* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download Transformer Basics
Electrical substation wikipedia , lookup
Resistive opto-isolator wikipedia , lookup
Current source wikipedia , lookup
Ground (electricity) wikipedia , lookup
Electromagnetic compatibility wikipedia , lookup
Buck converter wikipedia , lookup
Opto-isolator wikipedia , lookup
Stray voltage wikipedia , lookup
History of electric power transmission wikipedia , lookup
Voltage optimisation wikipedia , lookup
Earthing system wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Mains electricity wikipedia , lookup
Rectiverter wikipedia , lookup
Three-phase electric power wikipedia , lookup
Automatic test equipment wikipedia , lookup
Alternating current wikipedia , lookup
Current Transformer Testing Outline Current Transformer CT Test Setup Tap, Ratio and Polarity Test Megger Test Excitation Test Testing CT’s in a Circuit Breaker Testing CT’s in a Three Phase Delta-Wye Transformer Digital Current-transformer Testers (EZCT-10) Current Transformer Transformer is a transformer, no matter whether it is a voltage or current transformer. A Current Transformer circuit must be grounded; however, it should only be grounded in one location. A Current Transformer circuit secondary must never be opened when load is flowing in the Primary. CT TEST SETUP Tap, Ratio and Polarity Test This test is to verify the correct CT polarity, full CT ratio, and taps. It also verifies taps are correctly brought out to the CT terminal blocks. Voltage applied may be determined by the CT ratio per the next page chart. Reduce the voltage to zero before switching Off the AC source to prevent magnetizing of the CT core. Megger Test This test is to verify that adequate insulation exists between the CT winding and ground. With one Megger lead connected to ground, touch the other Megger lead to one CT tap. The CT should typically read 75 mega ohms or more. If the readings are not within this limit, then check the wires, terminal blocks, or CTs for moisture, condensation, or anything else that could contribute to the low resistance readings Note that the 75 mega ohms guideline is only applicable for testing individual CT’s, not parallel CT circuits or long cable runs connected to the CT. Excitation Test • This test is to verify that the CT does not have any shorted secondary turns and to compare the measured exciting current against the manufacturer’s CT test curves. • The best test method is to determine what voltage is required to approach the saturation point (knee of the curve) of the CT for the full winding and apply a voltage slightly below this value and read the current. • Measured currents greater than those shown on the CT curves would indicate trouble within the CT. • If the CT curves are not available and the current increases quickly with small increases in voltage there is trouble within the CT. Excitation Test • If the voltage source available for testing is not high enough to approach the saturation point, the test can be run with a lower voltage and or fewer secondary turns. • The lowest voltage that we would want to use would be 0.50 volts per turn connected from X1 to X5. • You may also use the minimum number of turns calculation as shown below to determine test values. Excitation Test Testing CT’s in a Circuit Breaker Testing CT’s in a Single Phase Transformer Testing CT’s in a Three Phase Delta-Wye Transformer With all bushings, not being tested, shorted together and connected to non-polarity Digital Current-transformer Testers (EZCT-10) This test set can perform the current transformer (CT) excitation, CT current-ratio, and winding polarity tests. EZCT Cable Connections Connection to CT’s on Y Transformer Connection to CT’s on Delta Transformer Typical EZCT Connection to Multiple CT’s