Download 63-1337—02 - Class 200 Meters Three-Phase Meters

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Sound level meter wikipedia , lookup

Geophysical MASINT wikipedia , lookup

Power inverter wikipedia , lookup

Peak programme meter wikipedia , lookup

History of electric power transmission wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power engineering wikipedia , lookup

Smart meter wikipedia , lookup

Stray voltage wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Voltage optimisation wikipedia , lookup

Ohm's law wikipedia , lookup

Rectifier wikipedia , lookup

Current source wikipedia , lookup

Three-phase electric power wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Mains electricity wikipedia , lookup

Power electronics wikipedia , lookup

Buck converter wikipedia , lookup

Multimeter wikipedia , lookup

Alternating current wikipedia , lookup

Current mirror wikipedia , lookup

Opto-isolator wikipedia , lookup

Transcript
Class 200 Meters
Three-Phase Meters
SPECIFICATION DATA
• Ideal for indoor and outdoor use.
• Monitors a single electrical circuit, piece of equipment,
department, tenant, or even the entire building.
• Easy and affordable installation virtually anywhere,
including both new and retrofitted facilities.
FEATURES
• 0-2 volt output split-core current sensors allow for
quick and safe installation without power interruption.
• Retain meter reading in the event of power failure.
• Meters can be placed up to 2,000 feet away from an
electric panel.
• Direct-read 8-digit LCD display without multiplier
displays cumulative kWh and "real-time" kW load.
• Demand option displays kW/Demand and kW Peak
date and time (15 minute interval standard, 30 minute
interval available).
• Current sensor installation diagnostic indicator.
• UL/CUL Listed with utility-grade accuracy.
• Parallel up to three (3) sets of current sensors for
cumulative reading.
OVERVIEW
The Honeywell Class 200 kWh meters are fully electronic,
low-cost meters for monitoring electrical usage in multifamily,commercial and industrial applications.
The pulse output on Honeywell branded meters is compatible
with and can be tied directly to the JACE I/O Module input
using the output at the orange screw terminal plug (TB5).
APPLICATIONS
Metering specific tenants, departments, cost centers or pieces
of equipment in your facility allows you to pinpoint when and
where energy is being used—right down to the specific date
and time. Armed with this data, you can take steps to curtail
this usage and thus reduce your overall energy consumption
costs.
• Meter can be used on the following configurations:
3-Phase, 4-Wire
3-Phase, 3-Wire
• Optional removable terminal block for pulse output.
• NEMA 4X Raintight Enclosure (Model numbers with an
“R” at the end)
• Non-volatile Memory.
• Certified to ANSI C12.1 and C12.16 electronic meter
National Accuracy Standards. (+/- 1% from 1%-100% of
the rated load.) Accuracy rating includes split-core
current sensors.
• California CTEP approved for use with solid-core
current sensors. Listed by the California Energy
Commission.
• New York City approved, Con Edison approved for
RSP program.
63-1337-02
CLASS 200 METERS THREE-PHASE METERS
SPECIFICATIONS
Dimensions:
7-1/4 in. H x 7 in. W x 3-1/4 in. D
Accuracy:
Certified to ANSI C12.1 & C12.16
7 (178)
3-1/4 (83)
Voltage Input Configuration:
(3 or 4 wire) 120/208-240V
(3 or 4 wire) 277/480V
(4 wire) 346/600V
Current Input:
Up to 3200 Amp RMS AC
7-1/2
(191)
Power Factor: .5 leading and lagging
Frequency: 50-60 HZ
Operating Temperature Range:
NEMA 4 (Outdoor) Housing: -4ºF to +158ºF (-20ºC to +70ºC)
NEMA 12 (Indoor) Housing: -4ºF to +122ºF (-20ºC to +50ºC)
Relative Humidity Range:
0-95% Non-Condensing
M29258
Fig. 1. Class 200 meter enclosure dimensions in in. (mm).
3-3/4 (95)
Voltage Overload:
+25% Continuously; +100% for 20 cycles
29/32
(23)
Pulse Output Type:
Optically coupled, normally open electronic switch.
1-19/64 (33)
1-3/8
(35) 2-3/4
(70)
Output:
Solid-state switch, N.O. equivalent.
Typical ON Resistance:
30 Ohms
M29268
Maximum OFF Leakage:
1 uA
Fig. 2. 100 and 200 Amp current sensor dimensions in in.
(mm).
Pulse Closure Time Cycle:
50%
3-3/4 (95)
1-19/64 (33)
External Interface Voltage:
1.5 to 36 volts DC or AC
Maximum Interface Current:
100 ma
1-3/8
(35)
1-1/2
(38)
4-1/4
(108)
Current Sensor Overload:
100% for 1 minute without damaging meter
29/32
(23)
Approvals:
UL/CUL Listed and CSA Approved
1-3/16
(30)
M29269
Fig. 3. 400 Amp current sensor dimensions in in. (mm).
63-1337—02
2
CLASS 200 METERS THREE-PHASE METERS
ORDERING INFORMATION
1-1/4
(32)
6-3/32 (155)
Table 1. Model Numbers.
Model #
2-3/8
(60)
4-19/64
(109)
5-3/4
(146)
M29270
Fig. 4. 800 and 1600 Amp current sensor dimensions in
in. (mm).
1-1/4
(32)
7-3/4 (197)
Amps
SUB208-100
100
SUB208-200
200
SUB208-400
400
SUB208-800
800
SUB208-1600
1600
SUB208-3200
3200
SUB480-100
100
SUB480-200
200
SUB480-400
400
SUB480-800
800
SUB480-1600
1600
SUB480-3200
3200
SUB600-100
100
SUB600-200
200
SUB600-400
400
SUB600-800
800
SUB600-1600
1600
SUB600-3200
3200
Description
120/208V, 3-Phase, 4W
240V, 3-Phase, 3W
(Supplied with one set of three (3)
split-core current sensors)
277/480V, 3-Phase, 4W
480V, 3-Phase, 3W
(Supplied with one set of three (3)
split-core current sensors)
346/600V, 3-Phase, 4W
(Supplied with one set of three (3)
split-core current sensors)
NOTE: Add an “R” at the end of the model number for NEMA
4X outdoor models.
NOTE: For Demand (kW) option add suffix “D” to the model
number (e.g. SUBD600-200).
9-3/32
(231)
5-3/8 (137)
7-7/8
(200)
M29271
Fig. 5. 3200 Amp current sensor dimensions in in. (mm).
3
63-1337—02
CLASS 200 METERS THREE-PHASE METERS
Table 2. Part Number Configuration Table.
Sub Meter
SUB
Demand option
Voltage
Current
Blank: No demand
208: 208 volts
100: 100 Amps
R: NEMA 4X
D: Demand
480: 480 Volts
200: 200 Amps
Blank: NEMA 12
600: 600 Volts
400: 400 Amps
—
Enclosure
800: 800 Amps
1600: 1600 Amps
3200: 3200 Amps
Example
SUB208-400R : Class 200, 208 Volts, 400A, NEMA 4X
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
By using this Honeywell literature, you agree that Honeywell will have no liability for any
damages arising out of your use or modification to, the literature. You will defend and
indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or
damages, including attorneys’ fees, arising out of, or resulting from, any modification to
the literature by you.
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2011 Honeywell International Inc.
63-1337—02 M.S. Rev. 02-11
Printed in U.S.A.