Survey
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Stray voltage wikipedia , lookup
Voltage optimisation wikipedia , lookup
Power engineering wikipedia , lookup
Opto-isolator wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Mains electricity wikipedia , lookup
Three-phase electric power wikipedia , lookup
History of electric power transmission wikipedia , lookup
Alternating current wikipedia , lookup
SECTION 26 1200 MEDIUM-VOLTAGE TRANSFORMERS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: Single and three phase individually mounted transformers and the transformer component of unit substation equipment operating at a voltage greater than 600 volts, for power and lighting applications. and medium-voltage transformers. B. Related Requirements: C. 1. Division 01 - General Requirements. 2. Section 26 0500: Common Work Results for Electrical. 3. Section 26 0513: Basic Electrical Materials and Methods. 4. Section 26 0526: Grounding and Bonding. 5. Section 26 0533: Raceways, Boxes, Fittings, and Supports. 6. Section 26 0516: Medium Voltage Cables, Splices and Terminations. 7. Section 26 1316: Medium-Voltage Metal-Enclosed Load Interrupter. 8. Section 26 1100: Load Center - Unit Substations. Codes and Applicable Standards: Transformers shall comply with all applicable IEEE, ANSI, and NEMA Standards for medium voltage Dry-Type Transformers including those with solid cast and/or resin-encapsulated windings. 1. Department of Energy Policy Act of 2005 - Public Law 109-58. 2. California Energy Commission Appliance Efficiency Regulations. 3. California Building Code. 4. ANSI/NFPA70, National Electrical Code, as adopted by the State of California. 5. IEEE C57.12.01, General Requirements for Dry-Type Distribution and Power Transformers Including Those with Solid Cast and ResinEncapsulated Windings PROJECT NAME SCHOOL NAME 10/01/2011 MEDIUM-VOLTAGE TRANSFORMERS 26 1200-1 D. 1.02 6. ANSI C57.12.51, Requirements for Ventilated Dry-Type Power Transformers, 501 KVA and Larger, Three-Phase with High-Voltage 601 to 34 500 Volts, Low Voltage 208Y/120 to 4160 Volts 7. ANSI C57.12.55, Dry-Type Transformers in Unit Installations, Including Unit Substations - Conformance Standard 8. ANSI/IEEE C57.98, Impulse Tests, Guide for Transformer (Appendix to ANSI/IEEE C57.12.90) 9. IEEE C57.12.91, Test Code for Dry-Type Distribution and Power Transformers 10. IEEE C57.94, Recommended Practice for Installation, Application, Operation and Maintenance of Dry-Type General Purpose Distribution and Power Transformers 11. IEEE C57.96, Guide for Loading Dry-Type Distribution and Power Transformers 12. NEMA ST 20, Dry Type Transformers for General Applications 13. OSHA 29 CFR 1910.145 Specification for Accident Prevention Signs and Tags ACRONYMS ANSI American National Standards Institute OAR Owner Authorized Representative CEC California Electrical Code EOR Engineer of Record IBC International Building Code IEEE Institute of Electrical and Electronics Engineers NEC National Electrical Code NEMA National Electrical Manufacturers Association SUBMITTALS A. PROJECT NAME SCHOOL NAME Provide in accordance with Division 01. 10/01/2011 MEDIUM-VOLTAGE TRANSFORMERS 26 1200-2 B. Shop Drawings: Include make, catalog number, dimensions, weight, KVA rating, percent impedance, finish, type, insulation class, design temperature and taps provided. Include regulation at 80 percent and 100 percent of full load, noload loss, full-load loss, percent efficiency, percent impedance, noise level and continuous capacity rating. Provide point to point connection diagrams and elevation details. C. Provide manufacturer’s data and inspection report that confirm compliance with the requirements of this section. D. Provide a copy of the following test reports: Tests shall be performed on transformers, in accordance with IEEE C57.12.91. EOR shall review the reports for conformance with the specified criteria and applicable standards. Submit one copy for each set of shop drawings: 1. No-Load Losses. 2. Load Losses: Measurements shall be taken at multiple levels and plotted to show compliance with the specified criteria and applicable standards. 3. Turn Ratio. 4. Applied Potential (High-Pot). 5. Temperature Rise. 6. Induced Potential. 7. Sound Level. 8. Basic Impulse Insulation level (BIL). 9. Impedance. 10. Polarity and Phase Rotation. 11. Exciting Current. 12. Certified Test Report. E. 1.03 Installation Instructions: Submit manufacturer's complete package of printed installation instructions and connection diagrams. WARRANTY A. PROJECT NAME SCHOOL NAME Transformers shall be warranted to be free from defects in materials, fabrication and execution for three years from date of substantial completion. 10/01/2011 MEDIUM-VOLTAGE TRANSFORMERS 26 1200-3 PART 2 - PRODUCTS 2.01 EQUIPMENT A. Transformers manufactured by Square D, Siemens, PowerSmiths, MGM, and Cutler Hammer or equal. B. Transformers shall be substation type with side-wall primary and secondary terminations. C. Transformers shall be solid-cast, dry-type construction, mounted in a ventilated enclosure. There shall be no exposed screws, bolts, or other fastening devices that are externally removable. D. There shall be no openings through which foreign objects such as sticks, rods, wires, or the like might contact live parts. Screen ventilated spaces from rodents and foreign objects. Provide means for padlocking compartment door(s). Padlocked locations shall be equipped with Corbin CAT 60 padlocks. E. The average temperature rise of the transformer windings shall not exceed 80 degrees C when the transformer is operated at full nameplate rating. The transformer shall be capable of carrying 100 percent of the nameplate KVA rating in a 40 degrees C maximum, 30 degrees C average ambient as defined by IEEE C57.12.01. F. Terminations shall be side-wall mounted for close-coupling to high and low voltage switchgear sections (Primary connection points shall have NEMA standard termination lug holes). G. The transformer shall be rated as indicated on Drawings. The transformer shall be furnished with two 2 ½ percent full capacity above normal and two 2 ½ percent full capability below normal primary taps. Sound level shall not exceed the maximum specified by NEMA TR-1 for the applicable KVA size of the transformer. H. Primary and secondary windings shall be constructed of copper conductors. Primary and secondary phase windings for each phase shall each be separately cast as one rigid tubular coil, and arranged coaxially. Each cast coil shall be fully reinforced with glass cloth, and cast under vacuum to provide complete, void-free resin impregnation throughout the entire insulation system. I. The transformer core shall be constructed of high grade, grain-oriented silicone steel laminations, with high magnetic permeability. Magnetic flux density is to be kept well below the saturation point. The core shall be cruciform in shape, with mitered joints to keep core losses, excitation current and noise level at a minimum. The outside surfaces of the core shall be protected against corrosion by painting with a suitable coating after assembly. Core dipping is not permitted. PROJECT NAME SCHOOL NAME General Electric, 10/01/2011 MEDIUM-VOLTAGE TRANSFORMERS 26 1200-4 J. The enclosure shall be constructed of heavy-gage sheet steel, minimum 12-gage. Ventilating openings shall be in accordance with NEMA and CEC standards for ventilated enclosures. The cabinet shall be furnished with a minimum of four hinged doors. The cabinet shall be furnished with door sills for easy panel installation. a. Outdoor units shall be furnished with a NEMA 3R enclosure. K. The base shall be constructed to permit rolling or skidding in any direction, and shall be furnished with jacking pads designed to be flush with the transformer enclosure. L. Transformers shall be free of partial discharge up to at least 1.2 times the rated line to ground voltage. High voltage coils shall be subjected to a partial discharge test to verify its partial discharge. M. Each transformer to be installed under this section shall be sound tested at the factory. Contractor shall provide two copies of transformers tests reports for EOR review. a. Transformers up to 35 KVA shall be less than 40 decibels. Transformers 36 KVA or more shall be a minimum of five decibels below NEMA standards per unit. N. Transformers shall be provided with vibration dampers consisting of Korfund, Mason, or Caldynamics rubber pad and Elastorib sheeting. Size and number of shock mounts shall be in accordance with manufacturer's recommendations. O. Transformers shall be UL listed. P. Verify all points of connection with the manufacturer’s requirements, instructions, or recommendations prior to installation. Actual dimensions, weights, clearances and installation requirements shall be verified and coordinated prior to commencement of work. Q. Provide and install OSHA/CAL OSHA mandated bilingual (English and Spanish) hazard warning signs on all accessible equipment sides containing access doors and/or panels. The signs shall be a minimum of 14 inch by 10 inch in size and be constructed on an aluminum backing. Design of signs shall be OSHA 29 CFR 1910.145 compliant with the words DANGER HIGH VOLTAGE KEEP OUT. Signs shall be attached to its intended mounting surface with a minimum if ten evenly distributed pop rivets for metal surfaces or tamper resistant screws on metal or other surfaces provided that protruding portion of screws if any is covered to eliminate the possibility of an injury. PART 3 - EXECUTION 3.01 DELIVERY AND STORAGE PROJECT NAME SCHOOL NAME 10/01/2011 MEDIUM-VOLTAGE TRANSFORMERS 26 1200-5 A. 3.02 Deliver, storage, protect and handle products in accordance with the manufacturer’s recommendations. INSTALLATION A. Transformer core frame shall be installed level on shock absorbing pads with enclosure. B. Mounting bolts shall be extended into pads only and shall not be in direct contact with building structural members. Install transformer ventilation openings not closer than six inches from any wall surface. Installation shall comply with CBC seismic design requirements. C. Flexible jumpers shall be installed for grounding continuity from enclosure to conduits or bus ducts where required. D. Transformers installed outdoors or below grade shall be installed on concrete pads as described under Section 03 3000: Cast-In-Place Concrete and as detailed in Drawings. Anchored bolts shall be tested to withstand 100 foot-pounds torque. E. Install according to manufacturer's installation instructions. 3.03 VOLTAGE CHECK A. Set taps on transformers as required providing satisfactory operating voltages with present loads energized, including new loads and any existing loads. B. Provide instruments and accessories required to perform testing. C. Follow manufacturer's instructions for checking output voltage and voltage tap changing. 3.04 PROTECTION A. 3.05 Protect the Work of this section until Substantial Completion. CLEANUP A. Remove rubbish, debris, and waste materials and legally dispose of off the Project site. B. Repair scratched or marred surfaces affected during the execution of this work. Repaired surfaces shall match original finish. C. Manufacturer to provide touch-up paint with delivery. END OF SECTION PROJECT NAME SCHOOL NAME 10/01/2011 MEDIUM-VOLTAGE TRANSFORMERS 26 1200-6