Veracity Asset Management Group
Bid Package 15-114
6 Pad Mounted Transformers
SPECIFICATION SHEET
The following items are available for purchase as is, where is. The transformers are
totally refurbished to new condition.
1) 1986 Pioneer – Old serial number A10669-2 – new serial # 1RD0434W - TRSF, PADMOUNT,
150KVA, 7.2/12.5KV/120/208, DF, RF
TRANSFORMERS SHALL BE CONSTRUCTED AND TESTED IN ACCORDANCE WITH
THE STANDARD BELOW.
TRANSFORMERS SHALL BE THREE PHASE, PADMOUNT TYPE
ONAN, FINLESS DESIGN, AND HAVE A 12470GrdY/7200 VOLT HIGH VOLTAGE
WINDING AND A 208GrdY/120 VOLT SECONDARY WINDING.
TRANSFORMERS WILL BE 15kV HIGH VOLTAGE INSULATION CLASS, COMPLETE
WITH 15kV 200 AMP BUSHING WELLS. INSERT BUSHINGS ARE EXTERNALLY
REMOVABLE AND CAN ACCOMMODATE ELASTIMOLD LOADBREAK ELBOWS. THE
DEAD-FRONT DESIGN SHALL INCORPORATE A RADIAL FEED CAPABILITY THE HIGH
VOLTAGE TAPS SHALL BE +5.0%, +2.5%, 0%, -2.5%, AND -5% WITH AN OFF-CIRCUIT
TAP SWITCH LOCATED ON THE EXTERIOR OF THE TANK. THE 0% CENTRE POSITION
TAP SETTING WILL BE EITHER 3 OR C AND THE TAP SWITCH IS TO BE SET IN THIS
POSITION WHEN DELIVERED.
ALL TRANSFORMERS SHALL COME COMPLETE WITH OIL- IMMERSED WITHDRAWABLE BAYONET FUSES, COMPLETE WITH DRIP TRAYS. THE BAYONET FUSE SHALL
BE CONNECTED ELECTRICALLY IN SERIES WITH NON-USER ACCESSIBLE INTERNAL
CURRENT LIMITING FUSE(S).
ACCESSORIES SHALL INCLUDE, DOUBLE FRONT DOOR ACCESS WITH HANDLES
AND HOLD OPEN DEVICES, A TOP LID FIR THE HIGH VOLTAGE AND LOW VOLTAGE
COMPARTMENTS ENCLOSED IN A WEATHERPROOF TAMPER-PROOF
COMPARTMENT, ONE (1) INCH IPS BRASS DRAIN BRASS OK FILL PLUG.
TRANSFORMERS SHALL HAVE A BITUMINOUS COATING APPLIED TO ALL
EXTERNAL UNDERSIDE SURFACES. STANDARDS: CSA-C227.4-06 (LATEST EDITION)
THREE-PHASE, DEAD-FRONT, PADMOUNTED DISTRIBUTION TRANSFORMERS
1
2) 1982 Pioneer – Old serial number A8852-2 – new serial # 1RD0432T - 75KVA,
7.2/12.5KV/120/208, DF, RF
3) 1982 Pioneer – Old serial number A8852-5 – new serial # 1RD0433T - 75KVA,
7.2/12.5KV/120/208, DF, RF
TRANSFORMERS SHALL BE CONSTRUCTED AND TESTED INACCORDANCE WITH
THE STANDARD BELOW.
TRANSFORMERS SHALL BE THREE PHASE, PADMOUNT TYPE ONAN, FINLESS
DESIGN, AND HAVE A 12470GrdY/7200 VOLT HIGH VOLTAGE WINDING AND A
208GrdY/120 VOLT SECONDARY WINDING.
2
TRANSFORMERS WILL BE 15kV HIGH VOLTAGE INSULATION CLASS, COMPLETE
WITH15kV 200 AMP BUSHING WELLS. INSERT BUSHINGS AREEXTERNALLY
REMOVABLE AND CAN ACCOMMODATE ELASTIMOLD LOADBREAK ELBOWS. THE
DEAD-FRONT DESIGN SHALL INCORPORATE A RADIAL FEED CAPABILITY
THE HIGH VOLTAGE TAPS SHALL BE +5.0%, +2.5%, 0%, -2.5%, AND -5% WITH AN OFFCIRCUIT TAP SWITCH LOCATED ON THE EXTERIOR OF THE TANK. THE 0%
CENTRE POSITION TAP SETTING WILL BE EITHER 3 ORC AND THE TAP SWITCH IS TO
BE SET IN THIS POSITION WHEN DELIVERED.
ALL TRANSFORMERS SHALL COME COMPLETE WITH OIL-IMMERSED WITHDRAWABLE BAYONET FUSES, COMPLETE WITH DRIP TRAYS. THE BAYONET FUSE SHALL
BE CONNECTED ELECTRICALLY IN SERIES WITH NON-USER ACCESSIBLE INTERNAL
CURRENT LIMITING FUSE(S).
ACCESSORIES SHALL INCLUDE, DOUBLE FRONT DOOR ACCESS WITH HANDLES
AND HOLD OPEN DEVICES, A TOP LID FOR THE HIGH VOLTAGE AND LOW VOLTAGE
COMPARTMENTS ENCLOSED IN A WEATHERPROOF TAMPER- PROOF
COMPARTMENT, ONE (1) INCH IPS BRASS DRAIN BRASS OK FILL PLUG.
TRANSFORMERS SHALL HAVE A BITUMINOUS COATING APPLIED TO ALL
EXTERNAL UNDERSIDE SURFACES.
STANDARDS: CSA-C227.4-06 (LATEST EDITION)
THREE-PHASE, DEAD-FRONT, PADMOUNTED DISTRIBUTION TRANSFORMERS
3
4) 1990 Cam Tram – Old serial number DC90L12201 – new serial # 1RD0435T - TRSF,
PADMOUNT, 300KVA, 7.2/12.5KV/120/208, DF,RF,
TRANSFORMERS SHALL BE CONSTRUCTED AND TESTED INACCORDANCE WITH
THE STANDARD BELOW.
TRANSFORMERS SHALL BE THREE PHASE, PADMOUNT TYPEONAN, FINLESS
DESIGN, AND HAVE A 12470GrdY/7200 VOLT HIGH VOLTAGE WINDING AND A
208GrdY/120 VOLT SECONDARY WINDING.
4
TRANSFORMERS WILL BE 15kV HIGH VOLTAGE INSULATION CLASS, COMPLETE
WITH15kV 200 AMP BUSHING WELLS. INSERT BUSHINGS ARE EXTERNALLY
REMOVABLE AND CAN ACCOMMODATE ELASTIMOLD LOADBREAK ELBOWS. THE
DEAD-FRONT DESIGN SHALL INCORPORATE A RADIAL FEED CAPABILITY THE HIGH
VOLTAGE TAPS SHALL BE +5.0%, +2.5%, 0%, -2.5%, AND -5% WITH AN OFF-CIRCUIT
TAP SWITCH LOCATED ON THE EXTERIOR OF THE TANK. THE 0% CENTRE POSITION
TAP SETTING WILL BE EITHER 3 OR C AND THE TAP SWITCH IS TO BE SET IN THIS
POSITION WHEN DELIVERED.
ALL TRANSFORMERS SHALL COME COMPLETE WITH OIL-IMMERSED WITHDRAWABLE BAYONET FUSES, COMPLETE WITH DRIP TRAYS. THE BAYONET FUSE SHALL
BE CONNECTED ELECTRICALLY IN SERIES WITH NON-USER ACCESSIBLE INTERNAL
CURRENT LIMITING FUSE(S).
ACCESSORIES SHALL INCLUDE, DOUBLE FRONT DOOR ACCESS WITH HANDLES
AND HOLD OPEN DEVICES, A TOP LID FIR THE HIGH VOLTAGE AND LOW VOLTAGE
COMPARTMENTS ENCLOSED IN A WEATHERPROOF TAMPER-PROOF
COMPARTMENT, ONE (1) INCH IPS BRASS DRAIN BRASS OK FILL PLUG.
TRANSFORMERS SHALL HAVE A BITUMINOUS COATING APPLIED TO ALL
EXTERNAL UNDERSIDE SURFACES.
STANDARDS: CSA-C227.4-06 (LATEST EDITION)
THREE-PHASE, DEAD-FRONT, PADMOUNTED DISTRIBUTION TRANSFORMERS
5
5) 1986 Westinghouse – Old serial number LM23875 – new serial # 1RD0412W - TRSF,
PADMOUNT, 300KVA, 7.2/12.5KV/347/600, DF, RF
TRANSFORMERS SHALL BE CONSTRUCTED AND TESTED IN ACCORDANCE WITH
THE STANDARD BELOW.
TRANSFORMERS SHALL BE THREE PHASE, PADMOUNT TYPE ONAN, FINLESS
DESIGN, AND HAVE A 12470GrdY/7200 VOLT HIGH VOLTAGE WINDING AND A
208GrdY/120 VOLT SECONDARY WINDING.
TRANSFORMERS WILL BE 15kV HIGH VOLTAGE INSULATION CLASS, COMPLETE
WITH 15kV 200 AMP BUSHING WELLS. INSERT BUSHINGS ARE EXTERNALLY
REMOVABLE AND CAN ACCOMMODATE ELASTIMOLD LOADBREAK ELBOWS. THE
DEAD-FRONT DESIGN SHALL INCORPORATE A RADIAL FEED CAPABILITY
6
THE HIGH VOLTAGE TAPS SHALL BE +5.0%, +2.5%, 0%, -2.5%, AND -5% WITH AN OFFCIRCUIT TAP SWITCH LOCATED ON THE EXTERIOR OF THE TANK. THE 0% CENTRE
POSITION TAP SETTING WILL BE EITHER 3 OR C AND THE TAP SWITCH IS TO BE SET
IN THIS POSITION WHEN DELIVERED.
ALL TRANSFORMERS SHALL COME COMPLETE WITH OIL-IMMERSED WITHDRAWABLE BAYONET FUSES, COMPLETE WITH DRIP TRAYS. THE BAYONET FUSE SHALL
BE CONNECTED ELECTRICALLY IN SERIES WITH NON-USER ACCESSIBLE INTERNAL
CURRENT LIMITING FUSE(S).
ACCESSORIES SHALL INCLUDE, DOUBLE FRONT DOOR ACCESS WITH HANDLES
AND HOLD OPEN DEVICES, A TOP LID FIR THE HIGH VOLTAGE AND LOW VOLTAGE
COMPARTMENTS ENCLOSED IN A WEATHERPROOF TAMPER-PROOF OMPARTMENT,
ONE (1) INCH IPS BRASS DRAIN BRASS OK FILL PLUG.
TRANSFORMERS SHALL HAVE A BITUMINOUS COATING APPLIED TO ALL
EXTERNAL UNDERSIDE SURFACES. STANDARDS: CSA-C227.4-06 (LATEST EDITION)
THREE-PHASE, DEAD-FRONT, PADMOUNTED DISTRIBUTION TRANSFORMERS
7
6) 1987 Federal Pioneer – Old serial number A12197-2 – new serial # 1RD0413 - TRSF,
PADMOUNT, 500KVA,19.9/34.5KV/347/600, DF,RF
TRANSFORMERS SHALL BE CONSTRUCTED AND TESTED IN ACCORDANCE WITH
THE STANDARD BELOW
EXCEPT THE HIGH VOLTAGE BIL LEVEL WILL BE 150kV. TRANSFORMERS SHALL BE
THREE PHASE, PADMOUNT TYPE ONAN, FINLESS DESIGN, AND HAVE A
34500GrdY/19900 VOLT HIGH VOLTAGE WINDING AND A 600GrdY/347 VOLT
SECONDARY WINDING.
8
TRANSFORMERS WILL BE 35kV HIGH VOLTAGE INSULATION CLASS, COMPLETE
WITH 35kV 200 AMP BUSHING WELLS. INSERT BUSHINGS ARE EXTERNALLY
REMOVABLE AND CAN ACCOMMODATE ELASTIMOLD LOADBREAK ELBOWS. THE
DEAD-FRONT DESIGN SHALL INCORPORATE A RADIAL FEED CAPABILITY THE HIGH
VOLTAGE TAPS SHALL BE +5.0%, +2.5%, 0%, -2.5%, AND -5% WITH AN OFF-CIRCUIT
TAP SWITCH LOCATED ON THE EXTERIOR OF THE TANK. THE 0% CENTRE POSITION
TAP SETTING WILL BE EITHER 3 OR C AND THE TAP SWITCH IS TO BE SET IN THIS
POSITION WHEN DELIVERED.
ALL TRANSFORMERS SHALL COME COMPLETE WITH OIL- IMMERSED WITHDRAWABLE BAYONET FUSES, COMPLETE WITH DRIP TRAYS. THE BAYONET FUSE SHALL
BE CONNECTED ELECTRICALLY IN SERIES WITH NON-USER ACCESSIBLE INTERNAL
CURRENT LIMITING FUSE(S). ACCESSORIES SHALL INCLUDE, DOUBLE FRONT DOOR
ACCESS WITH HANDLES AND HOLD OPEN DEVICES, A TOP LID FOR THE HIGH
VOLTAGE AND LOW VOLTAGE COMPARTMENTS ENCLOSED IN A WEATHERPROOF
TAMPER-PROOF COMPARTMENT, ONE (1) INCH IPS BRASS DRAIN BRASS OK FILL
PLUG.
TRANSFORMERS SHALL HAVE A BITUMINOUS COATING APPLIED TO ALL
EXTERNAL UNDERSIDE SURFACES. STANDARDS: CSA-C227.4-06 (LATEST EDITION)
THREE-PHASE, DEAD-FRONT, PADMOUNTED DISTRIBUTION TRANSFORMERS
EACH TRANSFORMER SHALL BE EQUIPPED WITH A NON-RESETTABLE DEVICE
WHICH DETECTS INTERNAL TRANSFORMER FAULTS, INCORPORATES PRESSUE
RELIEF AS SPECIFIED IN CLAUSE 8.3 OF CAN/CSA-2.2-06 AND PROVIDES AND
EXTERNAL INDICATION VISIBLE FROM THE GROUND. THE APROVED DEVICE IS
THE IFD (INTERNAL FAULT DETECTOR), MANUFACTURED BY IFD CORP.
IT IS TO BE INSTALLED IN ACCORDANCE WITH IFD CORP. SERVICE INFORMATION
AND LOCATES ON THE TRANSFORMER TANK IN THE RIGHT FRONT QUADRANT
APPROX. HALFWAY BETWEEN THE RIGHTMOST SECONDARY BUSHING AND THE
RIGHT HAND SIDE LIFTING LUG.
9
10
GENERAL INFORMATION

Vendor reserves the right to end this sale at any time for any reason.

Purchaser responsible for removal, loading and transportation of the units in a
safe responsible manner that meet Sellers Safety Guidelines. All units are deenergized.

Purchaser is responsible to arrange for all importing/exporting requirements
along with any custom brokerage and duties if applicable.

All offers to be submitted to Veracity.

All bids are to be submitted by 5pm Friday June 19, 2015
11
PLEASE RETURN THIS PAGE, DULY EXECUTED.
Offer to Purchase:
(6) Reconditioned Pad Mount Transformers
Sold “As-Is, Where-Is”
Bids Must Submitted by 5 PM Friday June 19, 2015
Offeror’s name, address (including zip/postal code), telephone no., and fax no.
Business Name: _________________________________________________
Contact Name:
________________________________________________
Address:
________________________________________________
Phone No:
____________________
E-mail Address:
_________________________________________________
Fax No:
_________________
The buyer pays all transportation costs and also bears the risks for bringing the goods to their final
destination.
Amount of Bid Submitted: ______________________________________ ($
)
Taxes 13% _____________________________________________________(
)
.
TOTAL AMOUNT__________________________________________
)
DATED at
, this
day of
($
,2015 .
SIGNATURE:
_________________________________________________
TITLE:
_________________________________________________
This is my formal offer and I accept all conditions of sale.
To: Rob Krysa
Veracity Asset Management Group
1520 Queen St. E. Suite BT2012, Sault Ste. Marie, On P6A 2G4
Phone: (705) 542-4821
Email: [email protected]
12
GENERAL CONDITIONS OF SALE
1.
WITHDRAWAL –Seller reserves the right to withdraw from the sale any property which
has not been removed by the Offeror, without incurring any liability except to refund to
the Offeror the amount paid on account of such property.
2.
CONDITION OF PROPERTY – The property listed herein (the “Property”) is for sale “asis-where-is”. The description of the Property is based on the best information available
to Veracity and Seller. However, Veracity and Seller expressly disclaims all written, oral,
express or implied warranties including any statutory warranties, and including any
warranties of merchantability, fitness for purpose, freedom from the infringement of
patents or other privately held rights and including any warranties as to the quantity,
kind, character, quality, use or the results of the use, weight, size, functionality or
description of any of the Property.
3.
PAYMENTS –The Offeror agrees to make payment prior to the time of removal of the
items. The Offeror agrees that payment shall be made via certified payment method
including certified cheque, electronic fund transfer, money order, or a bank draft. The
Purchase Price shall be paid in full by the Purchaser no later than 10 Business Days
following the date of the notification of the acceptance of offer. Unless agreed in
writing to an alternate timeframe, if the Purchaser has not made payment of the
Purchase Price in full within 10 Business Days from the date of the Acceptance
Notification, the purchase and sale of the Property contemplated by this Agreement may
be considered null and void and the Purchaser shall lose all claim to and interest in the
Property and may be held responsible for all loss, cost and expense incurred due to the
Purchaser’s failure or default.
4.
TITLE – Unless otherwise provided in the offer, title to the Property sold hereunder shall
vest in the Offeror as and when removal is effected.
5.
REMOVAL – The Offeror, upon acceptance of this offer by Seller and payment by the
Offeror, shall at his/her expense, pack, load and remove the Property. Arrangements to
be finalized with the contact identified in the Offer.
6.
The Offeror is solely responsible for: (i) obtaining all import/export permits, licenses
and permissions, (ii) complying with all applicable laws, regulations and conditions in
connection with such permits, licenses and permissions, and (iii) the payment of all
duties and brokerage fees.
13
7.
FAILURE TO REMOVE – Should the Offeror fail to remove the property in accordance with
Paragraph 5, Seller without prejudice to any other remedies, may cancel the contract
without notice to the Offeror and retain as liquidated damages any deposit or amount
paid on account of the Property. The Offeror shall lose all claim to and interest in the
Property and will be held responsible for all loss, cost and expense incurred due to
his/her failure or default.
8.
CLAIMS – The Offeror shall not be entitled to contest the accuracy of any information in
this document unless notice in writing, setting forth particulars of the Offeror’s claim,
shall have been received by Veracity and Seller at its address shown on the face of the
Offer to Purchase Form within thirty (30) days following acceptance of this offer, or
within ten (10) days following removal of the Property in respect of which such claim is
made, whichever is the earlier. No claim will be considered unless such Property is still
held by or held on the Offeror’s premises for inspection by a representative of Seller.
9.
DAMAGE TO THE PROPERTY – The Offeror shall be responsible for any damage to the
Property resulting from the handling, packing, loading, removal and use of the Property
sold.
10.
ADJUSTMENTS – If, through withdrawal, damage, loss or error, the Property cannot be
delivered to the Offeror, Seller’s liability shall be limited to a refund of the purchase
price.
11.
LIABILITY – In no event shall Veracity or Seller be liable to the Offeror for injuries
suffered by or the death of any person, or for any loss or damage to any property arising
out of the inspection, handling, removal or use of the property listed herein, whether
based on contract, tort including negligence, strict liability or otherwise. The Offeror
shall indemnify and save harmless Veracity and Seller from and against any and all claims,
demands, actions, suits or proceedings of whatever nature including all costs and
expenses incurred in connection therewith, brought or instituted by a third party, and
based on or arising out of the inspection, handling, removal or use of the Property.
12.
CONTACT – This Offer to Purchase form, together with the form of Acceptance, shall,
when executed, constitute the entire agreement between the Offeror and Seller and
time shall be deemed to be of the essence in all respects thereof.
13.
SURVIVAL – The provisions of sections 2, 3, 4, 5, 6, 7, 8, 10, 11, and 13 shall survive the
term of this Agreement.
14