Download 4. Electrical characteristics

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Electric power system wikipedia , lookup

Current source wikipedia , lookup

Ground (electricity) wikipedia , lookup

Ohm's law wikipedia , lookup

Decibel wikipedia , lookup

Coilgun wikipedia , lookup

Power inverter wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Islanding wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power engineering wikipedia , lookup

Electrical ballast wikipedia , lookup

Integrating ADC wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Oscilloscope history wikipedia , lookup

Resonant inductive coupling wikipedia , lookup

Three-phase electric power wikipedia , lookup

History of electric power transmission wikipedia , lookup

Metadyne wikipedia , lookup

Electrical substation wikipedia , lookup

Power MOSFET wikipedia , lookup

Voltage regulator wikipedia , lookup

Power electronics wikipedia , lookup

Opto-isolator wikipedia , lookup

Rectifier wikipedia , lookup

Capacitor discharge ignition wikipedia , lookup

Surge protector wikipedia , lookup

Stray voltage wikipedia , lookup

Buck converter wikipedia , lookup

Alternating current wikipedia , lookup

Voltage optimisation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Capacitor wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
Specification for Tender
582760314
S
General Specification for Automatic
Capacitor Bank with Detuning Reactors
for Electrical Networks up to 12KV
General presentation of CP53 SAH capacitor bank
Standards
Technical characteristics
Electrical characteristics
Operating conditions
Factory tests
Documents supplied in case of an order
Last update : 2017-05-06
-1-
Specification for Tender
582760314
Table of contents:
1. General presentation ……………………………………………………………….................
p. 3
2. Standards……………………………………………………………………………………….
p. 3
3. Technical characteristics ……………………………………………………………..............
p. 3
4. Electrical characteristics…………………………………………………………………........
p. 4
4.1 Acceptable overcurrent and overvoltage.....................................................................................
p. 4
4.2 Design voltage, design power and marking.................................................................................
p. 4
4.3 Composition.................................................................................................................................
p. 5
4.4 General layout and single line diagram........................................................................................
p. 5
4.5 Enclosures....................................................................................................................................
p. 5
4.6 Capacitor units..............................................................................................................................
p. 5
4.7 Contactor......................................................................................................................................
p. 6
4.8 Reactors........................................................................................................................................
p. 6
4.9 Connections................................................................................................................................... p. 6
4.10 Low voltage wiring...................................................................................................................... p. 6
4.11 Quick discharge coils (optional).................................................................................................. p. 6
4.12 Control and protection box (optional)......................................................................................... p. 6
4.13 Auxiliary voltages........................................................................................................................ p. 7
5. Operating conditions..................................................................................................................... p. 7
5.1 Internal fault protection.................................................................................................................. p. 7
5.2 Additional protections................................................................................................................... p. 7
6. Factory tests................................................................................................................................... p. 8
6.1 units : For PROPIVAR capacitor units .......................................................................................
p. 8
6.2 For CP253 SAH capacitor banks ................................................................................................. p. 8
7. Documents....................................................................................................................................... p. 8
Last update : 2017-05-06
-2-
Specification for Tender
582760314
1. General presentation
CP 253 SAH is a range of MV capacitor banks designed to be used in electrical networks up to 12kV. The
capacitor bank is made of unpainted aluminium or galvanised steel frame and panels, which is equipped with
PROPIVAR capacitors, SF6 contactor, HRC fuses and detuning reactors.
The bank is arranged in delta connection and the HRC fuses insure the protection against capacitor internal
fault.
Several capacitor stages are controlled by a power factor relay to make an automatic power factor correction
system.
2. Standards
The CP 253 SAH equipment is designed, manufactured, and tested according to the relevant IEC
recommendations.
- High voltage capacitors
IEC 60871-1 & 2, BS 1650, VDE 0560, C22-2 N° 190-M1985,
- High voltage contactors
IEC 420, IEC 470
- Reactors
IEC 289
- HRC Fuses
IEC 282.1, IEC 787
- Relays
IEC 255
3. Technical characteristics
CP 253 SAH capacitor bank is made of unpainted aluminium or galvanised steel frames and panels.
It is designed for the following installation conditions:
- indoor installation,
- altitude less than 1000m,
- average daily ambient temperature of between -25°C and +35°C, and a maximum of 40°C.
The protection degree of the enclosure is IP 23.
Available options for the enclosure:
- Door with lock for indoor type enclosure,
- Outdoor type enclosure,
- Door with lock for outdoor type enclosure, (to be used with outdoor type cubicle option).
Last update : 2017-05-06
-3-
Specification for Tender
582760314
4. Electrical characteristics
CP 253 SAH capacitor bank ranges are available for voltage up to 12kV, for 50Hz or 60Hz network.
According to network rated voltage, the insulation level of equipment is as follows:
Rated voltage (Vdim)
(V)
Insulation level
(kV)
4600
7100
12000
7,2
7,2
12
Power freq.
voltage withstand
(kVrms)
20
20
28
Impulse voltage
withstand (kV
peak)
60
60
75
The tolerance on the rated power of the capacitor bank is : 0/+10%,
Capacitance variation according to temperature is : -3,5.10-4/°C.
4.1 Acceptable overcurrent and overvoltage
CP 253 SAH capacitor banks are designed for:
- 1,10 x Un overvoltage - 12 hours per day,
- 1,15 x Un power frequency overvoltage - 30 minutes per day,
- Permanent overcurrent : 1,3 x In.
4.2 Design voltage, design power and marking
According to IEC 60871 recommendations, capacitor units or capacitor banks nameplates shall indicate the
maximum power and voltage for which it is designed (Qdim & Vdim).
Our capacitor units and capacitor banks have nameplates showing these design power and design voltage
(Qdim and Vdim). Operating values can be equal or lower than these values (Qn and Vn).
Last update : 2017-05-06
-4-
Specification for Tender
582760314
The documents supplied with our medium voltage products (price lists, order forms, catalogues, …) provide
reactive power values for the most common network voltages. If the required voltage does not appear in the
tables, it is possible to make a calculation using the formulae :
Qn = (Vn/Vdim)² x Qdim
4.3 Composition
Each stage of CP 253 SAH capacitor bank includes the following components:
4.3.1 Basic components :
- Unpainted aluminium or galvanised steel cubicle, IP23 for indoor installation,
PROPIVAR capacitor units, (1, 2 or 3 units per stage, depending on the rated power of the bank)
- One contactor,
- One three-phase detuning reactor,
- Three HRC fuses.
4.3.2 The following items are available as options :
- Set of two quick discharge coils,
- Control and protection box.
4.4 General layout and single line diagram
4.5 Enclosures
The capacitor banks enclosure is made of unpainted aluminium or galvanised steel frames and panels. The
stages are designed to include up to 3 capacitor units in delta connection.
There are five types of enclosures, for 1 up to 5 capacitor stages : CP253-1 SAH, CP253-2 SAH, CP253-3
SAH, CP253-4 SAH and CP253-5 SAH.
4.6 Capacitor units
The PROPIVAR capacitor units used in CP253 SAH banks have the following characteristics:
Last update : 2017-05-06
-5-
Specification for Tender
582760314
- All film technology,
- Filled with biodegradable dielectric fluid,
- Three-phase, delta connected,
- Fitted with three epoxy resin bushings,
- Fitted with internal discharge resistors (75V / 10min).
According to IEC 60871 standard requirements, capacitor units include internal discharge resistors so that
the residual voltage is less than 75V within 10 minutes after disconnection.
4.7 Contactor
There are two types of ROLLARC contactors, notably:
- the R400 with magnetic holding, and
- the R400D which is mechanically latched.
In CP253 SAH banks we use the R400 type.
The high breaking capacity of the Rollarc contactor (10kA) provides perfect co-ordination when used in
conjunction with HV fuses (with ratings of up to 250A).
4.8 Reactors
The reactors used are three-phase, dry type, with iron core and natural air cooling. The rated current is equal
or higher than 1,43 times the capacitor bank nominal current.
The inductance value is calculated so that the L-C tuning frequency is 4,3 times the fundamental frequency
value (215Hz for 50Hz network, or 258Hz for 60Hz network).
This "detuning" frequency avoid resonance risk and attenuates effect of 5th and higher harmonics.
In addition, they attenuate tremendously the peak inrush current due to capacitor bank switching (peak value
remains much lower than 100 times the nominal current of the capacitor bank, as per IEC recommendation).
4.9 Connections
The connection supports are made of porcelain or epoxy resin. Connections are of bare copper bars.
4.10 Low voltage wiring
Low voltage wiring is insulated with black PVC, 1000 V grade, with the following cross-sections:
- 2,5 sq. mm for currents circuits,
- 1,5 sq. mm for voltage circuits.
Each extremity of wire is marked using the independent marking system.
4.11 Quick discharge coils (optional)
Quick discharge coils allow a very fast discharge time (less than 10 s).
Caution : In any case (without or with quick discharge coils), a time delay relay must be used to avoid
connection of the capacitor bank within less than 5 minutes after its disconnection, either due to automatic
control, protection tripping, voltage outage, …
4.12 Control and protection box (optional)
There are five models of control and protection boxes available, for 1 up to 5 capacitor stages.
These control and protection boxes are designed for indoor use only. They include the following devices :
- One Varlogic power factor controller,
Last update : 2017-05-06
-6-
Specification for Tender
582760314
- Signaling lamps :
> Voltage "on",
> For each stage : Stage "On", Stage "Off", Melted fuse.
- Optional : a local manual control switch. This switch has three positions :
> "Auto" : the stages are controlled by the power factor relay,
> "Manu" : the stages are manually controlled by a 2 position switch, (1 per stage),
> "0" : the stages remain off all the time (no automatic nor manual operation permitted).
4.13 Auxiliary voltages
Here are the voltages which can be used for CP 253 SAH capacitor banks:
Control and signalling circuits (contactor coils, lamps, auxiliary relays):
- ac : 110Vac, 220/230Vac.
- dc : 48Vdc, 110Vdc, 125Vdc, 220Vdc.
Power factor controller reference voltage :
- ac : 110Vac, 220/240Vac, 380/415Vac.
5. Operating conditions
5.1 Internal fault protection
PROPIVAR capacitors have to be protected according to Rectiphase instructions.
Only HRC fuses types and ratings recommended by Rectiphase can be used for capacitor protection.
5.2 Additional protections
To provide a suitable protection level for the equipment, the capacitor bank feeder must include the
following additional protection devices :
- Short-circuit protection : recommended setting values : 3 x In / 0,1s,
- Overload protection : recommended setting values : 1,4 x In / 10s,
Important note: The feeder circuit-breaker shall be suitable for capacitor current switching.
Last update : 2017-05-06
-7-
Specification for Tender
582760314
6. Factory tests
Each CP 253 SAH capacitor bank manufactured by Rectiphase must pass routine testing before delivery.
The factory routine tests are performed according to IEC relevant recommendations and include the
following:
6.1 For PROPIVAR capacitor units :
-
capacitance measurement,
loss angle measurement (tg ),
sealing test,
internal discharge resistor value checking,
voltage test between terminals,
voltage test between terminals and container.
6.2 For CP253 SAH capacitor banks
-
phase to phase capacitance measurement,
insulation measurement,
conformity checking,
functional test (off-load operation),
7. Documents
The following documents are part of Rectiphase supply :
- three sets of routine test certificates (french / english)
- three sets of drawings and diagrams (french / english or french / spanish),
- one instruction manual (french / english / spanish)
Last update : 2017-05-06