Download Series 700 A/VS Power Conditioner

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Scattering parameters wikipedia , lookup

Transformer wikipedia , lookup

Tube sound wikipedia , lookup

Current source wikipedia , lookup

Linear time-invariant theory wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Audio power wikipedia , lookup

Control system wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Islanding wikipedia , lookup

Stray voltage wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power engineering wikipedia , lookup

Electrical substation wikipedia , lookup

Flip-flop (electronics) wikipedia , lookup

History of electric power transmission wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Three-phase electric power wikipedia , lookup

Power inverter wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Amplifier wikipedia , lookup

Two-port network wikipedia , lookup

Distribution management system wikipedia , lookup

Transformer types wikipedia , lookup

Surge protector wikipedia , lookup

Alternating current wikipedia , lookup

Voltage optimisation wikipedia , lookup

Rectifier wikipedia , lookup

Integrating ADC wikipedia , lookup

Mains electricity wikipedia , lookup

Voltage regulator wikipedia , lookup

Buck converter wikipedia , lookup

AC adapter wikipedia , lookup

Schmitt trigger wikipedia , lookup

Opto-isolator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Transcript
Series 700 A/V-S Power Conditioner
Designed for Varian Truebeam, Acuity or any High
Energy Accelerator
Input Voltages: 208 VAC, 240 VAC, 480 VAC or 600 VAC (60 Hz)
Output Voltages: 208/120 VAC or 480/277 VAC
▪ Integrated Input and Output Breakers
(1 input breaker - 1 output breaker)
▪ Intelligent Voltage Regulation (+/- 2.0% Output)
▪ Internal Bypass Switch
▪ Triple Shielded Isolation Transformer
▪ Internal TVSS
▪ User-Friendly LED Monitor Panel
▪ Front Access “Zero Clearance” Cabinet
50 kVA Power Conditioner with
Voltage Regulation (60 Hz)
Submittal Package and Specifications
50 kVA 60 Hz Power Conditioner | Submittal Package
2
TRANSTECTOR SERIES 700 A/V-S
Specifications for 50kVA Power Conditioner with Voltage Regulator (60Hz)
1.0 SCOPE
This specification covers the electrical characteristics of the Transtector Power Conditioner which provides
clean regulated power for the entire Varian TrueBeam, Acuity or any High Energy Accelerator.
2.0 GENERAL
The Power Line Conditioner consists of a front access power cabinet incorporating an all copper, multiple
tapped, triple shield isolation/regulation transformer. The ultra low output impedance of the transformer
in conjunction with the electrostatic shields assures precision hospital grade performance with excellent
noise and transient attenuation. Independently controlled inverse parallel electronic switches for each of
the 7 taps per phase provide tight regulation over a wide input range. Linear devices are used for line
synchronization to prevent phase shift errors normally associated with simple CT zero current crossing
acquisition. The microprocessor control accurately selects the correct tap to provide line voltage regulation
of + 2.0% typical, correcting for voltage disturbances within one cycle. Digital processing technique provides
fast and accurate regulation without output voltage over or undershoots.
2.01 MODEL NUMBERS
MODEL
Standard models
8BLX-50K-700A/V-S
8CLX-50K-700A/V-S
8DLX-50K-700A/V-S
8ELX-50K-700A/V-S-C
8BNX-50K-700A/V-S
8CNX-50K-700A/V-S
8DNX-50K-700A/V-S
8ENX-50K-700A/V-S-C
INPUT VOLTAGE
OUTPUT VOLTAGES
208 VAC nominal input
240 VAC nominal input
480 VAC nominal input
600 VAC nominal input
208 VAC nominal input
240 VAC nominal input
480 VAC nominal input
600 VAC nominal input
208/120 VAC output
208/120 VAC output
208/120 VAC output
208/120 VAC output
480/277 VAC output
480/277 VAC output
480/277 VAC output
480/277 VAC output
2.1 AGENCIES
2.1.1 STANDARDS
The systems shall be designed in accordance with:
▪ American National Standards Institute
▪ Institute of Electrical and Electronic Engineers
▪ National Electric Code (NEC)
▪ National Fire Protection Association (NFPA Article 70)
▪ Underwriters Laboratories (UL) 1449, 1012
▪ FCC Article 15, Section J, Class A
▪ ISO 9001:2008
3
2.1.2 LISTINGS
▪ The system shall be listed to UL standard UL1012
▪ The system shall comply to: FCC Article 15, Section J, Class A and ANSI C62.14
(electromagnetic compatibility)
▪ The TVSS shall be UL 1449 2nd Edition listed/recognized
3.0 DYNAMIC ELECTRICAL CHARACTERISTICS
3.1 OPERATING VOLTAGE AND OUTPUTS
The input voltage shall be 208VAC, 240VAC or 480VAC, Delta, three phase, 60Hz. The standard
transformer design shall be capable of accepting three (3) input voltages, 208 VAC, 240 VAC or 480
VAC. Each unit will be pre-wired at the factory to accommodate the selected nominal input voltage. The
input voltage and input breaker can be changed in the field to accommodate an alternative input voltage.
Units with other input voltages (i.e. 380, 400, 415, 600 VAC) and/or frequencies (50 Hz) are produced
upon request.
3.2 LINE VOLTAGE REGULATION
Usable Input Line Voltage +15%, -23%.
Nominal Input Line Voltage +10% to –15%
3.2.1 Output Line Voltage Regulation is typically +2.0%
The design of the system shall indicate that with an input voltage of -10% of nominal, increasing the load
to 1000% shall cause the output voltage to fall no lower than -6%.
3.3 OUTPUT VOLTAGE
The output voltage shall be 208/120 VAC, or 480/277 VAC, 3 phase 4 wire, in a WYE configuration
3.4 OUTPUT CONNECTIONS
A 175 Amp three (3) pole circuit breaker is provided for the 208/120 VAC output.
A 90 Amp three (3) pole circuit breaker is provided for the 480/277 VAC output.
3.5 INPUT/OUTPUT WIRING
The input/output wiring sizes are dependant upon the terminals provided by the circuit breakers.
Input wiring sizes:
208 VAC
240 VAC
480 VAC
600 VAC
#3/0 AWG to 350 MCM
#4 AWG to 4/0 AWG
#14 AWG to #3/0 AWG
#14 AWG to #3/0 AWG
Output wiring sizes:
208/120 VAC 175 Amp breaker
480/277 VAC 90 Amp breaker
#4 AWG to 4/0 AWG
#14 AWG to 3/0 AWG
The ILSCO TA-2/0 terminal allows wire sizes from #14 to 2/0 AWG to be connected to the ground.
1402-001
50 kVA 60 Hz Power Conditioner | Submittal Package
3.6 RESPONSE TIME
Response time is less than 1/2 cycle.
3.7 CORRECTION TIME
The output voltage is corrected within 1 cycle.
3.8 LOAD REGULATION
The output is maintained to within 2% of nominal or less, from no load to full load.
3.9 IMPEDANCE
Output impedance shall be less than 2.0%.
3.10 OPERATING FREQUENCY
60 Hertz + 3 Hertz.
3.11 HARMONIC DISTORTION
Less than 1% THD added to the output waveform under any dynamic linear loading conditions presented
to the line regulator.
3.12 TURN-ON CHARACTERISTICS
When energized the voltage overshoot is 5% or less of the nominal voltage for less than 1 cycle.
3.13 OVERLOAD RATING
200% for ten seconds.
1000% for one cycle.
3.14 NOISE ATTENUATION
Common mode noise attenuation is typically 140 dB or greater.
Transverse mode noise attenuation is 3 dB down at 1000 Hertz, 40 dB down per decade to below 50 dB
with a resistive load.
3.15 AUDIBLE NOISE
Not to exceed 55dB measured @1 meter.
3.16 EFFICIENCY
Efficiency shall be > 96% typical at full load. Excitation losses shall be less than 1.5% of KVA rating.
3.17 BTU
The Power Line Conditioner shall generate no more than 6,820 BTU/Hour in typical use.
3.18 POWER FACTOR
Input power factor shall be greater than .95 with a resistive load and reflect no triplen harmonics to the
utility under non-linear loads.
3.19 LINE TO LINE BALANCE
The Power Line Conditioner shall not produce more than a 2% phase to phase unbalance.
3.20 MTBF
The system shall exhibit a MTBF > 10,000Hr.
4
5
3.21 ENHANCED TRANSIENT OVER VOLTAGE SURGE SUPPRESSION
For 208V outputs a Transtector model MCP 120 W, silicon avalanche diode TVSS shall be installed
parallel to the secondary output of the power line conditioner to provide bi-directional and bi-polar surge
protection. The unit shall be non-degrading and provide <330 volt SVR rating. The suppression network
systems shall be UL recognized/listed and conform to UL 1449 ratings when subjected to ANSI/IEEE 62.411991 category C1/B3 waveforms. The surge suppressor is installed on the load side of the transformer,
connected in parallel.
For 480V outputs an enhanced surge protection device (SPD) shall be installed parallel to the secondary
output of the power line conditioner to provide all mode, bi-directional and bi-polar surge protection. The
SPD is rated for 100 Ka per phase, 50 Ka per mode capacity. (L-L, L-N, L-G, N-G) The suppression
network systems shall be UL recognized/listed and conform to UL 1449 ratings when subjected to ANSI/
IEEE 62.41-1991 category C1/B3 waveforms. The surge suppressor is installed on the load side of the
transformer, connected in parallel.
4.0 MAIN TRANSFORMER
4.1 BASIC CONSTRUCTION
The transformer windings are of all copper conductor construction with separate primary and secondary
isolated windings.
4.2 MAGNETIC
Grain oriented, stress relieved silicon transformer steel is utilized to minimize losses and provide maximum
efficiency. Flux density will not exceed 14k gauss.
4.3 INSULATION
Class N (200° C) insulation is utilized throughout.
4.4 SHIELDING
The transformer has multiple (three) copper shields to minimize inner winding capacitance, transient
and noise coupling between primary and secondary windings. Inner winding capacitance is limited to
.001 pf or less.
4.5 COOLING
The transformer is designed for natural convection cooling. Fans are inside the unit.
4.6 OPERATING TEMPERATURE
The system operating range: 0 to 40 degrees C, 32 to 104 degrees Fahrenheit
4.7 OPERATING HUMIDITY
0-95% relative humidity, non-condensing.
5.0 MAIN INPUT BREAKER
A main input molded case, thermal magnetic circuit breaker, rated at 125 % of the full load input current,
is furnished as an integral part of the unit. For example, a 200 Amp input breaker will be provided for
208 VAC input, a 175 Amp breaker will be provided for a 240 VAC input, or a 90 A input breaker will be
provided for 480 VAC input. A 70 Amp input breaker will be provided for 600 VAC input.
1402-001
50 kVA 60 Hz Power Conditioner | Submittal Package
6
6.0 BY-PASS SWITCH
A manually operated rotary bypass switch provides bypassing of the SCR controlled voltage regulator
portion of the Power Line Conditioner. The Power Line Conditioner can be operated in either the on-line
or bypassed mode with one turn of the switch. The transformer and surge suppression circuitry remains
in the circuit when in the bypass mode. The output will remain at 208/120 VAC or 480/277 VAC, three (3)
phase 4 wire WYE. The bypass switch is located on the front of the unit.
7.0 MONITORING
7.1 ALERT LIGHT
An indicator light shall annunciate that the output has been disabled by one of the following conditions.
(1) Transformer over-temperature.
(2) SCR thermal over-temperature.
7.2 INDICATING LAMPS
Output “ON” indicating lamps shall provided for each phase.
8.0 CABINET
8.1 TERMINATION
Input and output terminations shall be front access. Input terminations shall be made directly to the main
input circuit breaker and the input ground terminal provided. Output terminations shall be made directly
to the output circuit breaker and neutral & ground copper bus provided.
The unit is constructed using an isolation transformer and is considered to be a “separately derived system”.
It should be grounded in accordance with the NFPA 70 article 250.20 “Alternating-Current Circuits and
Systems to be Grounded”, article 250.20 (D) “Separately Derived Systems” and article 250.30 “Grounding
Separately Derived Alternating-Current Systems”.
The Output Neutral and Ground is bonded at the output of the transformer and is considered a single,
separately derived, power source and should be wired accordingly.
8.2 VENTILATION
Ventilation originates from the front of the cabinet, exiting through the top.
8.3 MOBILITY
The Power Line Conditioner cabinets are equipped with angle iron supports that allow for transport by
pallet jack or fork lift. These can be used for mounting unit to the floor in seismic zones.
8.4 ACCESSIBILITY
The Power Line Conditioner will have front access. Access to all wiring inputs, output, bypass and
breakers will be accessible through the front access panels. The back of the unit may be set next to a
wall without impeding access. It will also incorporate lift off side panels.
8.5 WEIGHT
Unit weight: Approximately 1142 lbs (518 kg).
8.6 DIMENSIONS
29” Wide x 35.875” Deep x 66” Height
(73.6 cm x 91.12 cm x 167.64 cm).
7
9.0 CONTROLS
The control portion of the cabinet containing the circuit boards and connection to the semi-conductor
devices is separate from the transformer section and apart from the input and output power connections.
10.0 WARRANTY
Units within the contiguous United States (lower 48 states) shall include a comprehensive warranty for
the first year, covering all parts and workmanship, inclusive of on site labor and travel expenses. All units
shall further be covered under a standard two year warranty covering parts and workmanship.
11.0 SERVICE
Transtector shall provide immediate phone support/consultation and if possible, same day parts shipment.
(contact must be prior to 12:00 PM PST). If necessary, on site service shall be scheduled the same day
for service to be conducted within 24 to 48 hours, based on customer requirements. Typical service hours
are 8 AM to 5 PM Monday through Friday.
12.0 CONTACT
Rick Ribbeck
Phone: (01) 208-762-6112 or 1-800-882-9110 extension 6112
Transtector Systems
Cell: (01) 208-755-2072
10701 Airport Dr.
Fax: (01) 208-762-6133
Hayden Lake ID
83835
E-mail: [email protected]
1402-001
50 kVA 60 Hz Power Conditioner | Submittal Package
8
INPUT AND OUTPUT BREAKER SIZE
OUTPUT KVA
CONTINUOUS
INPUT BREAKER
SIZE
OUTPUT BREAKER
SIZE
MAX OUTPUT CURRENT
50 kVA
200A @ 208V
175A @ 240V
90A @ 480V
70A @ 600V
175A, 3P @ 208V
OR
90A, 3P @ 480V
138A CONTINUOUS @ 208V
60A CONTINUOUS @ 480V
WEIGHTS, BTU AND DIMENSIONS
OUTPUT KVA
WEIGHT
OPERATIONAL
BTU/HR
TYPICAL
MAXIMUM DIMENSIONS
BTU/HR
50 kVA
1,142 lbs
518 kg
3,410*
6,820
29” w x 35.875” d x 66” h
73.6 cm x 91.12 cm x 167.64 cm
* Stated BTU’s / Hr is at 50KVA rated load, 100% duty cycle. Operational BTU’s / Hr is typically at
50% of rated load. Input over current protection provided by others.
9
SEISMIC CALCULATIONS
Coastal California, Zone 4
Z = 0.4
Equipment Anchorage
I = 1.5
Uniform Building Code, Table 160
Cp = 0.75
Fp = Z x I x (Cp) x Wp = 0.45 x Wp
Cabinet Weight
1142 lbs.
Center of Gravity Height
23.75 in.
Wp (max) = 1442.1 lbs x 1.15 = 1313.3 lbs.
Wp (min) = 1065.9 lbs. x 0.85 = 970.7 lbs.
Fp = 0.45 x 1313.3 = 591 lbs.
Vertical Force
(Fp) = 0.15 x 1313.3 = 197 lbs.
Moment
Mo = 23.75 x 591 = 14036.25 in. lbs.
Tension = Fp x Cg / V4 = 1406.7 lbs.
Shear = Wp(max)Fp/4 lbs., each anchor= 328.3 lbs.
EXAMPLE: <Rawl Power Bolt # 6913>
3/8” embedded 2.5” / min 2000 psi concrete
Tension rating of bolt: 5200 lbs.
Shear rating of bolt: 7270 lbs.
Interaction = (T/Tbolt) + (S/Sbolt)
Interaction = 0.32
Corners (a,b) 39.5 in
V1=V4 = 19.3 in.
Interaction = < 1.00 (OK)
1402-001
LIFT-OFF ACCESS PANELS
REV.
1
2
3
DESCRIPTION
REVISIONS
CHANGED INPUT BREAKER
FROM 80A TO 90A@480V INPUT.
CHANGED OUTPUT BREAKER
FROM 150A TO 175A.
CORRECTED COMPONET
LAY-OUT.
LEFT SIDE
AIR FLOW
36" CLEARANCE REQ'D
FRONT SIDE FOR SERVICE
OF REGULATOR SECTION.
TSZ
DATE
TSZ
2/19/2010
TSZ
10/2/09
4/30/2010
NOTE: PANEL FASTNERS REQUIRE
A COMMOMN HAND TOOL FOR ACCESS.
BY
66.000
167.639cm
BOTTOM VIEW
MONITOR ALERT
LIGHTS
BYPASS SWITCH
TVSS
35.875
91.123cm
TOP VIEW
FRONT VIEW
29.000
73.660cm
.
AIR
INLET
WEIGHT
BTU/HR
INPUT
VOLTAGE
INPUT
BREAKER
BOTTOM INPUT/OUTPUT
TERMINATION ACCESS
4.500
11.430cm
70A
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
TRANSTECTOR. ANY
REPRODUCTION IN PART OR AS A WHOLE
WITHOUT THE WRITTEN PERMISSION OF
TRANSTECTOR IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
600VAC
90A
RIGHT SIDE
AIR FLOW
480VAC
2.812
7.142cm
6,820 BTU/HR FULL LOAD
175A
1142
240VAC
200A
4.750
12.065cm
8.250
20.955cm
208VAC
Ø 0.312
OPTIONAL SIDE
OUTPUT TERMINATION
ACCESS AREA
(CUSTOMER CONNECTS DIRECTLY TO
LINE SIDE (TOP) OF BREAKER)
INPUT CIRCUIT BREAKER
.
.
INPUT GROUND LUG (1) TA 2/0
WIRE RANGE: 2/0-#14 STR.
6.125
OUTPUT TERMINATIONS
3 PHASE, N & G
COPPER BUS
1.500
.
90A @ 480V
(CUSTOMER CONNECTS DIRECTLY TO
LOAD SIDE (BOTTOM) OF BREAKER)
OUTPUT BREAKER
175A @ 208V
OUTPUT BREAKER
CABLE ENTRY FOR: OPTIONAL REPO STATION &
OTHER OPTIONAL CIRCUIT BREAKER
CONTROL/TRIP INTERFACE'S
W/ (3) Ø0.875 KNOCK-OUTS
Ø2.223cm
TOP INPUT/OUTPUT
TERMINATION ACCESS
REMOVABLE TOP PANEL
PROVIDES ACCESS TO MAIN
TRANSFORMER & OUTPUT FILTER
MATERIAL
SCALE
0.125 = 1.000
TOLERANCE
.
NO.
.
SHEET
421484-3
OF1
DATE
DATE
T.SZWAST 9/16/09
CHECKED
DRAWN
8E(LN)X-50K-7A/V-S-C
INPUT VOLTAGE: 208,240,480,or 600VAC
OUTPUT VOLTAGE: 208/120VAC or 480/277VAC
SERIES 700A/V-S FRONT ACCESS CABINET OUTLINE
8(BCD)(LN)X-50K-7A/V-S
.
R
SUPERIOR SURGE SUPPRESSION
Hayden Lake, ID 83835
REAR VIEW
REAR PANELS
MAY BE REMOVED
TO DECREASE DEPTH.
(MUST BE REINSTALLED)
3
50 kVA 60 Hz Power Conditioner | Submittal Package
10
CABINET OUTLINE
BOTTOM VIEW
30.750
78.105cm
2.562
6.507cm
TOP INPUT/OUTPUT
TERMINATION ACCESS
TOP VIEW
24.750
62.865cm
8.000
20.320cm
2.125
5.398cm
1.876
4.766cm
3.001
7.623cm
8.500
21.590cm
23.000
58.420cm
REMOVABLE TOP PANEL
PROVIDES ACCESS TO MAIN
TRANSFORMER & OUTPUT FILTER
Ø 0.562
1.427cm
x 1.00
x 2.540cm
BOTTOM INPUT/OUTPUT
TERMINATION ACCESS
Ø2.223cm
REV.
1
2
3
DESCRIPTION
REVISIONS
CHANGED INPUT BREAKER
FROM 80A TO 90A@480V INPUT.
CHANGED OUTPUT BREAKER
FROM 150A TO 175A.
CORRECTED COMPONET
LAY-OUT.
OPTIONAL SIDE
OUTPUT TERMINATION
ACCESS AREA
CABLE ENTRY FOR: OPTIONAL REPO STATION &
OTHER OPTIONAL CIRCUIT BREAKER CONTROL/TRIP
INTERFACE'S
W/ (3) Ø0.875 KNOCK-OUTS
3.875
9.843cm
6.895
17.513cm
2.292
5.822cm
3.233
8.211cm
6.895
17.513cm
15.875
40.323cm
3.706
9.414cm
10/2/09
DATE
TSZ
TSZ
2/19/2010
4/30/2010
BY
TSZ
4.750
12.065cm
8.250
20.955cm
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
TRANSTECTOR. ANY
REPRODUCTION IN PART OR AS A WHOLE
WITHOUT THE WRITTEN PERMISSION OF
TRANSTECTOR IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
2.812
7.142cm
RIGHT SIDE
.
MATERIAL
SCALE
0.125 = 1.000
TOLERANCE
NO.
.
SHEET
421484-3
OF2
DATE
DATE
T.SZWAST 9/16/09
CHECKED
DRAWN
8E(LN)X-50K-7A/V-S-C
INPUT VOLTAGE: 208,240,480,or 600VAC
OUTPUT VOLTAGE: 208/120VAC or 480/277VAC
SERIES 700A/V-S FRONT ACCESS CABINET OUTLINE
8(BCD)(LN)X-50K-7A/V-S
.
R
SUPERIOR SURGE SUPPRESSION
Hayden Lake, ID 83835
4.500
11.430cm
AIR FLOW
3
11
CABINET OUTLINE
1402-001
TOP VIEW
FRONT
36" CLEARANCE REQUIRED
NO CLEARANCE REQUIRED
NO CLEARANCE REQUIRED
REV.
1
2
3
DESCRIPTION
REVISIONS
CHANGED OUTPUT BREAKER
FROM 150A TO 175A.
CORRECTED COMPONET
LAY-OUT.
CHANGED INPUT BREAKER
FROM 80A TO 90A@480V INPUT.
DATE
TSZ
TSZ
2/19/2010
10/2/09
4/30/2010
BY
TSZ
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
TRANSTECTOR. ANY
REPRODUCTION IN PART OR AS A WHOLE
WITHOUT THE WRITTEN PERMISSION OF
TRANSTECTOR IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
MATERIAL
SCALE
0.125 = 1.000
TOLERANCE
.
NO.
.
SHEET
421484-3
OF3
DATE
DATE
T.SZWAST 9/16/09
CHECKED
DRAWN
8E(LN)X-50K-7A/V-S-C
INPUT VOLTAGE: 208,240,480,or 600VAC
OUTPUT VOLTAGE: 208/120VAC OR 480/277VAC
SERIES 700A/V-S FRONT ACCESS CABINET OUTLINE
8(BCD)(LN)X-50K-7A/V-S
.
R
SUPERIOR SURGE SUPPRESSION
Hayden Lake, ID 83835
2
3
50 kVA 60 Hz Power Conditioner | Submittal Package
12
CABINET OUTLINE
NO CLEARANCE REQUIRED
Smiths Power is a leading supplier of power distribution, conditioning, protection and monitoring solutions
for data centers, wireless communications and other critical or high-value electrical systems.
As a family of brands, PDI, Onyx, PolyPhaser, Transtector, LEA, and RO Associates unite under one
umbrella to Transform, Distribute, Monitor and Protect™ power in global networks and systems. Our
companies provide expertise in consulting, design and manufacturing of power transformers and
distribution systems, static switching, power monitoring, RF, AC, DC, data signal and EMP protectors as
well as power quality engineering services.
Alongside Smiths Connectors and Smiths Microwave, Smiths Power is part of the Smiths Interconnect
division of Smiths Group (www.smiths.com), a global leader in applying advanced technologies for markets
in threat and contraband detection, energy, medical devices, communications and engineered components.
Smiths Group employs around 23,000 people in more than 50 countries.