Download 3. Rated voltage and short-time withstand current

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Switch wikipedia , lookup

Voltage optimisation wikipedia , lookup

Stray voltage wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Buck converter wikipedia , lookup

Opto-isolator wikipedia , lookup

Alternating current wikipedia , lookup

Mains electricity wikipedia , lookup

Electrical substation wikipedia , lookup

Earthing system wikipedia , lookup

Transcript
Specification for Tender-
582763457
General Specification for High Voltage
metal-enclosed cubicles from 1 to 24 kV
This is the common article to use for mainly prescription
and tendering purposes.
Content of it;
 General condition,
 Standards,
 Rated values,
 Main system parameters,
 General acceptation parameters,
 Type & routine tests,
 Quality futures
Last update : 2017-05-08
-1-
Specification for Tender-
582763457
Table of contents:
1. General conditions ………………………………………………………..............................
p. 3
2. Standards …………………………………………………………………………………….
p. 3
3. Rated voltage and short-time withstand current………………………..............................
p. 3
4. System parameters …………………………………………………………………..............
p. 4
4.1 Main electrical characteristics ………………………………………….................................
p. 4
4.2 General characteristics …………………………………………………………....................
p. 4-5
5. General requirements relative to the design and manufacture of the switchgear.............
p. 5
5.1 Introduction ……………………………………………………….........................................
p. 5
5.2 Switchboards …………………………………………………………..................................
p. 5-6
5.3 Earthing of metallic parts ………………………………………………..............................
p. 6
5.4 Earthing of the power circuit …………………………………………………………..........
p. 6
5.5 Switches ……………………………………………………..................................................
p. 6-7
5.6 Circuit breakers …………………………………………………………...............................
p. 7
5.7 Busbars ………………………………………………………...............................................
p. 8
5.8 Connections………………………………………………………………………………….
p. 8
5.9 Operating mechanisms …………………………………………………………....................
p. 8
5.10 LV cabinet ………………………………………………..........................................................
p. 9
5.11 Current transformers ……………………………………………………………….............
p. 9
5.12 Low Power Current transformers (LPCT)…… …………………………............................
p. 9
5.13 Voltage transformers ………………………………………………….................................
p. 9
5.14 LV auxiliaries …………………………………………………............................................
p. 9-10
5.15 Control and monitoring …………………………………………………………………......
p.10
5.16 Voltage indicator and phase comparators …………………………………………………..
p.10
5.17 Fault Passage Indicators …………………………………………………………………….
p.10
5.18 Safety of people ……………………………………………………………………………..
p.10
5.19 Automatic Transfer System ………………………………………………………………..
p.11
6. Type tests and routine tests ……………………….....................……...................................
p.11
7. Quality …………………………………………………………….....................…….............
p. 11
Last update : 2017-05-08
-2-
Specification for Tender-
582763457
1. General conditions
The following specifications apply to modular indoor switchboards comprising factory built, metal-enclosed
switchgear assembles.
The equipment to be supplied shall consist of modular cubicles satisfying the following criteria:
- open-ended design,
- easy to install,
- safe and easy to operate,
- compact design,
- low maintenance.
The supplier must be able to prove its extensive possess experience in the field of MV switchgear, and has
already supplied equipment of the same type & production process, in which has been in operation for at
least three years.
2. Standards
The switchgear shall comply with the latest issues of the following IEC recommendations:
- IEC 62 271-200
- IEC 60265-1
- IEC 62271-102
- IEC 60694
- IEC 62271-105
- IEC 62271-100
- IEC 60282-1
- IEC 60185
- IEC 60186
- IEC 60801
- IEC60529
Alternative current metal-enclosed switchgear and controlgear for rated
voltages above 1 kV and up to and including 52 kV,
Switches for rated voltages above 1kV and less than 52kV,
High voltage alternative current disconnectors and earthing switches,
Common specifications for high voltage switchgear and controlgear standard,
High Voltage alternative current switch-fuse combinations,
High Voltage alternative current circuit breakers,
MV fuses,
Current transformers,
Voltage transformers,
Electromagnetic compatibility for industrial process measurement
and control equipment.
Degrees of protection provided by enclosures (IP code)
3. Rated voltage and short-time withstand current
3.1 The switchgear shall be suitable for three-phase systems operating at 24 kV, and 50 Hz. (Please, consult
us for 60 Hz)
3.2 The rated voltage shall be at least 24 kV.
3.3 The short-time withstand current (Ik/tk) shall be 25 kA/1s up to 24kV. (Please, consult us for 2 s and 3 s)
All switchgear shall be capable of withstanding the above conditions without provoking damage, in
accordance with paragraphs 4.5, 4.6 and 4.7 of IEC 60694 and paragraph 4.5 of IEC 62 271-200
recommendations.
Last update : 2017-05-08
-3-
Specification for Tender-
582763457
4. System parameters
The insulation level of the switchgear shall comply with IEC recommendations and the values indicated in
the following table.
4.1 Main electrical characteristics
The hereunder values are for working temperatures from -5° C up to +40° C and for a setting up at an
altitude below 1000 m.
(Please, consult us for out of range temperatures’ and over 1000 m application)
---------------------------------------------------------------------------------------------------------------------------rated voltage (kV) Ur
7.2
12
17.5
24
---------------------------------------------------------------------------------------------------------------------------insulation level
---------------------------------------------------------------------------------------------------------------------------50/60 Hz / 1 mn Ud insulation
20
28
38
50
(kV rms)
Ud isolation
23
32
45
60
---------------------------------------------------------------------------------------------------------------------------1,2/50µs
Up insulation
60
75
95
125
(kV peak)
Up isolation
70
85
110
145
---------------------------------------------------------------------------------------------------------------------------transformer off load (A)
16
cables off load (A)
31.5
--------------------------------------------------------------------------------------------------------------------------short –time withstand current
at 25
630 - 1250 A
Ik/tk (kA/1s)
20
630 - 1250 A
16
630 - 1250 A
(Please, consult us for 2s and 3s)
12.5 400 - 630 - 1250 A
------------------------------------------------------------------------------------------------------------------------------making capacity
at 62.5
630 A
Ima (kA)
50
630 A
40
630 A
31.25 400 - 630 A
-------------------------------------------------------------------------------------------------------------------------------
4.2 General characteristics
---------------------------------------------------------------------------------------------------------------------------Maximum breaking capacity (Isc)
---------------------------------------------------------------------------------------------------------------------------rated voltage (kV)
7.2
12
17.5
24
---------------------------------------------------------------------------------------------------------------------------switch unit (A)
630 - 800
fuse-switch unit (kA)
25
25
20
20
Contactor unit with fuses (kA) 25
25
Circuit breaker unit (kA)
25
25
25
25
Last update : 2017-05-08
-4-
Specification for Tender-
582763457
---------------------------------------------------------------------------------------------------------------------------Endurance
---------------------------------------------------------------------------------------------------------------------------units
mechanical
electrical
endurance
endurance
---------------------------------------------------------------------------------------------------------------------------switch unit (*)
IEC 60265-1
IEC 60265-1
1000 operations class M1
100 breaks at In,pf = 0.7classE3
contactor unit 400
IEC 60470
IEC 60470
300 000 operations
100 000 breaks at 320 A
300 000 breaks at 250 A
contactor unit 400D
100 000 operations
100 000 breaks at 200 A
circuit breaker unit
IEC 62271-100
IEC 62271-100
10 000 operations
40 breaks at 12.5 kA
10 000 breaks at In,pf=0.7
---------------------------------------------------------------------------------------------------------------------------(*) as per recommendation IEC 62271-105, three breaking at pf = 0,2
1730 A / 12 kV
1400 A / 24 kV
2600 A / 5,5 kV
5. General requirements regarding the design and manufacture of the switchgear
5.1 Introduction
The equipment shall satisfy the criteria for indoor, metal-enclosed switchgear class LSC2A & Class PI
partitioning in accordance with paragraph 3.131.1; 3.109.2& 5.102 of 2003-11 edition of IEC 62271-200
recommendations.
The cubicles shall be designed with three compartments housed in a single enclosure:
- switchgear compartment,
- busbar compartment,
- connection compartment, (shall be interlock-controlled accessible)
5.2 Switchboards
The switchboards shall be made up of separate factory built cubicles housing the switchgear (switchdisconnector and switch enclosures shall be mounted horizontally in the cubicles and the circuit breaker shall
be disconnectable and mounted vertically). The cubicles therefore form a compartmented distribution
switchboard that can be extended if necessary.
The cubicles shall meet the requirements of degree of protection index IP3X. The galvanised and electrogalvanised sheet metal and metal fittings shall be painted to provide protection against corrosion. The epoxybased paint shall have a thickness of at least 50 micronsmeter and shall be applied to both sides of all sheet
metal. The colour shall correspond to the RAL colour range proposed.
The switchboard shall be suitable for mounting above cable trenches, crawl spaces or base structures.
Last update : 2017-05-08
-5-
Specification for Tender-
582763457
Each cubicle shall carry a suitably dimensional identification label clearly indicating the functions and
electrical characteristics of the cubicle in accordance with chapter 5.10 of IEC 62271 -200.
The switchgear and the switchboards shall be designed in such a way that the positions of the various
switchgear devices shall be visible by the operator from the front of the switchboard. It shall also be possible
to operate the switchgear from the front of the switchboard.
The civil works specifications shall be unique for all cubicles making up the MV switchboard. The cubicle
widths shall be multiples of 375 mm. In particular, the civil works for the circuit breaker cubicles shall be
identical to the civil works for the switch cubicles.
The manufacturer shall provide an installation drawing to serve as a guide for the civil works.
In accordance with applicable standards, the switchboards shall be designed to prevent access to all live parts
when in operation as well as during maintenance work.
5.3 Earthing of metallic parts
The earthing bars of each of the cubicles making up the switchboard shall be interconnected by a set of
busbars, which shall be connectable outside the switchboard and extend over its full width.
The cross-section of the busbars shall be determined so as to withstand the rated short-circuit current of the
switchgear in accordance with IEC 62271-200 recommendations.
The earthing bar shall be designed for connection to the main earthing bar of the substation without
dismantling any of the bars.
5.4 Earthing of the power circuit
Cable earthing shall be carried out by an earthing switch with a short-circuit making capacity, in accordance
with IEC 62271-102 recommendations. It shall be possible to operate the earthing switch when the switch or
disconnector is open.
A padlocking system shall be provided to lock the earthing switch in either open or closed position. The
position of the earthing switch shall be clearly visible from the front of the cubicle.
Mechanical interlocking (padlocking) systems shall be provided to prevent incorrect operations such as the
closing of the earthing switch with the switch or disconnector in closed position.
The use of keyed or electric locks to actuate the above mentioned interlocking system shall not be accepted.
5.5 Switches
The switches shall use low pressure SF6 gas for current interruption and shall require no maintenance. The
switch enclosure shall be mounted horizontally within the cubicle and the position of the main and earthing
contacts shall be clearly visible from the front of the cubicle. The position indicator shall be placed
directly on the contact-operating shaft.
The open and earthed positions of the main moving contact shall be visible (inspection windows) from the
front of the cubicle upon the customer request.
Last update : 2017-05-08
-6-
Specification for Tender-
582763457
The switch enclosures shall be made of cast epoxy resin that shall be capable of bearing for mechanical
strength, as well as electromagnetic forces.
The switches shall be of the high operating frequency type in accordance with paragraph 3.104 of IEC
60265-1 recommendations. They shall have three positions (closed, open and earthed) and shall be fully
assembled and tested before leaving the factory. The relative pressure of the SF6 gas inside the enclosure
shall not exceed 0.4 bars (400 hPa).
The pole unit enclosures shall be of the “sealed pressure system” type as defined by
IEC 62271-200 chapter 3.118.2 recommendations. Leakage rate shall not be over 0.1% for life span that is
at least 30 years. No refilling of the gas shall be required over this period.
Switch units requiring maintenance or gas refilling will not be accepted.
Switch units would be equipped with analog or pressure switch. Both of them shall be temperature
compensated. Pressure switch shall provide 2 level of indication that are low level and critical level.
The mechanical endurance of the switch operating mechanisms shall ensure at least
1000 operations.
5.6 Circuit breakers
5.6.1 SF6
The circuit breakers shall be mounted vertically and shall be disconnectable. They shall use SF6 gas as the
current interruption medium. They shall require only minimum maintenance and shall provide a high level
of electrical endurance. The position of the circuit breaker shall be clearly visible.
Furthermore, the circuit breakers shall be mechanically interlocked with the power circuit disconnector.
The pole units shall be made of cast epoxy resin and shall be fully assembled and tested before leaving the
factory. The relative pressure of the SF6 gas shall not exceed 2 bars (2000hPa). The pole units shall be of the
“sealed pressure system” type as defined by IEC 62271-100, with a service life of at least 30 years.
No refilling of the gas shall be required over this period.
Circuit breaker pole units requiring maintenance, inspection or gas refilling will not be accepted.
The mechanical and electrical endurance shall ensure at least 10,000 operations.
The circuit breakers shall be covered with test reports that are issued by a recognised organisation affiliated
with an international organisation.
5.6.2 Vacuum
The circuit breakers shall be mounted vertically and shall be disconnectable. They shall use vacuum as the
current interruption medium. They shall require only minimum maintenance and shall provide a high level
of electrical endurance. The position of the circuit breaker shall be clearly visible.
Furthermore, the circuit breakers shall be mechanically interlocked with the power circuit disconnector.
The pole units shall be fully assembled and tested before leaving the factory. The pole units shall be of the
“sealed pressure system” type as defined by IEC 62271-100, with a service life of at least 30 years.
Circuit breaker pole units requiring maintenance, inspection will not be accepted.
The mechanical and electrical endurance shall ensure at least 10,000 operations.
Last update : 2017-05-08
-7-
Specification for Tender-
582763457
The circuit breakers shall be covered with test reports that are issued by a recognised organisation affiliated
with an international organisation.
5.7 Busbars
The busbar compartment shall be located at the top of the cubicle.
It shall include three parallel-mounted bars without phase separating means. Connections shall be made to
the top pads of the switch or disconnector enclosures. Access to the busbars shall only be possible after
removing a single access panel carrying a symbol warning of the danger of electrical shock. No other busbar
access system will be accepted.
5.8 Connections
The HV cable connection pads shall be designed to accept simplified terminations for dry-type cables or to
accept paper-insulated cables impregnated with a non-draining material.
Access to the connection compartment, shall be interlock-controlled accessible, and shall only be possible
after closing the earthing switch. No other access mode will be accepted.
5.9 Operating mechanisms
The operating mechanisms shall provide in front all the necessary means for operating the switches,
disconnectors and circuit breakers.
5.9.1 Load break switch
The operating mechanism box shall include a switch and earthing switch position indicator fixed directly to
the shaft of the moving pole, thereby satisfying the positive break criteria.
This box shall also house the voltage indicators and the mechanical “fuse blown” indicator for fuse-switch
combination units.
The box shall be accessible with the cables and busbars live, without isolating the entire switchboard,
and shall be designed for easy installation of padlocks, key locks, auxiliary contacts, releases and the
usual LV accessories.
The front cover of the operating mechanism shall be suitable for the application of all symbols, mimic
diagrams, nameplates and padlocking fixtures required by the function implemented.
All switch and earthing switch operations shall be carried out with an anti-reflex lever and shall be
independent of the action of the operator after charging the operating mechanism springs.
The operating mechanisms shall be so constructed that can come out of their neither open nor closed
positions by forces arising from gravity, vibration, reasonable shocks or accidental touching of the lever of
their operating devices, or by electromagnetic forces.
5.9.2 Circuit breaker
The operating mechanism box shall include:
mechanical “open/closed” position indicator,
“charged/discharged” indicator for the operating mechanisms springs,
spring charging lever forming an integral part of the operating mechanism; circuit breakers not satisfying
this condition will not be accepted,
Last update : 2017-05-08
-8-
Specification for Tender-
582763457
local means for opening and closing the circuit breaker,
local means for manually discharging the springs.
It shall be possible to add, on site, a motor mechanism for electrical charging of the operating mechanism as
well as the necessary accessories.
5.10 LV cabinet
The LV cabinet shall be included in the overall volume of the cubicle. It shall be designed to house the
various LV elements required for the operation of the motor mechanism and auxiliary equipment.
For specific needs, it shall be possible to enlarge or extend the LV box by adding an enclosure with a door to
the top of the cubicle. The overall height of the cubicles shall not exceed 2225 mm.
In all cases, these volumes shall be accessible with the cables and busbars live, without isolating the entire
switchboard. LV cabinet not satisfying these criteria will not be accepted.
5.11 Current transformers
The current transformers shall have the same short-time withstand current and rated voltage as the
switchgear.
It shall be made of cast epoxy resin and must be labelled individually.
The manufacturer shall be in a position to provide type-test reports certified by an approved laboratory
affiliated with international organisations.
Current transformers not satisfying these criteria will not be accepted.
5.12 Low Power Current transformers (LPCT)
The LPCT is a magnetic sensor in which provides a voltage output that represents the primary current, and
shall meet the characteristic of switchgear.
It shall be in accordance to IEC 60044-8, and shall have two type of application in which medium voltage
LPCT that shall be made of cast epoxy resin protection, and low voltage LPCT that shall be made of plastic
protection. And, both must be labeled individually.
It shall be easily installed, and shall be direct connection (plugging) to protection relay.
LPCT not satisfying these criteria will not be accepted.
5.13 Voltage transformers
The voltage transformers shall be made of cast epoxy resin and must be labeled individually.
Depending on the needs, they shall be of the phase-to-phase or phase-to-earth type. They shall be protected
by MV fuses or by circuit breakers on the power circuit.
The manufacturer shall be in a position to provide type-test reports certified by an approved laboratory
affiliated with international organisations.
Voltage transformers not satisfying these criteria will not be accepted.
5.14 LV auxiliaries
Auxiliary equipment shall satisfy section 5.4 of IEC 62 271-200 recommendations.
The LV cables shall be class 2 type with a 2000 V insulation level.
Last update : 2017-05-08
-9-
Specification for Tender-
582763457
They shall be marked at each end for easy verification during maintenance or servicing work.
The cable cross-sections shall not be less than 2.5 sqmm for circuits carrying high currents, or 1 sqmm for
other circuits.
5.15 Control and monitoring
All the relays, instruments and meters shall be incorporated in the LV box located at the top of the cubicle.
The relays shall be of the “integrated unit” type, meeting all protection and automatic control needs.
They shall comply with IEC 60801.4 and 50263 recommendations concerning electromagnetic
compatibility.
If necessary, they shall be able to communicate:
- using standardised protocols,
- adapting to a wide range of power supply voltages,
- with the possibility of being disconnected while live without any danger to installation,
- storing the information in memory in the event of an auxiliary power failure.
The manufacturer shall provide proof that he has already supplied equipment of the same type and same
make and that this equipment has been in operation for at least three years.
5.16 Voltage indicators and phase comparators
Function shall be able to be equipped with a voltage indicator box on the front of the device to indicate
whether or not there is voltage in the cables. The capacitive dividers will supply low voltage power to the
lamps.
Three inlets can be used to check the synchronization of phases.
This device shall be in compliance with IEC 61958 standard.
5.17 Fault Passage Indicators
Load break switch function shall be equipped with a fault passage indicator (FPI), in order to detect and
localise easily the faulty part of the network.
The latter FPI shall segregate the short circuit and earth faults, shall indicate permanently the phase-perphase load currents, and shall easily actuate a remote indication lamp.
The FPI fault detection core function shall be self-powered without help external power supply or built-in
batteries.
5.18 Safety of people
Any accidental overpressure due to internal arc in one of three compartments of the functions shall be resist,
and gas shall be exhaust to the rear of the switchboard away from the operator. Manufacturer shall provide
type test report to prove compliance with IEC 62271-200 Annex A for two different Internal Arc
performance;
IAC: A-FL at 12.5kA/1s with downstream exhaust,
And,
IAC: A-FLR at 16kA/1s with downstream, and upstream exhausts.
Last update : 2017-05-08
- 10 -
Specification for Tender-
582763457
5.19 Automatic Transfer System (ATS)
ATS switchgear shall give automatic control and management of sources in the medium voltage.
The minimum time to switch from one source to second source shall be between (minimum) 0.34s to 2.24s
that would be adjustable.
Switchgear shall be equipped with mechanical and electrical interlacing to avoid any wrong operation.
Switchgear shall guarantee parallels operation by mechanical and electrical synchronization.
6. Type tests and routine tests
Depending on switchboard, type-test certificates may be required for the equipment, including the switches
and the circuit breakers.
- impulse dielectric tests,
- power frequency dielectric tests,
- temperature-rise tests,
- short-time withstand current tests,
- mechanical operating tests,
- verification of the degree of protection,
- internal arc withstand
In addition, for the switches and circuit breakers, the rated making and breaking capacities shall be
substantiated by a test report.
For the earthing switch, the making capacity, the short-time withstand current and the corresponding peak
value shall be substantiated by a test report.
The routine tests carried out by the manufacturer shall be substantiated by a test report signed by the
manufacturer's quality control department.
The report shall cover the following aspects:
- conformity with drawings and diagrams,
- power frequency tests,
- manual operating mechanism tests,
- functional tests of LV auxiliaries and relays.
7. Quality
If requested by the client, the supplier shall provide proof of application of a quality procedure complying
with standards. This means:
- use of a quality manual approved and signed by a management representative,
- regular updating of this manual so that it reflects the most recent applicable quality control procedures,
- ISO 9002; 9001 certification and also ISO 14001.
Last update : 2017-05-08
- 11 -