookup

Power engineering wikipedia , lookup

Current source wikipedia , lookup

Power inverter wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Islanding wikipedia , lookup

Stray voltage wikipedia , lookup

Opto-isolator wikipedia , lookup

Transformer types wikipedia , lookup

History of electric power transmission wikipedia , lookup

Buck converter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Power electronics wikipedia , lookup

Voltage optimisation wikipedia , lookup

Mains electricity wikipedia , lookup

Three-phase electric power wikipedia , lookup

Alternating current wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Transcript
Generator Loading, Harmonics Monitoring and Mitigating Analysis in
a Water Treatment Plant
Eddie Jones, PE; Larry Ray, PE; Tim Shuter, PE; Square D Engineering Services
Abstract
Water treatment plants are often equipped with variable-frequency drives, ozone generators, and other loads that
produce harmonic distortion. These facilities are also equipped, in many cases, with emergency standby generators
required to operate critical electrical loads during extended electric utility outages. One such facility, a reverseosmosis desalination plant located on the United States coast, was concerned about the ability of its 938-kVA
standby generator to operate reliably in the presence of harmonic distortion injected by large VFD’s serving pump
motors. Subsequent harmonic measurements compared distortion levels on both utility and generator sources, and
engineering analysis offered harmonic mitigating techniques indicated by the measured harmonic levels.
Electric System
Onsite Genset
760 kW synch
938 kVA
Standby rated
Utility source
2000 kVA
6% Z
Open transition
transfer switch
R1, R2: Line reactors, 3%
Z at 60 hp
Circuit Monitor
VFD1-3: 250-hp 6-pulse
PWM
2000 A 3-section QED Switchboard
T1
T2
T3
Key:
T1-3: 270 kVA dry-type
isolation transformers;
460/460-V, 5.3% Z at 170 C
R1
R2
VFDTP1, VFDTP2: 60-hp,
6-pulse PWM
MF1-3: Drive output
(motor) filters
VFD1
VFD2
VFD3
MF1
MF2
MF3
HPP1
HPP2
HPP3
VFDTP1
VFDTP2
HPP1-3: 250-hp vertical
suction water pumps
TP1, TP2: 60-hp pumps
TP1
TP2
Summary of Results
™ Load measurements indicated that the onsite standby generator was loaded to about 53% of its rated capacity
under the load conditions that existed at the time. Load levels peaked at 403 kW and 431 kVA during the test.
™ Key power system parameters, including voltage regulation and unbalance, and current unbalance, were within
acceptable limits during the test on both electric utility and generator sources.
™ Harmonic distortion levels measured during the test did not cause noticeable operating problems for any of the
plant equipment.
™ Harmonic voltage distortion at the 480-V bus peaked at about 6.3% at highest load on the electric utility, and
about 10.5% at highest load on the generator.
Square D Engineering Services
1
Recommendations
™ While harmonic distortion levels did not cause noticeable operating problems for the facility loads, harmonic
reduction techniques should be considered in order to maximize equipment life and system reliability. IEEE
Standard 519-1992 harmonic limits are being exceeded when operating on the standby generator.
™ Bypassing one of the existing isolation transformers serving a 250-hp drive may achieve some beneficial
effects due to increased harmonic cancellation of 5th and 7th current components, but this measure should be
considered temporary.
™ The better solution is to replace one delta/wye isolation transformer with a delta/zig-zag transformer to improve
cancellation while maintaining attenuation effects.
™ The best solution is to install an active harmonic filter at the service entrance.
™ Onsite power monitoring should be installed to track performance of desalination facility in harmonic
distortion, voltage quality, disturbances, and costs.
Monitoring Results
Summary
Testing was performed at the line (source) side of the Square D QED switchboard serving the desalination facility.
Testing was performed with a PowerLogic CM4000T Portable Circuit Monitor, capable of measuring over 200
power system parameters. Harmonic distortion measurements were taken at a sampling rate of 512 points per cycle,
to provide accuracy to the 250th harmonic.
Average Current During Load Test
700
Average 3 Phase RMS Current
Three 250 hp,
two 60 hp
600
Three 250 hp, one 60 hp
500
Three 250 hp VFD
Three 250 hp, two 60 hp
Three 250 hp,
one 60 hp
Three 250 hp VFD
Two 250 hp VFD
400
Two 250 hp VFD
One 250 hp VFD
300
One 250 hp VFD
200
Lighting and HVAC
100
Utility Source
Generator Source
Lighting Only;
Transfer to Generator
0
13:30
14:00
14:30
15:00
15:30
Average RMS current during the test shows the effects of various machines operating. Current unbalance was
acceptable during the test, about 20% without the drives operating (lighting and HVAC only), and less than 5% with
drives operating.
Square D Engineering Services
2
RMS Voltage During Load Test
495
Three 250 hp, two 60 hp
Three 250 hp,
two 60 hp
VOLTAGE (PHASE TO PHASE)
490
485
Lighting and HVAC
Lighting Only;
Transfer to Generator
480
Utility Source
475
470
13:30
Generator Source
14:00
14:30
15:00
15:30
Voltage levels were slightly lower on the generator source, but both utility and generator sources were able to
maintain acceptable steady state voltage (100% to 103% of 480 V) for the entire duration of the testing. Voltage
unbalance was likewise within acceptable limits, less than 1%.
Real and Total Power Demand During Load Test
500
Three 250 hp, two 60 hp
450
Real (kW) & Total (kVA) Demand
Three 250 hp, two 60 hp
400
Total Power, kVA
350
300
250
Lighting and HVAC
200
Real Power, kW
150
100
Utility Source
50
0
13:30
Generator Source
Lighting Only;
Transfer to Generator
14:00
14:30
15:00
15:30
Real and total power demand trends on one-minute intervals during the test. Note that the 938-kVA-rated generator
is about 50% loaded during peak operation.
Square D Engineering Services
3
Power Factor During Load Test
1
0.9
Three 250 hp,
two 60 hp
Three 250 hp, two 60 hp
0.8
Lighting and HVAC
Power Factor (Lagging)
0.7
0.6
Lighting Only;
Transfer to Generator
0.5
0.4
Utility Source
Generator Source
0.3
0.2
0.1
0
13:30
14:00
14:30
15:00
15:30
Power factor during the load test. Note that power factor is lowest during times of lightest load and is high when all
drives are operating. This makes it difficult to utilize conventional harmonic filters to reduce harmonics on this
circuit due to their inherent power factor improvement characteristics.
Harmonic Distortion During Load Test
20
Voltage THD or Current TDD, %
18
Three 250 hp, one 60 hp
16
14
Three 250 hp, two 60 hp
Three 250 hp,
one 60 hp
Three 250 hp,
two 60 hp
Three 250 hp VFD
Three 250 hp VFD
12
10
Current Distortion
8
6
Lighting Only;
Transfer to Generator
Lighting
and HVAC
4
Voltage Distortion
2
Utility Source
0
13:30
14:00
Generator Source
14:30
15:00
15:30
Harmonic distortion levels during testing. Voltage distortion peaked at about 6.5% on the utility source and about
10% on the generator source. Note that current distortion drops when 60 hp drives are operated with 250 hp
drives. This is due to the cancellation effects of the combination of delta-wye transformers and line reactors.
Current Total Demand Distortion (TDD) is based on IL of 900 A, or 80% of the generator rating of 1129 A.
Square D Engineering Services
4
Harmonic Analysis
Summary
Square D performed harmonic simulations to estimate the reduction in harmonic current that could be achieved by
the following modifications. Note that the “Existing Harmonic Cancellation” section shows that some harmonic
cancellation is already being achieved when 250-hp and 60-hp drives are operated at the same time. The other
techniques that were considered include:
♦
Bypass one existing delta-wye isolation transformer serving a 250-hp drive to increase cancellation of 5th and 7th
harmonics (short-term measure);
♦
Replace one existing delta-wye isolation transformer serving a 250-hp drive with a delta/zig-zag-wound
transformer to increase cancellation of 5th and 7th currents, and to maintain the beneficial effects of harmonic
attenuation;
♦
Install a passive harmonic filter at the 480-V main to remove harmonics injected by the drives.
♦
Install an active harmonic filter at the 480-V main.
Existing Harmonic Cancellation
Harmonic Current Shows Effects of Cancellation
600
500
Despite increase in total rms current when all
drives are operating...
Amperes, RMS
400
...5th and 7th harmonic currents show effects of
cancellation from mix of delta-wye transformers
(250 hp drives) and line reactors (60 hp drives)
300
Base Case
Worst Case
All Drives
200
100
0
Total
5th
7th
11th
13th
Harmonic
Note that existing system of delta-wye transformers and line reactors serving the facility’s drives benefits from some
cancellation of 5th and 7th harmonic currents. The system required about 27% and 16% less current at 5th and 7th
harmonics, respectively, despite a 19% increase in total rms current. “Worst Case” occurs when only the 250-hp
drives are operating.
Square D Engineering Services
5
Harmonic Reduction/Mitigation Analysis
Replace One Isolation Transformer
Bypassing one of the existing three isolation transformers serving a 250-hp drive seems to have a beneficial effect
on the amount of harmonic current distortion at the facility. As shown in the following summary, cancellation
effects can be improved to further reduce 5th and 7th harmonic currents by bypassing one transformer and allowing
its 5th and 7th harmonic currents to be unchanged. Once these currents are added to the other one or two 250-hp
drive currents, additional cancellation occurs. This technique, however, should be considered only for temporary
improvement until more effective means are installed.
Harmonic:
<11
11-17
17-23
Measured
Worst Case
All Drives
10.6%
7.9%
3.4%
3.4%
1.5%
1.5%
Simulated
w/o isol xfmr
6.5%
2.0%
1.1%
Current Total Demand Distortion, ITDD, based on IL=900 A (80% of generator rating of 1129 A)
A better technique is to replace one isolation transformer – instead of bypassing it – with a harmonic mitigating
transformer of similar impedance. This modification would provide both cancellation effects (harmonic currents are
not phase-shifted through delta/zig-zag-wound transformers) and attenuation effects. At this point, however, the
simple computer model breaks down, perhaps due to a resonance between the drive capacitance and the line reactor
that may or may not be real. The model predicts a further reduction in 5th and 11th currents to about 5.8%, but shows
an increase in 11th and 13th currents over the “w/o isol xfmr” case that cannot be fully explained.
Other Techniques
Two other options were considered.
The first option that was considered but is not recommended is the addition of a 5th harmonic filter at the 480-V
main. This option is not practical because passive harmonic filters of this type also increase fundamental power
factor. Since power factor at the facility is already high (94%) at full load, the system cannot tolerate much parasitic
capacitance without putting the facility into a leading power factor.
The best option that should be considered if further harmonic current reduction is desired is an active filter. Active
filters measure the amount of harmonic current required by the load and inject current 180° out of phase with that
current. This technique reduces the harmonic distortion levels considerably and is often used where stringent
harmonic limits are applied.
How Much Harmonic Distortion Is Too Much?
IEEE Guidelines
Drives and other facility loads operated without disruption during the May 7 testing, so why consider harmonic
reduction? Since the adverse effects of harmonics may be manifested over an extended time period, it is difficult to
determine the economic attractiveness of reducing harmonic distortion. The Institute of Electrical and Electronics
Engineers developed the Recommended Practices and Requirements for Harmonic Control in Electric Power
Systems, IEEE Standard 519-1992, to offer guidelines on this question. While this standard was developed primarily
as a recommended practice for electric utilities and their customers, not as an equipment or facility standard, it can
be used to develop some guidelines.
Square D Engineering Services
6
Harmonic:
IEEE "Limit"
<11
4.0%
11-17
2.0%
17-23
1.5%
3.4%
3.4%
1.5%
1.5%
Measured
Worst Case
All Drives
11%
7.9%
Simulated
6.5%
2.0%
1.1%
w/o isol xfmr
IEEE 519-1992 is often used as a guide for assessing existing harmonic current levels inside a facility even though
that is not its primary purpose. This table shows the harmonic limits from Table 10-3 of the Standard typically
imposed on power generation equipment. Note that these limits were exceeded during the onsite measurements. As
before, “Measured” and “Simulated” ITDD figures on based on 80% of the generator full-load amperage.
Square D Engineering Services
7
Voltage and Current Waveforms
Baseline – No Drives Operating
Utility Source
Phase A-N Voltage
Phase A Current
512 Points / Cycle
400
300
200
100
0
-100
-200
-300
-400
Current
Voltage
512 Points / Cycle
0.0
2.5
5.0
7.5
10.0
Milliseconds
12.5
200
150
100
50
0
-50
-100
-150
15.0
0.0
2.5
5.0
7.5
10.0
Milliseconds
12.5
15.0
12.5
15.0
12.5
15.0
12.5
15.0
Generator Source
Phase A-N Voltage
Phase A Current
511 Points / Cycle
400
300
200
100
0
-100
-200
-300
-400
150
100
50
Current
Voltage
511 Points / Cycle
0
-50
-100
-150
0.0
2.5
5.0
7.5
10.0
Milliseconds
12.5
15.0
0.0
2.5
5.0
7.5
10.0
Milliseconds
Worst Case – Three 250-hp Drives Operating at 83% of Rated Load
Utility Source
Phase A-N Voltage
Phase A Current
512 Points / Cycle
400
300
200
100
0
-100
-200
-300
-400
750
500
250
Current
Voltage
512 Points / Cycle
0
-250
-500
-750
0.0
2.5
5.0
7.5
10.0
Milliseconds
12.5
15.0
0.0
2.5
5.0
7.5
10.0
Milliseconds
Generator Source
Phase A-N Voltage
Phase A Current
511 Points / Cycle
400
300
200
100
0
-100
-200
-300
-400
750
500
250
Current
Voltage
511 Points / Cycle
-0
-250
-500
-750
0.0
2.5
5.0
7.5
10.0
Milliseconds
Square D Engineering Services
12.5
15.0
0.0
2.5
5.0
7.5
10.0
Milliseconds
8
All Drives Operating (Three 250 hp, Two 60 hp)
Utility Source
Phase A-N Voltage
Phase A Current
512 Points / Cycle
400
300
200
100
0
-100
-200
-300
-400
Current
Voltage
512 Points / Cycle
0.0
2.5
5.0
7.5
10.0
Milliseconds
12.5
750
500
250
0
-250
-500
-750
15.0
0.0
2.5
5.0
7.5
10.0
Milliseconds
12.5
15.0
12.5
15.0
Generator Source
Phase A-N Voltage
Phase A Current
511 Points / Cycle
400
300
200
100
0
-100
-200
-300
-400
Current
Voltage
511 Points / Cycle
0.0
2.5
5.0
7.5
10.0
Milliseconds
Square D Engineering Services
12.5
15.0
1000
750
500
250
0
-250
-500
-750
0.0
2.5
5.0
7.5
10.0
Milliseconds
9
Harmonic Distortion Fundamentals
Introduction
Electronic or “non-linear” loads, such as variable frequency and dc motor drives, computers, and automation
equipment, draw current from the power system that is not sinusoidal. The resulting non-linear current may be
expressed as a series of sinusoidal waves with frequencies equal to integer multiples of the 60 Hz system frequency.
The individual high-frequency waves are referred to as harmonics—the 3rd harmonic is equal to 3 times the system
frequency (i.e., 180 Hz), the 5th harmonic has a frequency of 5 x 60 Hz = 300 Hz, etc. Harmonic currents are
undesirable because they are an additional source of thermal stress on various types of electric equipment, reducing
the current-carrying capability of conductors and transformers. Harmonic currents also interact with line
impedance, causing the system voltage to become distorted. When equipment such as capacitors or motors are
served with a distorted system voltage, significant harmonic currents may flow, effectively reducing the lifetime of
such equipment.
When power factor correction capacitors are installed in a facility that contains harmonic-producing loads, the plant
electrical system should be evaluated to ensure that no resonant conditions are created that could cause excessive
harmonic voltage or current levels within the facility. Parallel resonance occurs when the installed capacitance
interacts with the existing power system to create a high impedance at some resonant frequency greater than the 60
Hz system frequency. As a result, harmonic currents near the resonant frequency are amplified, in turn producing
harmonic voltage levels higher than would normally be expected.
Cancellation Effects
Harmonic cancellation is an effective means of reducing harmonic distortion, especially among three-phase drives.
Cancellation works best when pairs of drives of similar size are operating at similar loading on the same bus.
Cancellation is achieved by serving one of the drives from a delta-wye transformer, and the other by a delta-delta
transformer or simple line reactor. Some cancellation can also be achieved by using a combination of delta-wye
transformer and no inductive device, as has been modeled for Dare County.
Cancellation is achieved because 5th and 7th harmonic frequency current components are phase-shifted by 30° in a
delta-wye transformer. When these phase-shifted currents are combined with the unchanged currents passing
through line reactors or delta-delta transformers, significant cancellation can occur.
480 Volt Bus
ASD
ASD
Harmonic cancellation can be achieved on similar size adjustable-speed drives (ASD) operating at similar load
levels. Source: IEEE Standard 519a, Draft Application Guide.
Attenuation Effects
Harmonic distortion can be reduced by adding impedance, usually in the form of an isolation transformer or line
reactor, between the harmonic load and its source. Inductive impedance serves to limit the amount of higher
Square D Engineering Services
10
frequency currents that the harmonic load can inject into the system. Of course, there is a limit to the amount of
impedance that can be inserted into the system without affecting performance and operation of the harmonic load.
Input Current Distortion as a Function of Choke Inductor Size
80.0%
Input Current Distortion (%)
70.0%
60.0%
50.0%
40.0%
30.0%
20.0%
10.0%
0.0%
0%
1%
2%
3%
4%
5%
Choke Inductor (% on Drive Base)
Reduction in harmonic currents can also be achieved by attenuation. This chart shows the typical drop in current
distortion for line reactors (inductors) of various impedances.
Harmonic Mitigating Transformers
Harmonic Mitigating Transformers, or HMT’s, use phase shifting, electromagnetic flux, and source impedance to
help reduce the effects of harmonics in electrical distribution systems. These devices provide the beneficial effects
of harmonic cancellation and harmonic attenuation, as described above, in order to improve reliability of power
systems serving variable-frequency drives. These transformers can be supplied with either delta/wye windings that
provide 30° phase shift for 5th and 7th harmonics, or delta/zig-zag windings that do not provide phase shifting.
System Modeling
A computer simulation of the power system was performed using the SKM Hi_Wave computer program. The
model of the system, complied from data collected by the Power Logic monitoring along with information gained
from inspection of equipment at the site, depicts the major loads and sources. Information about the utility system
was derived based on load measurements taken during the onsite visit.
Square D Engineering Services
11