* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download Power System Transients - Chapter 1
Integrating ADC wikipedia , lookup
Regenerative circuit wikipedia , lookup
Spark-gap transmitter wikipedia , lookup
Immunity-aware programming wikipedia , lookup
Operational amplifier wikipedia , lookup
Schmitt trigger wikipedia , lookup
Index of electronics articles wikipedia , lookup
Radio transmitter design wikipedia , lookup
Josephson voltage standard wikipedia , lookup
Voltage regulator wikipedia , lookup
Valve RF amplifier wikipedia , lookup
Current source wikipedia , lookup
Resistive opto-isolator wikipedia , lookup
Current mirror wikipedia , lookup
Power MOSFET wikipedia , lookup
RLC circuit wikipedia , lookup
Power electronics wikipedia , lookup
Opto-isolator wikipedia , lookup
Switched-mode power supply wikipedia , lookup
1 Transient phenomena 1 Transient Phenomena in Electrical Power Systems 1.1 Introduction Power system networks are subjected to various forms of transient phenomena ranging from the relatively slow electromechanical oscillations associated with synchronous machines and drives to the comparatively fast variations in voltage and current brought about by sudden changes such as due to lightning strokes. Lightning is a common cause of faults and subsequent current outages, but faults can and do occur for many other reasons. Malfunctioning of the system can occur in numerous ways and has a variety of consequences, e.g. opening of one phase of a three-phase circuit can lead to a rearrangement of circuit inductances and capacitances in such a manner that a resonant circuit is produced and excited with large values of voltage and/or current as a consequence. Transient overvoltages are produced by both opening and closing of a circuit breaker and their computation and assessment is the particular concern of this course. Over the years, the voltages at which electrical power is transmitted over long distances have been increasing continually and many systems are now in operation at 400 kV, 500 kV, 750 kV and even 1000 kV. The lightning performance of transmission lines shows an improvement with increasing operating voltage level, because the magnitude of lightning surges on lines are not greatly affected by the line design. In contrast, system-generated overvoltages are directly related to the system voltage and their magnitudes increase as the system voltage increases. As a result, at operating voltages of 400 kV and above, system-generated overvoltages play an increasingly large part in determining the insulation level of the system. Although the system insulation level must be sufficiently high in order not to hazard the reliability of the system, at the same time there are strong economic incentives (minimizing costs) for keeping it as low as possible. This chapter intends to give a general introduction into transient phenomena, origin and consequences of transients in simple single- and three-phase circuits. Compared to steady-state behaviour of power systems at one frequency, where the system can be described by complex phasor equations easily, mathematical formulation of transient response of individual equipment and/or the system is rather complex, because in the transient state, the system response is involved in a wide frequency range. Therefore, it is important to understand basics of electrical transients and their physical interpretation. Power System Transients (Kizilcay) 1-1 1 Transient phenomena 1.2 Examples of Transients in Single-Phase Circuits 1.2.1 Introduction The transient response of any electric circuit can be explained in a simplified manner by the interaction of following basic electrical parameters: • Resistance, R • Inductance, L • Capacitance, C All components, whether in a power utility system or industrial circuit possess each of these parameters to a greater or lesser degree. The resistance, inductance and capacitance of a circuit are distributed quantities; that is, each small part of the circuit possesses its share. But it is frequently found that they can be treated as "lumped" parameters, concentrated in particular branches, without seriously impairing the accuracy of computations. There are other circumstances, where this technique is not suitable, as in dealing with long transmission lines, where a different approach will be used. The parameters L and C are characterized by their ability to store electrical energy, L in the magnetic field and C in the electric field of the circuit. These stored energies are functions of the instantaneous current i and voltage v and are, respectively, (1.1) In contrast, the parameter R is a dissipater of energy, the rate of dissipation being R@i 2 at any instant. Under steady-state conditions the energy stored in the various inductances and capacitances of a direct current (DC) circuit is constant, whereas in an alternating current (AC) circuit energy is being transferred cyclically between the L's and C's of the circuit as the current and voltage rise and fall sinusoidally at the frequency of the supply. When a sudden change occurs in a circuit, there is generally a redistribution of energy to meet the new conditions, and in a way, it is this what we are studying when we inquire 1-2 Power System Transients (Kizilcay) 1 Transient phenomena into the nature of transients. The transient behaviour of basic elements L and C are described by the following equations: ! Inductance (1.2) To change the magnetic energy requires a change of current. But change of current in an inductor causes an induced voltage L di/dt. An instantaneous change of current would therefore require an infinite voltage to bring it about. Since this is unrealizable in practice, currents in inductive circuit do not change abruptly and consequently there can be no abrupt change in the magnetic energy stored. In other words, the magnetic flux linkage of a circuit cannot change suddenly. ! Capacitance (1.3) To change the electric energy requires a change in voltage. For an instantaneous change of voltage an infinite current in a capacitor must flow. This is unrealizable, too. Consequently, the voltage across a capacitor cannot change abruptly nor can the energy stored in its associated electric field. The redistribution of energy following a change in the circuit state takes a finite time, and the process during this interval, as at any other time, is governed by the principle of energy conservation, that is, the rate of supply of energy is equal to the rate of storage of energy plus the rate of energy dissipation. A transient is initiated whenever there is a sudden change of circuit conditions; this is most frequently occurs when a switching operation takes place. The following examples studied have been concerned with switching transients. A prime concern is the emphasis on the physical aspects of what occurs in the circuit. The circuits given have been generated using graphical preprocessor ATPDraw for ATP-EMTP and the simulations have been performed using electromagnetic transients program ATP-EMTP. Power System Transients (Kizilcay) 1-3 1 Transient phenomena 1.2.2 Energization of an RL circuit The single-phase circuit involved in this example is built using ATPDraw and shown in Fig. 1.1. The load is represented by a series combination of R und L. The sinusoidal voltage source is defined by the following equation (1.4) Fig. 1.1 Energization of a 500-kV shunt reactor The source is assumed to have negligible internal impedance compared with the load. Consider a 500-kV system (50 Hz) solidly grounded, supplying a single-phase shunt reactor with power, S = 10 MVA. X/R ratio of the reactor is 50. The circuit parameters are obtained as follows: ; ; ; The peak value of steady-state current can be calculated as Im = 46.66 A. The current waveforms are shown in Fig. 1.2 for two cases: (a) switch closes at t = 4.936 ms corresponding to phase angle 2 = 88.85/; (b) switch closes at t = 9.936 ms corresponding to phase angle 2 = 178.85/. 1-4 Power System Transients (Kizilcay) 1 Transient phenomena 50 . 0 50 0 [A ] [k V ] 37 . 5 37 5 25 . 0 25 0 12 . 5 12 5 0. 0 0 -1 2. 5 -1 25 -2 5. 0 -2 50 -3 7. 5 -3 75 -5 0. 0 0. 00 -5 00 0. 02 0. 04 (f ile E N E R G R L 1. pl4 ; x -v a r t ) c : S R C -N 1 0. 06 0. 08 [s ] 0. 10 v :S R C Fig. 1.2 (a) Switch closes at t = 4.936 ms (Q: source voltage; ": current) 20 50 0 [k V ] [A ] 37 5 0 25 0 -2 0 12 5 -4 0 0 -1 25 -6 0 -2 50 -8 0 -3 75 -1 00 0. 00 -5 00 0. 02 (f ile e nergrl2. p l4; x -v ar t ) c : S R C 0. 04 -N 1 0. 06 0. 08 [s ] 0. 10 v :S R C Fig. 1.2 (b) Switch closes at t = 9.936 ms (Q: source voltage; ": current) In both cases the current attains a steady-state peak value of Im and it lags in phase the voltage by the angle n = 88.85/ after decaying of transients. The solution for current i(t) can be obtained by the Laplace transform method [1] (1.5) where " = R/L : (time constant)–1 Power System Transients (Kizilcay) 1-5 1 Transient phenomena In case (a) the switch closes at the instant when 2 = n, the transient term becomes zero and the current wave is symmetrical. On the other hand, if the switch closes when 2 = ± 90/ + n (case b), the transient term attains its maximum amplitude and the first peak amplitude of the current wave approaches twice of Im (see Fig 1.2b). The rate of decay of the transient component is determined by the time constant 1/" = 0.159 s of the circuit. 1.2.3 Double-Frequency Transients The simplest form of the double-frequency transient is that initiated by opening the circuit breaker in the simplified 10-kV circuit shown in Fig. 1.3. In this single-phase circuit, R1 = 33 mS and L1 = 2.1 mH stand for the short-circuit impedance of the 10-kV source network. Vs is the r.m.s. value of the source voltage. C1 = 2 :F is the equivalent capacitance of the cable connecting an inductive load to the source. L2 = 30 mH and C2 = 40 nF represent the inductive load (motor) and its equivalent winding capacitance. The winding losses of the motor are represented by R2 = 0.47 S. Fig. 1.3 Single-phase disconnection of an inductive load (motor) In general, R1 n TL1 and R2 n TL2. When the switch opens the two halves of the circuit behave independently. Before switch opening, the 50 Hz voltage will divide in proportion to the inductances, that is, to a close approximation the voltage of the capacitors will be , because L2 o L1 and (1.6) When the current passes zero, the switch will open, and the voltage at switch will be at its peak, because the circuit is dominated by inductances. Following current interruption 1-6 Power System Transients (Kizilcay) 1 Transient phenomena C2 will discharge through L2 with a resonance frequency given by (1.7) The influence of R2 is neglected. Meanwhile C1 is now free to take up the source potential, will oscillate about the peak value, , until the losses of the system damp out the disturbance. 10 . 0 [k V ] 7. 5 5. 0 2. 5 0. 0 -2 . 5 -5 . 0 -7 . 5 -1 0. 0 4 5 (f ile S w_O pen 1. pl4; x -v a r t ) v : S W 6 7 8 9 [m s ] 10 v :MO T Fig. 1.4 Source side (") and load side (Q) voltage transients 20 [k V ] 15 10 5 0 -5 4 5 (f ile S w_O p en1 . p l4; x -v a r t ) v : S W 6 7 8 9 [m s ] 10 -M O T Fig. 1.5 Transient recovery voltage across circuit breaker contacts Power System Transients (Kizilcay) 1-7 1 Transient phenomena The frequency of this oscillation is approximately (1.8) Source side and load side transients are depicted in Fig. 1.4. The recovery voltage across the circuit breaker contacts will be the difference between these two, as shown in Fig. 1.5. 1.2.4 Ferroresonance In the phenomenon of series resonance, a very high voltage can appear across the elements of a series LC circuit, when it is excited at or near its natural frequency. From Fig. 1.6a it is obvious that the voltages VL and VC add to give the applied voltage V. But because the voltage across the inductor leads the current in phase by 90/, and the capacitor voltage lags the current by the same amount, the phasor diagram results shown in Fig. 1.6b. It is seen that both VL and VC can far exceed Vs. Such resonant conditions are to be avoided in power circuits, but they can occur inadvertently. The phenomenon is referred to as ferroresonance, since the inductance involved is usually iron cored and consequently, a series resonance between a nonlinear inductance and a linear capacitance may occur. Fig. 1.6 Simple series resonance 1-8 Power System Transients (Kizilcay) 1 Transient phenomena To explain ferroresonance, distortions in the current and in the voltage across the L and C will be ignored, only the fundamental components will be concerned with. Resistance of the circuit will be neglected for simplicity. Fig. 1.7 shows a 245-kV ferroresonant circuit consisting of voltage source, nonlinear inductance, L(I) and capacitance, C. The nonlinear inductance represents the magnetizing inductance of an 245-kV inductive voltage transformer (VT) [4]. C = 150 pF is the grading capacitor across the open circuit breaker. The voltage transformer and the circuit breaker are part of a 220-kV outdoor switchyard. Fig. 1.7 245-kV simple ferroresonant circuit The r.ms. voltage across the inductance can be written as (1.9) This voltage leads the current I by 90/. The voltage across the capacitor is given by (1.10) the minus sign indicating that it is antiphase with VL and lags the current by 90/. The total voltage will be (1.11) The voltage and current relationships specified by Equations (1.9) and (1.11) are drawn in Fig. 1.8. The inclined straight line depicts Eq. (1.11) for VL. Since both curves represent VL in the diagram, the operating point must be where the two curves cross at P. The capacitor voltage in this instance is PQ and the inductor voltage PB, which modestly exceeds Vs, whereas the current is given by 0B. Power System Transients (Kizilcay) 1-9 1 Transient phenomena Fig. 1.8 Voltage and current relationships in a ferroresonant circuit If the voltage were applied to the capacitor alone, it would take a much larger current IC, but if applied to the inductor alone, the current would be the smaller current, IL. The slope of the inclined line is given by (1.12) indicating that if either T or C is reduced the slope will increase and the intersection point P will progress up the curve. Simultaneously, the voltage VC and VL will increase sharply. This is demonstrated in Fig. 1.9 which shows the consequences of changing C, all other parameters remaining constant. In general the capacitor line makes multiple intersections with the curve VL = TL(I) when the complete characteristic is considered. Three such intersections for one straight line, designated (a), (b) and (c), illustrate this point. It is observed that values of VC and VL corresponding to point (a) are negative and far exceed those corresponding to point (b). VC > VL is for point (a), whereas VC < VL for point (b). This shows that the current I leads the voltage Vs for condition (a), but lags behind V for condition (b). Both (a) and (b) are stable operating points, since any slight variation of I from operating point, will cause voltage changes tending to restore the current to its initial value. The phase of the voltage at the time of energization effects which operating point, (a) or (b), will be reached. Point (c) is unstable operating point. A momentary variation in I would cause changes in VC and VL such as to reinforce the deviation and destabilize rather than stabilize. 1-10 Power System Transients (Kizilcay) 1 Transient phenomena Fig. 1.9 Effect of increasing C in a ferroresonant circuit Fig. 1.10 shows the flux-current characteristic of the inductance. The current and voltage at "VT" across voltage transformer in the circuit (Fig. 1.7) is plotted in Fig. 1.11. The combination of C = 150 pF and the non-linear characteristic of the inductor results in typical ferroresonant oscillations, where the voltage across VT reaches very high values. Increasing the series capacitance to 300 pF causes that the ferroresonance almost disappears (Fig. 1.12). Also introducing a resistance connected parallel to the inductance (500 MS) has a limiting effect on ferroresonance as shown in Fig. 1.13. Fig. 1.10 Flux versus current for the magnetizing inductance of VT Power System Transients (Kizilcay) 1-11 1 Transient phenomena 900 0. 090 [ k V] [ A] 600 0. 052 300 0. 014 0 -0.024 -300 -0.062 -600 -900 0. 00 -0.100 0. 04 (f ile f erro0. pl4; x -v ar t ) v : VT 0. 08 0. 12 0. 16 0. 20 [s] c : SO U R C E-VT Fig. 1.11 Ferroresonance in the circuit of Fig. 1.7 (C = 150 pF) 25 0. 0 1. 0 [kV] [m A] 18 7. 5 0. 6 12 5. 0 62 . 5 0. 2 0. 0 -0. 2 -62 . 5 -12 5. 0 -0. 6 -18 7. 5 -25 0. 0 0. 0 0 -1. 0 0. 0 4 0. 0 8 (f ile f erro1 . pl4; x -v a r t ) v : VT c : S O U R C E -V T 0. 1 2 0. 1 6 [s] 0. 2 0 Fig. 1.12 Influence of increased C on ferroresonance (C = 300 pF) 250. 0 3 [ k V] [m A] 187. 5 2 125. 0 1 62. 5 0. 0 0 -62.5 -1 -125.0 -2 -187.5 -250.0 0. 00 -3 0. 04 (f ile f erro0r. pl4; x -v a r t) v : VT 0. 08 0. 12 0. 16 [s] 0. 20 c : SO U R C E-VT Fig. 1.13 Effect of parallel resistance on ferroresonance 1-12 Power System Transients (Kizilcay) 1 Transient phenomena 1.3 Transients in Three-phase Circuits In Section 1.2 transients in single-phase circuits have been discussed. Polyphase circuits are generally more complicated, though little more complex than the single-phase circuits. Power systems consist of three-phase circuits in general. The complication arises from the proliferation of three-phase components and branches introduced by the other two phases and also because of the need to consider mutual coupling between phases. The three-phase systems can be solidly grounded at their neutrals, they can be completely isolated from ground, or they can be grounded through a neutral impedance of some kind. The transient voltages caused by switching operations or other disturbances (faults) will often depend upon the neutral point treatment. In a system where the neutral is solidly grounded, the three phases are virtually independent and behave like three independent single-phase circuits if the ground impedance itself is negligible and mutual inductive coupling between phases is omitted. Thus, if a circuit breaker opens to clear a fault or shed a load, the c.b. poles interrupt the current in each phase independently at current zero-crossing. The transient recovery voltage across the breaker poles or load can be determined by the single-phase methods. The situation is different when the neutral is ungrounded, or grounded through an impedance, for example through a arc suppression coil, the inductance of which forms a parallel resonant circuit with the line-to-ground capacitances. Suppose we are switching off a Y-connected capacitor bank which has no connection at the neutral as shown in Fig. 1.14. The 15 Mvar capacitor bank is connected to 10-kV busbar (Vpeak = 8.165 kV). The neutral point of the bank is isolated. 1 nF connected to neutral shown in Fig. 1.14 represents the small stray capacitance. Fig. 1.14 Three-phase capacitor bank switching Power System Transients (Kizilcay) 1-13 1 Transient phenomena Under steady-state conditions when the bank is energized, the symmetry of the circuit will cause the neutral point N of the capacitor bank to be at ground potential. Suppose that when the switch is opened, phase A interrupts first. The current IA will reach zero when the voltage VA is at its peak. This can be seen in Fig. 1.15, where waveforms of capacitor voltage and current of phase A are plotted. The current in phase A is interrupted at t = 10 ms. The other poles B and C of the switch remain closed. Once the capacitor of phase A is disconnected, there is nowhere for the charge on CA to go, it remains trapped and this capacitor will retain Vpeak. Phases B and C form now a single circuit in which the current I = IB = –IC flows. This unsymmetry causes the potential of the neutral point, N, to rise with respect to ground as shown in Fig. 1.15. Hence phase A follows the voltage of the neutral with a displacement of Vpeak. 10 1 50 0 [k V] [A] 5 1 00 0 0 5 00 -5 0 -1 0 -5 0 0 -1 5 -1 0 00 -2 0 -1 5 00 0 10 20 (f ile C a p3 p h 1. p l4 ; x -v ar t ) v : C A P A 30 v :N 40 50 [m s ] 60 c : S R C A -C A P A Fig. 1.15 Waveforms of phase A current ()) and voltage (") of the disconnected capacitor CA, and of neutral point voltage (Q) 1500 [ A] 1000 500 0 -500 -1000 -1500 0 10 20 (f ile c ap3ph3 .pl4; x -v ar t ) c : SR C A -C APA 30 c : SR C B -C APB 40 50 [m s] 60 c : SR C C -C APC Fig. 1.16 Three phase switch opening. Phase currents A: ", B: Q, C: ) 1-14 Power System Transients (Kizilcay) 1 Transient phenomena Since the neutral point is not effectively grounded, after opening of phase A, the remaining poles B and C of the switch interrupt the current at the same time at zerocrossing as depicted in Fig. 1.16. The waveforms of the capacitor voltages to ground are plotted in Fig. 1.17 when the capacitor bank is entirely disconnected. Due to charges trapped on the capacitors after three-phase switching off, the voltages of capacitors and of the neutral point remain constant. 15 [k V ] 10 5 0 -5 -1 0 -1 5 0 10 (f ile c ap3 ph 3. p l4; x -v ar t ) v : C A P A 20 v :C A PB 30 v :C A PC 40 50 [m s ] 60 v :N Fig. 1.17 Phase to ground voltages of the capacitor bank and voltage of the neutral after three-phase disconnection of the bank If the neutral of three-phase capacitor bank and the source neutral are solidly grounded, the analysis for a single-phase circuit would apply to the individual phases of the threephase circuit. For completeness, that case is shown in Fig. 1.18. The three-phase interruption is plotted in Fig. 1.19, whereas voltages to ground of the three capacitors are shown in Fig. 1.20. Fig. 1.18 Switching off of a Y-connected capacitor bank with solidly grounded neutral Power System Transients (Kizilcay) 1-15 1 Transient phenomena 15 00 [A ] 10 00 50 0 0 -5 00 -1 00 0 -1 50 0 0 10 20 (f ile c ap3 ph 5. p l4; x -v ar t ) c : S R C A -C A P A 30 c : S R C B -C A P B 40 c:SR C C 50 [m s ] 60 -C A P C Fig. 1.19 Three-phase interruption of capacitor currents (A: ", B: Q, C: )) 90 00 [V ] 60 00 30 00 0 -3 00 0 -6 00 0 -9 00 0 0 10 (f ile c ap3 ph 5. p l4; x -v ar t ) v : C A P A 20 v :C A PB 30 40 50 [m s ] 60 v :C A PC Fig. 1.20 Voltages of the disconnected capacitors (A: ", B: Q, C: )) The current of each capacitor is interrupted at zero-crossing of the phase current independently. Since the voltage reaches its peak when the current crosses zero value for a capacitance, all three capacitor voltages remains at the peak value after disconnection of phases because of trapped charges. 1-16 Power System Transients (Kizilcay) 1 Transient phenomena 1.3.1 Typical Power System Transients Electrical transients in power systems are manifold. Over the years through the experience in the operation of power systems, especially due to malfunction of the system, different kinds of transient phenomena have been identified and investigated. In the following important topics of transient phenomena are given: ! Lightning overvoltages – direct lightning strokes – indirect lightning strokes, back flashover – induced lightning overvoltages – protection by surge arresters ! Switching transients – energization and re-energization of lines and cables – energization of transformers – capacitor switching – reactor switching – circuit breaker duty, current chopping, restriking phenomena – load rejection – ferroresonance – motor startup – power electronics applications – harmonic distortion ! Faults – symmetrical and unsymmetrical faults – fault clearing – short-line faults – shaft torsional oscillations – transient stability ! Very fast transients in GIS (gas-insulated switchgear) – disconnector operations – faults (fast breakdown of the gas gap) Power System Transients (Kizilcay) 1-17 1 Transient phenomena 1.4 Stresses on Equipment caused by Transients Electrical transients in power systems may cause stresses on equipment. These are mainly due to overvoltage and/or overcurrent. In the following the origin and typical characteristics of overvoltages and overcurrents will be briefly described. 1.4.1 Overvoltages In general the overvoltages caused by the transients are important in a power system because of their stresses exerted on the insulation or on protective devices like surge arresters. The overvoltages can be classified regarding their origin or duration/shape. Regarding origin of overvoltages, a distinction can be made between internal and external overvoltages. Internal overvoltages are caused by an excitation within the system such as faults or switch closing and opening without any influence from outside. In contrary, external overvoltages arise by an excitation exerted from outside of the system. Lightning stroke is typical cause of external overvoltages. Fig. 1.21 summarizes the classification of overvoltages. Fig. 1.21 Classification and origin of overvoltages 1-18 Power System Transients (Kizilcay) 1 Transient phenomena The classification of overvoltages for insulation coordination studies is given in the norm IEC 71-1 Insulation Co-ordination, Part 1: Definitions, principles and rules [2]. Characteristics of voltages and overvoltages are specified according to [2] as follows: • Continuous (power frequency) voltage: Power frequency voltage, considered having constant r.m.s. value, continuously applied to any pair of terminals of an insulation configuration. • Temporary overvoltage: Power frequency overvoltage of relatively long duration. • Slow-front overvoltage: Transient overvoltage, usually unidirectional, with time to peak 20 :s < Tp # 5000 :s, and tail duration T2 # 20 ms. • Fast-front overvoltage: Transient overvoltage, usually unidirectional, with time to peak 0.1 :s < T1 # 20 :s, and tail duration T2 # 300 :s. • Very fast-front overvoltage: Transient overvoltage, usually unidirectional with time to peak Tf # 0.1 :s, total duration < 3 ms, and with superimposed oscillations at frequency 30 kHz < f < 100 MHz. Overvoltage may occur between one phase conductor and earth or between phase conductors having a peak value exceeding the corresponding peak of the highest voltage of equipment, Um. Um is the highest r.m.s. value of phase-to-phase voltage for which the equipment is designed in respect of its insulation. Overvoltage values (phase to earth) are expressed in p.u. as overvoltage factor, unless otherwise indicated: (1.13) 1.4.2 Overcurrents Overcurrents initiated by transients may cause thermal and mechanical stresses on equipment. The classification of overcurrents can be made analog to overvoltages. Internal overcurrents get their energy from the system. Typical example is short circuit Power System Transients (Kizilcay) 1-19 1 Transient phenomena currents caused by faults in power systems. They are mainly power frequency overcurrents superimposed by high frequency oscillations. Depending on inception angle, they may be asymmetric with high peak value. The duration of the s.c. current plays a role for thermal stress, whereas the peak value is responsible for mechanical stress due to magnetic force. External overcurrents arise from direct and indirect lightning strokes. They may have very high amplitude and are of very short duration. 1.5 Electrical Transients and Associated Frequency Ranges The study of electrical transient phenomena in power systems involves a frequency range from DC to about 50 MHz or in specific cases even more. Above power frequency these usually involve electromagnetic phenomena, whereas below power frequency also transients of the electromechanical type in rotating machines can be involved. Table 1.1 gives an overview on the various origins of transients and their most common frequency ranges. Minimum frequency values below power frequency indicate the frequency band required to represent main time constants of the relevant transients. Table 1.1 Origin of electrical transients and associated frequency ranges Origin Transformer energization, ferroresonance Load rejection Fault clearing Fault initiation Line energization Line reclosing Transient recovery voltage Terminal faults Short line faults Multiple restrikes of circuit breaker Lightning surges, Faults in substations Disconnector switching and faults in GIS 1-20 Frequency range (DC) 0.1 Hz – 1 kHz 0.1 Hz – 3 kHz 50 Hz – 3 kHz 50 Hz – 20 kHz 50 Hz – 20 kHz (DC) 50 Hz – 20 kHz 50 Hz – 20 kHz 50 Hz – 100 kHz 10 kHz – 1 MHz 10 kHz – 1 MHz 100 kHz – 50 MHz Power System Transients (Kizilcay) 1 Transient phenomena In some cases the total duration of electrical transients may last longer than indicated in the above table, e.g. saturation of large transformers during energization, but normally shorter time periods of study is of real interest. Representation of all system components which are valid within the large frequency range of 0 to 50 MHz is practically not possible. For this reason, those physical characteristics of a specific network element that play significant role in the transient phenomena to be studied, should be given detailed consideration for the modeling. The representation of the individual network elements must therefore correspond to the specific frequency range of the particular transient phenomenon. In [3] the frequency ranges of electrical transients given in Table 1.1 are classified as four typical groups with overlapping frequency ranges for which specific models of components may be established. Table 1.2 shows these groups related to the actual steepness of overvoltages. Table 1.2 Classification of frequency ranges for modeling of system components Group Frequency range time-domain characteristic Representation mainly for I 0.1 Hz – 3 kHz low frequency oscillations temporary overvoltages II 50 Hz – 20 kHz slow front surges switching overvoltages III 10 kHz – 3 MHz fast front surges lightning overvoltages IV 100 kHz – 50 MHz very fast front surges restrike overvoltages Power System Transients (Kizilcay) 1-21