Download Capacitor Bank Switching with Vacuum Circuit Breakers : pdf

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Regenerative circuit wikipedia , lookup

Standing wave ratio wikipedia , lookup

Radio transmitter design wikipedia , lookup

Test probe wikipedia , lookup

Multimeter wikipedia , lookup

CMOS wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Valve RF amplifier wikipedia , lookup

TRIAC wikipedia , lookup

RLC circuit wikipedia , lookup

Operational amplifier wikipedia , lookup

Josephson voltage standard wikipedia , lookup

Integrating ADC wikipedia , lookup

Ohm's law wikipedia , lookup

Schmitt trigger wikipedia , lookup

Current source wikipedia , lookup

Power electronics wikipedia , lookup

Power MOSFET wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Current mirror wikipedia , lookup

Voltage regulator wikipedia , lookup

Opto-isolator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Surge protector wikipedia , lookup

Rectiverter wikipedia , lookup

Transcript
Technical collection
Capacitor Bank Switching with
Vacuum Circuit Breakers
2008 - Conferences publications
H. Schellekens
Schneider Electric 2008 - Conferences publications
2008 China International Conference on Electricity Distribution (CICED 2008)
1
Capacitor Bank Switching with Vacuum Circuit Breakers
Hans Schellekens
Schneider Electric, Power SBU, Medium Voltage Development, Usine 38V, ZAC Champ Saint-Ange, Varces, France
Abstract: After interruption of a capacitive current sometimes Non Sustained Disruptive Discharges (NSDDs) are observed when
using vacuum circuit breakers. According to network calculations, NSDDs generate significant over-voltage on the terminal of the
capacitor bank to ground and across the circuit breaker (CB) terminals. In a full scale experiment at 12kV on an 8Mvar capacitor
bank artificial NSDDs are produced using a Triggered Vacuum Gap. The over-voltage depends on the momentary voltage
difference across the breaker and, hence, varies with the phase angle. The over-voltage on the terminal of the capacitor bank to
ground varies from 1.5 to 4.2 pu, and to maximum 5.2 pu. across the CB terminals. The effectiveness of surge arrestors on the
limitation of the over-voltages is measured. The over-voltages are limited to 2.2 pu. on the terminals of the capacitor bank to
ground and 3.2 pu. across the CB terminals. A single surge arrestor on the neutral point of the capacitor bank yields the same level
of protection and, therefore, is a cost effective alternative. An application guide for switchgear and arrestors is presented.
1. INTRODUCTION
which appear as NSDDs1. Breakdown frequencies of typically
3/1000 where found under the experimental conditions
The capacitive current switching duty is characterised
studied. The probability of breakdown depends on the
by frequent, day to day or hour by hour, switching of low to
dielectric conception or contact stroke of the vacuum
moderate currents in industrial or public networks, and by a
interrupter. So for the same voltage rating different designs
low rate of rise of recovery voltage. Modern circuit breakers
lead to different probabilities of occurrence of NSDD. Fig. 1
(CB’s) which claim a long mechanical but also electrical life
shows the experimentally found relation between dielectric
without maintenance seem to be best adapted to this
conception, based on contact gap, and the probability of a
switching duty [1,2,3]. Yet the behaviour of vacuum CB’s is
NSDD during an operation. It shows that a minimum contact
rather different from that of gas CB’s.
distance of 16 mm is necessary to reduce this probability
Today, the circuit breaker envisioned for capacitor bank
below 1/500.
switching is either a vacuum or SF6 circuit breaker or a
The overvoltage produced by a NSDD differs notably
vacuum or SF6 contactor. All these devices are known for
from the overvoltage produced by a restrike. A restrike can
their long service life. The circuit breaker offers a protection
generate an overvoltage of 3 pu. between the terminals of
against short circuit currents with an electrical life between
the capacitor bank, whereas a NSDD causes a sudden voltage
10.000 and 30.000 operations at nominal current. Contactors
shift of the neutral capacitor bank voltage, which leaves the
offer an electrical life up to 1 million operations depending on
voltage across the capacitor unchanged, but creates an
load conditions. SF6 CB’s, in the past referred to as “restrike
overvoltage between 1.5 and 5 pu. on the terminal of
free” breakers, are according to the new IEC62271-100 class
capacitor bank to ground and between 2.5 and 6 pu. across the
C2 breakers with proven “very low restrike probability” [4].
CB terminals. Due to this high overvoltage a second NSDD in
Field experience indicates that the restrike probability even
the adjacent phases becomes more likely.
When
for the electrically very stressed 36 kV networks is lower than
1/50.000.
For vacuum CB’s, the physical processes during the
two
NSDDs
occur
simultaneously,
the
phenomenon turns into a restrike. Typically, a vacuum CB
with a contact gap of about 16 mm has a probability of about
capacitive switching duty have been studied by [5]. They
found that the pre-ignition at contact closing and the
subsequent inrush current heavily eroded the contacts leading
to detached particles. These particles cause late breakdowns
1
NSDD or non-sustained disruptive discharge [7] is a disruptive
discharge associated with current interruption that does not result in
the resumption of power frequency current or, in the case of
capacitive current interruption does not result in current in the main
load circuit.
Schneider Electric 2008 - Conferences publications
2008 China International Conference on Electricity Distribution (CICED 2008))
2
1/500 for producing a NSDD and belongs to the class C2 with
The source side of the network is represented by:
proven “very low restrike probability”.
-
a generator with a driving voltage of U
-
a short circuit impedance of value Ls
-
a TRV network as defined by IEC for short circuit
conditions
-
a capacitor Cp to account for parallel feeders
The load side of the network is represented by:
-
a 8Mvar capacitor bank with floating neutral
-
single phase cables between CB and the bank.
The load and the source side of the network are
connected to each other by the CB. The CB is treated as an
Fig.1 : Experimentally found dependence between probability of a
NSDD
and nominal contact stroke of vacuum interrupter.
Due to the rare occurrence and the random nature of the
phenomenon, the relation between NSDD and overvoltage is
not evident. Therefore in this paper this question is addressed
in section II using a numerical network simulation. By this
the worst case overvoltage for different voltage levels is
determined. Then in section III an experiment designed to
verify the simulation results is shown. Here the NSDD is
created artificially, which permits to measure the influence of
phase angle and network parameters. A good understanding of
the origin of the overvoltage enables the definition of
protective measures adapted to the switchgear and capacitor
bank. In section IV protection schemes based on surge
arrestors are tested and compared on their effectiveness.
Finally in section V the results are discussed and an
application guideline is presented for the choice of switchgear
and arrestor.
ideal breaker with a NSDD some time after current
interruption. The moment of NSDD has been chosen in order
to create the worst possible case. The CB is allowed to
recover immediately at the first occurring current zero. At a
NSDD, on the R phase for the case illustrated by Fig. 2, the
voltage across the breaker moves as a travelling wave through
the line impedance towards the capacitor bank. The capacitor
bank being a high frequency short circuit allows the wave to
pass on to the neutral point of the bank. At the neutral point
the wave splits itself and continues its propagation in the
neighbouring phases towards the healthy CB poles. These
healthy poles are in fact open terminals for the incoming
wave causing it to reflect by doubling the voltage. After
reflection the wave travels back to the failing CB pole. Here it
creates a current zero passage on which the breaker can
interrupt. The frequency of this current is typically of the
order of 100 kHz for cable connected capacitor banks. Fig. 3
shows the voltage swing on the bank terminals with respect to
ground. Note that
2. ORIGIN OF OVERVOLTAGES
2.1
Numerical simulation
The simplified electrical circuit, Fig. 2, will be used
here to simulate the phenomena associated with a NSDD; the
NSDD is simulated as a temporary loss of dielectric strength
in the vacuum interrupter of a vacuum CB.
Fig. 3 : The voltage on all 3 capacitor bank terminals during current
interruption (at 0.1s) followed by a NSDD (at 0.13s) in R phase in a
12kV network.
-
For each of the three bank terminals the voltage
jumps to a new value, which means that the neutral point of
Fig. 2 : Electric circuit used to calculate overvoltage on capacitor
bank during a NSDD. TVG see section III.
the bank attains also a different value.
-
The voltage difference between terminals remains
Schneider Electric 2008 - Conferences publications
2008 China International Conference on Electricity Distribution (CICED 2008)
3
unchanged. The capacitors themselves are not stressed by the
frequency withstand voltage. For the CB the overvoltage
breakdown.
comes very close to the rated BIL voltage for 36 kV class
-
The maximum terminal voltage to earth attains a
high value (see table I). This is a dc voltage, so all parts of the
installation are stressed during a long period.
-
The CB is stressed by the composed voltage of
network voltage and capacitor bank terminal voltage.
-
networks.
2. EXPERIMENTAL VERIFICATION
3.1
Test procedure
The objective was to create in a reproducible way
The capacity of the bank itself is of no significance
for the phenomenon.
NSDD type breakdowns in a capacitive current interruption
test. This allowed to minimize the number of tests to obtain
the desired NSDD. NSDDs do not occur frequently and are
Table 1:
Compilation of voltages associated with
therefore difficult to reproduce. A triggered vacuum gap
capacitor bank switching for nominal network voltages
(TVG) parallel to the R-phase of the VCB is used to create an
artificial NSDD in a controllable way. A separate experiment
Um
US
U C-bank
UVCB
BIL
Power
frequency
kVrms
kVrms
kV
kV
kV
kVrms
12
10
47
55
75
28
currents of, for instance, 300A at 100kHz and 10 A at 900
confirmed that the TVG was able to interrupt high frequency
24
20
93
110
125
50
kHz at the first current zero. Hence, the duration of the
36
30
140
164
170
70
“artificial” NSDD is determined by the circuit topology and
only one half cycle of high frequency current will pass
2.2. Identification of zones at risk
through the TVG. Numerical modelling showed that this will
In table I the maximum possible overvoltage produced
by a NSDD is shown for three commonly used classes of
network voltages. For each voltage class column 2 gives Us
the nominal network voltage. Column 3 gives the maximum
overvoltage on the capacitor bank terminal to ground and
column 4 the maximum overvoltage across the CB terminals.
For reference the BIL and power frequency withstand
voltages of the equipment are given. For all three voltage
classes both overvoltages exceed the peak value of the power
Fig. 4 :
3.2
lead to the highest possible overvoltage. Using the TVG
provided a measurement window with high frequency
sampling centred at the time of breakdown allowing precise
measurements to be made.
Full scale tests are performed in a direct test circuit fed
by a generator 2000 MVA at 12 kV with short circuit current
limited at 14 kA. The capacitive load was a 8 Mvar capacitor
bank; nominal current of 430 A. The detailed characteristics
of the test circuit are given in Fig. 4 and table II.
3-phase test circuit with generator and 8 Mvar capacitor bank.
Test results
phase R at a maximum voltage difference across the CB. At
Fig. 5a shows an oscillogram of a normal interruption
this moment the voltages on all C-bank terminals change
with NSDD. The first phase to interrupt, R, creates a dc
suddenly and settle to a new constant value. The highest
voltage on the capacitor bank terminal of 1.5 pu. Then 30
overvoltage is found in phase T. The instant of occurrence of
milliseconds after current interruption a NSDD is generated in
the NSDD was varied by firing the TVG at a predetermined
Schneider Electric 2008 - Conferences publications
2008 China International Conference on Electricity Distribution (CICED 2008))
4
moment to see the influence of the phase angle on the nature
the most severe one, the experiment was repeated by keeping
and the value of the over-voltage. The waveform of the
the first phase to clear in phase R and generating the NSDD in
overvoltage is a dc voltage and is the same for all tested phase
phase T. The highest overvoltage is now found in phase R.
angles.
The instant of occurrence of the NSDD was varied by firing
the TVG at a predetermined moment to see the influence of
the phase angle on the nature and the value of the
over-voltage. The waveform of the overvoltage is a dc voltage
and is the same for all tested phase angles. Fig. 6b shows the
measured voltage on the capacitor bank terminal in phase R to
ground after the NSDD in phase T. Before the NSDD the
voltage is about 1.5 pu. The voltage jump is between 0 and
2.5 pu. resulting into an over-voltage of maximum 4.0 pu.
The height of the overvoltage varies harmonically with the
phase angle.
Fig.5a: Normal interruption of
capacitive current followed by
NSDD in R phase after 30 ms.
Fig.5b: As Fig. 5a Surge arrestor
in phase T limits the overvoltage.
For each phase (R, S, T). Red : Source side voltage on CB.
Green : Load side voltage on CB and capacitor bank terminal.
Blue : Current through CB. Time scale: 1ms/div.
Fig. 6a shows the measured voltage on the capacitor
Fig. 6b : Variation of over-voltage in phase R expressed
bank terminal in phase T to ground after the NSDD in phase
in pu due to instant of occurrence (phase angle)
R. Before the NSDD the voltage is about 0.89 pu. The voltage
of the NSDD in 2nd phase T to interrupt.
jump is between 0.6 and 3.2 pu. leading to an over-voltage of
Note that the over-voltage is the addition of the original
maximum 4.1 pu. The height of the overvoltage varies
capacitor bank voltage after current interruption and a voltage
harmonically with the phase angle.
jump due to the NSDD. The amplitude of the voltage jump
depends on two factors :
●
the voltage across the breaker at the instant of
breakdown, which varies with time or phase angle, and which
is maximum 2.5 pu. (see Fig. 5a).
●
an amplitude multiplication K-factor (section IIIC)
The voltage difference at breakdown is transmitted
integrally to the neighbouring phases as predicted by the
numerical simulation. Except for a reduced amplitude factor
the behaviour found is identical to the simulation. Moreover,
the most severe overvoltage is produced by a NSDD in the
first phase to interrupt at the moment of the largest voltage
Fig. 6a : Variation of over-voltage in phase T expressed in pu
due to instant of occurrence (phase angle) of the
NSDD in 1st phase R to interrupt.
In order to investigate whether the above condition is
difference across the CB.
3.3
Influence of TRV circuit
The influence of the TRV circuit on the high frequency
behaviour of the breakdown has been studied with the
following circuits:
Schneider Electric 2008 - Conferences publications
2008 China International Conference on Electricity Distribution (CICED 2008)
TRV-1 : The standard TRV circuit composed of 2
branches see Fig. 2.
5
TRV generated by the driving voltage of the generator and the
TRV circuit. The load side voltage settles to a new dc voltage
TRV-2 : No TRV circuit; only stray capacitance between
Generator and CB.
level. Numerical simulation suggests voltage doubling with a
K-factor equal to 2. Therefore the reduced value of
K-immediate is attributed to damping of the high frequency
TABLE III :
Influence TRV circuit on peak
current at NSDD.
value of overvoltage
4. PROTECTION BY SURGE ARRESTORS
TRV-1
TRV-2
K-theoretical
2
2
K-Immediate
1.6
1.7
the capacitor bank against excessive overvoltages due to
K-Late
1.3
1.6
restrikes [6]. In such a case the overvoltage rise-time is of the
16.5µs
13.5µs
order of milliseconds. Yet in case of an NSDD the
150 kHz
28 kHz
28 A
6A
Voltage jump
Damping time
Frequency NSDD current
Current
Results are shown in table III. The voltage jump after
breakdown can be characterised by :
●
A peak voltage immediately after the NSDD: with K
factor : K-immediate.
●
A dc voltage after a transition period: K-late. The
transition is characterised by a time constant here called
“damping time”.
●
The frequency of the NSDD current.
Fig. 7 shows an oscillogram of the voltage on both sides of
Arrestors are commonly proposed as means to protect
overvoltage rise-time is only several microseconds. In order
to verify the effectiveness of the surge arrestor the following
two cases are investigated.
4.1
Surge arrestors on all three phases to ground
Test conditions are similar as under section IIIA but
with surge arrestors on the load side of the CB to ground. On
initiation of a NSDD in phase R, the highest overvoltage of
2.2 pu. was in phase T due to immediate limitation of the
overvoltage by the surge arrestor in phase T; the associated
oscillogram is shown in Fig. 5b. A significant current flows
through the surge arrestor: 890 A during 1 ms; representing an
energy of about 8 kJoule. This current is determined by :
the CB during the NSDD for TRV-2 circuit. During the
1. The series impedance of two branches R and T of the
NSDD, between 12 and 30 µsec, both voltages are identical as
capacitor bank and the series inductance of phase R and the
an arc in the CB allows for current to pass from the source
resistance to ground of the generator.
2. The voltage difference across the capacitor prior to
side to the load side. Due to the small TRV capacitance, the
source side voltage collapses at 12 µsec and joins the load
breakdown minus the voltage of the arrestor.
side voltage. During the current flow the voltage makes an
Notice, that during the limitation of an overvoltage due
oscillation around the driving voltage (the source voltage
to a NSDD only one surge arrestor is conductive and
before the NSDD). When this reaches a new maximum at 30
dissipates the energy. Due to the random nature of current
µsec the current passes through zero and interruption takes
interruption the maximum overvoltage can be in any of the
place. After interruption, the source voltage is subject to the
three phases. Therefore, surge arrestors have to be installed on
all three phases.
4.2
Surge arrestor on neutral to ground
Test conditions are similar as under section IIIA but
with a single surge arrestor on the neutral point of the
capacitor bank. If a NSDD was initiated in phase R, the
highest overvoltage of 2.1 pu. was in phase T due to
immediate limitation of the overvoltage by the surge arrestor.
A significant current flows through the surge arrestor: 575 A
during 2.5 ms; representing an energy of about 13 kJoule.
This current is determined by
Fig. 7 Zoom at voltage behaviour at NSDD in R phase with TRV-2.
Green (1) : Load side voltage on CB and capacitor bank terminal.
Red (2) : Source side voltage on CB.
Time scale 10µs/div.
1. The series impedance of one branch of the capacitor
bank, the inductance of one phase of the circuit and the
resistance to ground of the generator.
Schneider Electric 2008 - Conferences publications
2008 China International Conference on Electricity Distribution (CICED 2008))
6
2. The voltage difference across the capacitor prior to
severe conditions determine the continuous operating voltage
of the surge arrestor.
breakdown minus the voltage of the arrestor.
For arrestors on the circuit-breaker
The energy dissipated in the arrestor is higher than
terminals the nominal voltage can reach 1.5*Un/√3; the
under IV-A due to the lower COV of the arrestor. Yet here the
resulting level of protection is 3.3 pu. For a single arrestor on
arrestor will function regardless the phase in which the
the neutral of the bank the continuous voltage can reach
maximum overvoltage will occur. This limits the number of
Un/√3; the resulting level of protection is 3.2 pu. During
surge arrestors to install to one.
interruption of the capacitive current the voltage of the neutral
can increase slightly more. Yet, the surge arrestor is capable
Table IV :
Choice of continuous operating voltage
of the arrestor and the resulting overvoltage protection level
depends on network operation conditions and arrestor location.
Arrestor
location
Continuous
Operating
Voltage
Overvoltage
protection
level [pu] or
Un√(2/3)
networks with highohmic insulated neutral
system and automatic
earth fault clearing
CB
terminals
Un/ 3
2.2
Neutral
point
0.5*Un/ 3
2.1
networks with earth
fault compensation or
with a high-ohmic
insulated neutral system
CB
terminals
1.5*Un/ 3
3.3
Neutral
point
1*Un/ 3
3.2
of dealing with this temporary overvoltage under this rare
abnormal network condition.
5. DISCUSSION
The main results of this study are summarized in table V.
An important difference is found between the numerically and
experimentally obtained overvoltage values. The measured
overvoltage on the bank terminal to ground is significantly
lower than calculated. This is due to natural damping of the
high frequency phenomena by dissipative elements in the
circuit and by the very small capacitance on the source side
due to the absence of parallel feeders. The peak over-voltage
Choice of the surge arrestor
has a limited duration of about 10µs. Surge arrestors
The surge arrestor limits effectively the overvoltage by
effectively limit these overvoltages to values as low as 2.2 pu
suppressing the high frequency (150 kHz) peak overvoltage.
between terminal and ground. The capacitors themselves are
The absolute value of the remaining overvoltage depends
stressed neither by the NSDD nor by the action of the surge
though on the choice of the surge arrestor. The voltage
arrestors during limitation, as the discharge current is a single
limitation is effective at a level of 3.1 times the rated
phase current flowing towards ground.
4.3
continuous operating voltage of the surge arrestor. The choice
TABLE V :
Over-voltages in capacitor bank switching
of the rated voltage of the surge arrestor must take into
Situation
account abnormal circuit conditions as well. In table IV two
common situations are compared.
●
For networks with high-ohmic insulated neutral
Capacitor
bank terminal
Across CB
1
Normal Interruption
1.5 pu
2.5 pu
2
NSDD :
Predicted
6.0 pu
7.0 pu
3a
NSDD (K-Late = 1.3)
4.2 pu
5.2 pu
3b
NSDD (K-Immediate = 1.7)
5.2 pu
6.2 pu
of each phase is fixed at Un/√3 and the neutral point of the
4
Surge arrestors on all terminals
2.2 pu
3.2 pu
capacitor bank has 0 (zero) voltage. The continuous operating
5
Surge arrestor on C-bank neutral
2.2 pu
3.2 pu
system and automatic earth fault clearing the nominal voltage
voltage of the surge arrestor can be chosen accordingly. The
surge arrestor with associated continuous operating voltage
In the introduction it was outlined that NSDDs are a
(COV) gives a protection of 2.2 pu. During a normal breaking
common phenomenon in vacuum interrupters and that the
operation the neutral point attains a peak voltage of
simultaneous occurrence of NSDDs in 2 phases give rise to a
0.5*Un√(2/3), which lasts until discharging of the capacitor
restrike. The frequency of occurrence of a NSDD is related to
bank; this corresponds to a COV of 0.5*Un/√3; the resulting
design parameters like the contact opening stroke. Hence it is
level of protection is 2.1 pu.
possible to design a vacuum CB according to the
For networks with earth fault compensation or with a
requirements of either “low restrike probability” class C1 or
high-ohmic insulated neutral system a possible persistent
“very low restrike probability” class C2 of [7]. For 24 kV
single phase earth failure increases the nominal voltage of the
Class C2 vacuum CBs with “very low restriking probability”
healthy phases a factor √3, and the voltage on the neutral
this leads to a nominal contact gap of 16 mm, see Fig. 1. For
point of the capacitor bank increases to 1 pu. These more
voltages of 36 kV and above [8] proposes to use two vacuum
●
Schneider Electric 2008 - Conferences publications
2008 China International Conference on Electricity Distribution (CICED 2008)
interrupters in series. Although these measures are effective
7
Protection against NSDD
from a normative point of view, they do not contribute to an
economically conclusive and reliable solution as shown by
Arrestor on CB terminals to ground
1 * Sk/ω
Arrestor on C-bank neutral to ground
2 * Sk/ω
the following numerical example. For instance, contactors
which allow for frequent operations have a small contact
opening stroke. Even with a NSDD frequency of only 1/500
they will produce over 2000 NSDDs in their entire lifespan.
Therefore, only the application of surge arrestors is an
I. CONCLUSION
effective solution to suppress overvoltages and eliminate any
This study focussed on the interaction of the vacuum
risk for equipment: capacitor bank, circuit breaker and switch
circuit breaker with a capacitor bank during switching
board. The application guide in table VI summarises this
operation. The occurrence of a NSDD leads to a shift of the
recommendation relating the choice of switchgear to the
voltage of the neutral point of the bank. Although the
application duty. If the CB is used only occasionally for
phenomenon in itself is rare, the over-voltages produced are
energizing and de-energizing the capacitor bank a vacuum CB
deterministic and depend on the recovery voltage of the phase
with class C1 or C2 can be used. Yet for daily operation of the
in which the NSDD occurs and on the moment of breakdown.
capacitor bank a protection by surge arrestor is recommended,
The experimental study shows that the overvoltage after
and in this case a class C1 rating is sufficient, as the
NSDD is limited to about 4.2 pu. on the capacitor bank
suppression of overvoltage during a NSDD reduces
terminals.
significantly the probability of a second simultaneous NSDD,
means to limit this overvoltage. As cost efficient solution it is
and hence the risk of a restrike. For more than daily operation
proposed to use a single surge arrestor on the neutral point of
a vacuum contactor with surge arrestor is an economical
the capacitor bank. Guidelines are presented to dimension
viable solution in series with a vacuum CB for protection.
these arrestors.
Table VI :
Surge arrestors are shown to be an effective
Application guide
REFERENCES
Capacitive switching duty
Protection and
Occasional operation
[1] T. Yokoyama, Y. Matsui, K. Ikemoto and M. Inoyama
Daily operation
Frequent
operation
Vacuum-C
B
Class C1 or C2
Class C1 +
Surge arrestors
—
Vacuum-C
ontactors
—
Surge arrestors
Surge
arrestors
“ Technique on Overvoltage Phenomenon Analysis for
Vacuum Switching Equipment ” by, Meiden Review
Series No. 78,1986
[2] Y. Sunada,N.Ito, S. Yanabu, H. Awaji, H. Okumura and Y.
Kanai, “ Research and Development on 13.8kV 100kA
When applying surge arrestors, special attention must
be given to the energy dissipation in the arrestor. It is
Vacuum
CB
with
Huge
capacity
and
Frequent
Operation ”, CIGRE, Paris, 1982
proposed to dimension the arrestor to be capable to carry out
[3] P. Huhse and E. Zielke, “ 3AF Vacuum CBs for Switching in
3 consecutive protective actions without cooling down.
Capacitor Banks ”, Siemens Power ENGENEERING III
Furthermore the dimensioning is related to the reactive power
of the capacitor bank, Sk. Guidelines are given by [6, 9] in the
case of restriking CBs, in which case the arrestor has to be
(1981) No 8-9
[4] D. Koch, “Control equipment for MV capacitor banks”,
ECT142, Schneider-Electric, Grenoble, 1992
dimensioned for an energy of 6*Sk/ω, where ω : angular
[5] T. Kamakawaji, T. Shioiri, T. Funahashi, Y. Satoh, E.
frequency of the network. Transposing this approach to a
Kaneko and I. Oshima, “ An Investigation into Major
protection against NSDD the guidelines as presented in table
Factors in Shunt Capacitor switching Performances By
VII dimension the energy dissipation capability of the arrestor.
Vacuum CBs With Copper Chromium Contacts ”, IEEE
Hence, for the protection against NSDDs the arrestor can be
Power Engeneering 1993 winter meeting Columbus
designed 3 to 6 times smaller.
OHIO
[6] L. Gebhardt, B. Richter, ”Surge arrestor application of
Table VII :
the requested energy dissipation
capability of the arrestor
MV-capacitor banks to mitigate problems of switching
restrikes”, paper 0639, 19th CIRED, 2007, Vienna.
[7] International Standard IEC 62271-1, 2008, “High Voltage
Schneider Electric 2008 - Conferences publications
2008 China International Conference on Electricity Distribution (CICED 2008))
8
Switchgear and Controlgear – Part 1: Common specifications ”
Eindhoven, The Netherlands, in 1983, with a specialization in
[8] E. Dullni, W. Shang, D. Gentsch,I. Kleberg and K.
plasma physics. He worked at the HOLEC Research
Niayesh, “ Switching of Capacitive Currents and the
Laboratory from 1978 to 1982 and at KEMA testing
Correlation of Restrike and Pre-ignition Behavior” , IEEE
laboratories from 1983 to 1985. From 1986 to 1993, he was
trans. on dielectrics and electrical insulation, vol. 13, n 1,
responsible for the development of vacuum interrupters and
pp. 65-71, 2006
vacuum circuit breakers at HOLEC. Since 1994, he is
[9] R. Rudolph and B. Richter, “Dimensioning, testing and
involved in the development of vacuum interrupters for
application of metal oxide surge arrestors in medium
Schneider
Electric
Medium
Voltage
SBU
(formerly
voltage networks”, open document ABB, Wettingen, 1999
Merlin-Gerin) at Grenoble in France. He has been active in
the Dutch Brazing Soc. as well as in the CIGRE Working
About the author
Hans Schellekens (54) received the Ph.D. degree in
technical engineering from the Technical University of
Group 13.01 from 1985 to 1993. Dr. Schellekens is a member
of the Current Zero Club.
E-mail of author: [email protected]