Download Electrical Services Audit - Gold Coast Hospital

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Stray voltage wikipedia , lookup

Standby power wikipedia , lookup

Flexible electronics wikipedia , lookup

Portable appliance testing wikipedia , lookup

Electric power system wikipedia , lookup

Electrical engineering wikipedia , lookup

Three-phase electric power wikipedia , lookup

Electronic engineering wikipedia , lookup

Telecommunications engineering wikipedia , lookup

War of the currents wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Distribution management system wikipedia , lookup

Power engineering wikipedia , lookup

Metadyne wikipedia , lookup

Voltage optimisation wikipedia , lookup

Electrification wikipedia , lookup

Surge protector wikipedia , lookup

Ground (electricity) wikipedia , lookup

History of electric power transmission wikipedia , lookup

Alternating current wikipedia , lookup

Rectiverter wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Earthing system wikipedia , lookup

Mains electricity wikipedia , lookup

Residual-current device wikipedia , lookup

Home wiring wikipedia , lookup

Electrical substation wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Transcript
1.
Memorandum
Len Taplin
Principal Consulting /Chief Engineer
Professional Services Portfolio
From:
Glen Kay
Position:
Senior Electrical Engineer
Division:
Electrical Engineering
Phone:
3227 8626
Date:
23 July 2007
Subject:
Gold Coast Hospital - Electrical Services Audit
Len,
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
To:
Ref:
50445
DE
Inspections of the QEII hospital were carried out on the 8th June, 14th June and the 20th July
2007 with the assistance of Mr David James and Mr Kim Fetter. The purpose of the
inspection was to examine the infrastructure which needs to be upgraded to meet current
accepted standards and practices. In compiling this report, information has also been used
from as installed drawings, where available and information gathered during inspections.
Electrical Services Audit - Gold Coast Hospital-CFDE59AB.doc
RTI Folio No. 1
-2-
1.
Electrical General
The Gold Coast hospital was been located on the present site for more than 50 years. The
site consists of three main buildings – Tower Block, Block D (Rehabilitation) and Mental
Health building. Numerous other smaller buildings also are present on the site.
The Tower Block electrical services were refurbished in 1998. The Mental Health building
was built in approx 1991 with major reburbishments to parts of the electrical installation in
1999 to 2000. The Rehabilitation building or block D is the most recently constructed
building which was built in 2001.
1.
2.
3.
4.
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
The services covered by the electrical services report include the following:
Substations and Incoming Supplies
Tower Block
Block D
Mental Health or Psych Building
Each building is examined for the following electrical services:
•
•
•
•
•
•
•
2.
Electrical reticulation
Standby Generator System
Lighting
Emergency lighting
General Power Outlets and circuits
Uninterruptible Power Supplies.
Lifts
Substation and Incoming Energex Supplies
The hospital complex is supplied with electricity from the Energex 11 kV network and is
connected to three feeders from the Southport distribution subststation. The Southport
distribution substation is in turn connected to a 110 kV ring system and can draw power from
either the Surfers Paradise or Ashmore 110 kV substations. Separate 11 kv to 415 volt
substations are provided in the hospital complex for The Tower Block, Block D and the Mental
Health Building. Each of these substations can be connected to one or two 11 kV feeders from
the Southport distribution substation.
The Tower Block substation comprises three 1500 kVA transformers which can be supplied
from either one of the two incoming 11 kV feeders. An automatic high voltage transfer switch is
provided to switch to the alternate feeder in the event of a feeder failure.
DE
Block D and the Mental Health building have single transformer substations with 11 kV ring main
switches to enable manual switching to alternate backup incoming 11 KV supplies. Both of
these substations are sized to accept an additional transformer if required by future expansion.
The 11 kV supplies to the Mental Health and Tower Block are reticulated in underground cabling
The block D substation is connected to an underground feeder and a feeder which comprises
both underground and overhead reticulation.
The arrangement of substations and high voltage reticulation is considered sufficiently reliable
and no changes are recommended. The following electrical sketch ESK01 is based on
information provided by Energex and details the present arrangement of substations and 11 kV
feeders.
RTI Folio No. 2
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
-3-
ESK 01 - Substations and Incoming High Voltage Feeders
3.
Tower Block – Electrical Installation
3.1
General
The Tower block was constructed in stages comprising part A and part B/C. While both stages
were refurbished in 1998, part A includes some older electrical equipment more than 20 years
old. Lifts were also 1997. The main switchboard and substation were upgraded in 2006. The
cardiac catheter laboratory on level 9 has also been recently completed.
3.2
Electrical Reticulation
DE
The electrical reticulation consists of the following:
• Three 1500 kVA transformers supplying a load of maximum demand of approximately
2600 kVA in summer with all chillers operating.
• Main switchboard located on the lower ground floor within a fire rated room and
comprises metalclad combination switchfuse units in the older section and circuit
breaker protection in the new section
• At the main switchboard lighting, general power, fire services, lifts 2, 3, 7 and 8 are
connected to transformers No 1 and 2. A low voltage bustie switch enables the total load
of transformers No 1 and No 2 to be transferred to a single transformer in the event of a
failure. Total load on these two transformers is less 50% which enables all loads to
operated on one transformer.
• Mechanical air conditioning loads, lifts No 1, 4, 5 and 8 and essential ventilation are
RTI Folio No. 3
-4-
•
•
•
•
•
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
•
connected to transformer No 3. Transformer No 3 is fully loaded in summer when all
chiller plant is operating.
Automatic transfer switches connect the essential loads to the standby generator should
the normal power be not available.
The low load chiller No. 4 can be connected to the standby generator power supply.
MIMS and fire rated polymer submain cables distribute power to essential ventilation
and lift services.
Metal clad distribution switchboards are located in plant rooms and fire rated or non
combustible riser cupboards.
MIMS reticulation of 240v AC wiring for emergency lighting.
Connection points are provided for the connection of temporary generators to power non
essential loads in the event of a long term outage.
The electrical protection system throughout the hospital is also a concern. Unlike modern
hospital electrical designs the protection system is not discriminating for all types of faults. The
existing system comprises generally fuses to protect submains cables with downstream
subcircuit protection comprising non current limiting circuit breakers. With this combination it is
not possible to isolate subcircuit faults in all instances with the chance that a minor short circuit
fault on a distribution switchboard could blow the submains protection and affect numerous
other circuits connected to the same switchboard.
Subcircuit protection on lighting and power distribution switchboards in block A are
Westinghouse E frame circuit breakers in the order of 30 years old. These are not longer
available. Replacement circuit breakers are available but are relatively expensive. It is
considered more practical to replace circuit breakers and switchboard chassis with DIN style
miniature circuit breakers which are current limiting type and of suitable fault rating. All
distribution switchboards in sections A, B and C of the building have minimal RCD protection of
socket outlet circuits.
Existing switchboard chassis do not permit safe online connection of new circuits. Recent
advances in switchboard chassis provide fully insulated assemblies with switched busbar tee
offs which permit new circuits to be safely connected without load disruption.
The following recommendations are made for upgrading the electrical reticulation in the Tower
Block:
•
•
Distribution switchboards in part A of the Tower Block be replaced and distribution
switchboards in sections A, B and C are upgraded with RCD protection for all general
socket outlets circuits for office, kitchenette, cleaners, etc
Selection of new circuit breakers should be based on a fully discriminating protection
design which prevents short circuits on minor sub circuits blowing fuses which feed
multiple floors of the Hospital.
Replacement switchboards should incorporate circuit breaker chassis which enable online connection of new circuits to minimise hospital operations.
DE
•
RTI Folio No. 4
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
-5-
Typical Distribution Switchboard in part A of the Tower Block – Email E Frame circuit
breakers which are in the order of 30 years old. Switchboard chassis is not fully insulated
and requires power down of all connected loads to connect a new circuit.
3.3
Standby Generator System
The standby generator system for the Tower Block compises two Detroit Diesel enginees
coupled to Newage Stamford alternators.with a rating of 750 kVA/ 600 kW. Generators are
located in a fire rated room on the lower ground level and were in stalled in 1997. The
generators have facilities to parallel with the output of transformer No 3 for load testing.
Loads connected to the generator include essential ventilation, lifts, air compressors,
emergency lighting and essential lighting and general power and the low load chiller No 4. The
generators have the capacity to operate existing essential loads and the low load chiller No 4.
The protection provided on the generator is comprehensive and includes under and over voltage
protection for the load.
Exhaust from the generators is piped to the original boiler flues which rise to the top of the
Tower Block. Access to the exhaust stacks for maintenance is not possible and future repair
works when required will be costly.
DE
Standby generators in the Tower Block and block D are served by a 20,000 litre underground
fuel storage tank (permatank) with dual wall construction and monitoring.
The standby generator system is considered to be in reasonable condition.
3.4
Lighting
Lighting throughout is generally fluorescent 36watt triphoshor lamps installed in recessed
troffers with prismatic diffusers. Lighting in wards is either recessed troffers with prismatic
diffusers or bed head lighting. Lighting birthing suites, ICU , HDU and recovery consists of
recessed troffers and medical examination pendants.
RTI Folio No. 5
-6-
Lighting in general wards is of lower a standard than current practice. A lighting upgrade of
wards on levels 4 to 9 is recommended. Consideration should be given to providing
additional general lighting, recessed medical inspection lights for each bed and night
lighting. Lighting in theatres is of recent design and considered satisfactory.
It appears that existing lighting does not have toxic PCB type power factor correction
capacitors as earlier buildings do, however in any refurbishment it would be prudent to
confirm this prior to reuse or removal of existing luminaries.
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
It is recommended that future refurbishment of general wards consider the use of more
efficient lighting systems with electronic ballasts, T5 fluorescent lamps.
DE
Typical Ward Bed head Lighting
RTI Folio No. 6
-7-
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
Birthing Suite Lighting – Comprising room lights and examination lighting.
Pendant and room lighting for Theatres.
3.5
Emergency Lighting
General Emergency lighting within stairwells, corridors and larger spaces comprises a mixture of
a central battery emergency lighting system and single point stand alone units with integral
batteries. The central system was installed originally and single point lights have been added
more recently. Reticulation cabling for the central system is fire rated and uses MIMS cabling. A
dedicated UPS and battery room for the 240volt systems is located on the lower ground level.
Construction of the battery room appears to be fire rated as required by the latest building codes
and standards.
The central emergency lighting system is in reasonable condition. The calculated capacity
based on a 2 hour discharge with the existing batteries is approx 9400 watts of load which
appears sufficient capacity for the Tower Block. The battery recharge capacity is up to 30 amp
which will permit compliance with the 16 hour recharge time of the standard AS 2293.1.
DE
Non Compliance Aspects of the Central System are as follows:
• The switchboards in part B and C have three phase monitoring of local lighting circuits,
however part A of the Tower Block does not have three phase monitoring as required by
the code.
• The Master test switch for the central UPS does not automatically reset as required by
the standard AS 2293.1- part 3.
• Many Emergency Exit signs in part A of the Tower Block have green on white lettering
which is non compliant and have not been available for approx 15 years.
The disadvantages of the central battery system are that the cabling is fire rated and the system
does not have central monitoring system which is available for single point systems and aids in
maintenance. A further disadvantage of the central system is full testing requires discharge of
the central battery. This will remove all emergency lighting from the hospital until batteries are
recharged. With a computer based single point system testing can be carried out in sections so
that some emergency lighting is always available and non 24 hour operations are tested outside
of normal hours. Single point systems with central Stanilite monitoring have been installed in the
more recently built Block D.
RTI Folio No. 7
-8Theatre pendant and examination lighting is supported by 32 and 24 volt DC central battery
systems and are locate on level 1 part B on the same level as operating theatres.
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
It is recommended that consideration is given to replacing the existing 240 volt AC central
battery emergency lighting with a computer monitored self contained emergency lighting
system.
This will standardise the emergency lighting systems throughout the complex and simplify
maintenance, modification, and extension of the emergency lighting system.
DE
Non complying Green on White Exit emergency sign connected to central battery
system.
RTI Folio No. 8
.
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
-9-
DE
240volt AC Central Battery and UPS
RTI Folio No. 9
- 10 -
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
Self Contained emergency Exit sign installed on level 10
DE
24 volt and 32 volt Batteries for Operating Theatre Satellite Pendant Lighting
RTI Folio No. 10
- 11 -
3.6
General Power Outlets and Circuits
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
Within the last five years the use of RCD protection of general socket outlets has become
normal practice. Since the majority of the Tower Block electrical installation was installed more
approximately 9 years ago RCD protection is restricted to medical areas and wards where
compliance with AS3003 only (body protection and cardiac protection) is provided. Many
general use socket outlets are connected to circuits without residual current protection (RCD).
DE
Typical Ward - Six socket outlet on the LHS of the bed. All are connected to essential
lighting circuits. Two are for computer equipment only. One ceiling mounted socket
outlet provided for television.
Local 6 bed ward RCD Protection for Bed Socket Outlets. One circuit for essential and
one for computer socket outlets (also on essential)
RTI Folio No. 11
- 12 -
Socket outlets in general wards are installed to AS 3003 body protected areas with six outlets
adjacent each bedhead. All socket outlets are connected to essential circuits. Two are for
computer equipment only.
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
Socket outlets in the operating theatres comprise four service panels with 4 socket outlets each.
Each panel is connected to a separate RCD, however all RCDs are on the one circuit. No UPS
power or line isolation monitored power is available. This arrangement is not considered
acceptable. Staff advised that on at least one occasion the single circuit to a theatre overloaded
and required an electrician to reset the circuit breaker at the distribution switchboard. As a
minimum it is recommended the following is installed:
• Additional 2 socket outlets per service panel connected to a separate circuit.
• Additional 2 socket outlets on each panel be installed connected to a UPS power supply
and line isolation monitored supply.
• Additional essential circuit and a UPS circuit.
Actual installation design would need to examine the possible equipment arrangements and
ratings.
UPS socket outlets are also recommended and typically installed for other critical care areas
such as HDU, ICU, birthing and emergency resuscitation room and minor operating theatre are .
DE
Surge diverters, filtering or uninterruptible power supplies are generally not provided. The use of
fuse protection in the distribution system is a source of voltage surges if faults short circuits or
overloads occur and therefore it is essential surge protection is installed to protect sensitive
equipment. It is recommended all socket outlets for IT equipment and electronic medical
equipment are protected by surge protection at each floor distribution switchboard.
Cardiac Protected Area in Birthing Suite – 6 socket outlets on essential circuit
RTI Folio No. 12
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
- 13 -
Operating Theatre main service panel with 4 socket outlets.
DE
Recovery service panel with 6 essential socket outlets.
RTI Folio No. 13
- 14 -
3.7
Uninterruptible Power Supplies
The present installation has UPS installed for IT equipment in server rooms and communication
cupboards, Cardiac Catheter Ward and each Mechanical Services Switchboard for BMS
monitoring. No UPS power is provided for Theatres, Emergency, delivery rooms, HDU, NICU
and ICU areas.
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
Recent hospital projects have included reticulated UPS for all these areas to enable electronic
computer based equipment to continue to operate in the event of a power outage and to protect
such equipment from voltage disturbances due to electrical faults and lightning. It is
recommended that a central UPS installation is installed and reticulated to staff stations,
operating theatres, emergency ward, delivery rooms, HDU, NICU and ICU areas where life
maintaining and computer based medical equipment or IT equipment is installed.
In addition to additional UPS power, it is recommended surge protection is provided at all
distribution switchboards serving computer and electronic equipment.
3.8
Lifts.
DE
Recently completed Cardiac Catheter Ward services panel with blue UPS socket
outlets – Level 9 part B/C
The Tower block is served by 8 traction lifts which were upgraded in 1997. Lifts 1 and 2 are
public lifts and the remainder designed for staff use. Lifts 3 to 8 can operate as emergency lifts
and have emergency recall key switch control on the ground floor. Staff lifts (3 to 8) comply with
the minimum dimensions for lift car size and entrances for emergency lifts as specified in the
Building Code of Australia. Lifts 3 to 8 are sized to accept a stretcher.
Lifts 3 and 4 have doors at the front and rear and can be switched between operation for the
staff lobby or the public lobby.
A fire service key on the ground floor calls all lifts to the ground floor.
RTI Folio No. 14
- 15 -
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
All lifts are connected to generator power in the event of loss of normal supply. In the event of
only one of the two standby generators failing, only four lifts will operate and comprise two staff
lifts and two public lifts.
Lifts generally comply with the Australian standard AS 1735.12 - 1994 for Facilities for persons
with disabilities however they do not comply with the latest standard dated 1999 in the following
points:
1. Control buttons within the lift cars and at landings shall have braille and tactile
information.
2. Audible automatic information provided within lift cars. Floors identified in English
voice at each lift stop.
3. Braile and tactile information provided for landing control buttons.
4. Automatic identification of each lift at the answering service receiving communication
from the lift car.
The minimum features required to comply with the current Building Code of Australia is items 1
and 3 – Braille and tactile information.
DE
Lift Motor Room in Tower Block
RTI Folio No. 15
- 16 -
Summary of Recommendations – Tower Block
Item
E1
Description
Reason
Replacement of Distribution
• Service and replacement
Switchboards in part A including
parts no longer available.
the installation of RCD circuit
• Not compliant with
breaker protection for all socket
current practice.
outlet circuits and chassis which
permit safe online addition and
replacement of circuit breakers.
Upgrade distribution switchboards
• Not compliant with
in part B/C with RCD protection of
current practice.
general socket outlets.
Upgrade lighting in general wards
• Not compliant with latest
with recessed inspection lighting,
standards and current
new night lighting and general
practice.
lighting.
Provision of Central UPS power
• Not compliant with latest
supply for operation theatres,
standard practice.
emergency, HDU, NICU and ICU
for socket outlets and reticulation
to computer based equipment.
Provide additional outlets and
• Not compliant with latest
circuits in operating theatres and
standard practice
adjacent anesthetic rooms
• Existing facilities have
proven inadequate.
Replacement of emergency
• Testing of emergency
lighting system with computer
lighting can be carried
monitored single point system.
out in parts to minimize
Parts A, B and C.
risk of loss of facility after
discharge testing.
• Uniform system
throughout hospital
Upgrade emergency lighting
• Not compliant with latest
monitoring in part A only, upgrade
standards
master test switch, replace older
out of date exit signs.
Upgrade of Lift facilities for
• Not compliant with latest
disabled in lift cars and at
standards
landings
Replacement of Simplex central
• Service and replacement
clock system. Provide 10 off
parts no longer available.
Theatre Clocks in operating and
procedure rooms.
Review and Upgrade of
• Equipment is in state of
Roof Lightning Protection System
disrepair with corroded
parts and unsuitable
earthing terminations.
Provision of surge protection at
• Necessary for protection
distribution switchboards.
of electronic equipment
and computer.
E3
E4
E5
E6
E7
E8
E9
E10
E11
DE
E2
Budget
$300,000
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
3.9
RTI Folio No. 16
$80,000
$540,000
$550,000
$100,000
$450,000
$170,000
$130,000
$430,000
$50,000
$40,000
- 17 -
4.
Psychiatric Unit - Electrical Services
4.1
General
The Psychiatric Building was constructed in 1992. The building was designed for the later
addition of extra floors. Services have extra space or capacity to allow expansion to extra levels.
The first level was refurbished in 1999. Electrical services on ground level are of an older
vintage than level 1 and are in need of an electrical upgrade. The lift installation has been
recently upgraded and changed from the original Boral to Kone lift installation with new controls.
4.2
Electrical Reticulation
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
The Psychiatric Unit has a separate substation to the Tower Block and Block D. A 1000 kVA
transformer powers the building. Due to the electrical infrastructure being sized for additional
floors the present main switchboard is lightly loaded and the maximum demand is less than 50%
of the supply capacity.
The main switchboard is in good condition, however replacement switchgear is no longer
available for the Merlin Gerin compact circuit breakers in the event of equipment failures. Lift
main switches do not comply with AS3000 as they are down stream of a switch which controls
non emergency services. It is recommended the switchboard is relabelled to comply with AS
3000.
Main Switchboard Essential Section – MCCB are no longer available Main Switch
Labelling is incorrect.
4.3
Standby Generator
DE
A 165 kVA/ 132 kW Detroit Diesel with Stamford Newage Alternator standby generator is
located on basement level and supplies essential lighting, general power, lifts, FIP and
ventilation. A single automatic transfer switch connects essential loads to the generator in the
event of mains supply failing.
The generator is in reasonable condition.
RTI Folio No. 17
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
- 18 -
Standby Diesel Engine Generator with base fuel tank.
4.4
Lighting
DE
Lighting generally comprise recessed plasterboard fluorescent vandal proof luminaires with
prismatic diffusers. Lighting in wards is either recessed troffers with prismatic diffusers or bed
head lighting. Some luminaires on the ground level are showing signs of ageing and it is
recommended all lights are cleaned, relamped and provided with new diffusers.
Ground Level lighting is showing signs of ageing. Exit light no longer complies with
code.
RTI Folio No. 18
- 19 -
4.5
Emergency Lighting
4.6
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
Emergency lighting on the first floor comprises single point emergency lights with integral
batteries and test switches located on distribution switchboards.
Emergency lighting on the ground floor appears to be the original emergency lighting
installation. Colour of exit signs does not meet the current standard and automatic time delay
test switches are provided on the ground floor.
Current practise is to provide emergency lighting in all rooms with staff and patients in a secure
mental health facility.
It is recommended the ground floor lighting is replaced with a compliant system and
consideration be given to adding additional emergency lighting in areas where staff are at risk.
General Outlets and Circuits
Socket outlets in patient areas have vandal resistant stainless steel cover plates. RCD
protection of socket outlet circuits is provided on level 1 however RCD protection is limited on
the ground level. It is recommended RCD protection is provided to all socket outlet circuits
throughout the building.
Surge diverters, filtering or uninterruptible power supplies are not provided. It is recommended
as a minimum all socket outlets for IT equipment and electronic medical equipment are
protected by surge protection at each floor distribution switchboard.
4.7
Lifts
Lifts have recently been upgraded from the original Boral lifts to Kone controls. Control panels in
cars are provided with facilities for disabled with tactile and Braille information and control
buttons.
Two lifts are installed with a spare lift shaft for a third lift. The third lift was planned to served
future floor levels if installed.
DE
The two lifts have stretcher facilities with a stretcher recess in the rear of the lift car to provide
the 2000 length required by the BCA. Lift car dimensions are as follows: - 1472 Wide, 1709
deep, 2400 High with a 920 wide entrance.
Lifts are provided with emergency Call and Fire Service controls, and hands free
communications for assistance.
The lift installation is in reasonable condition and is compliant with the latest Building Code of
Australia.
RTI Folio No. 19
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
- 20 -
Lift Car control panel with tactile controls and Braille information
4.8
Item
E1
E2
Summary of Recommendations – Psychiatric Unit
Description
Reason
Upgrade distribution switchboards
• Not compliant with
on level ground with RCD
current practice.
protection of general socket
outlets.
Refurbish or replace lighting on
• .Equipment reaching end
ground level.
of life.
Budget
$35,000
• Ground Level not
compliant with latest
standards
• Testing of emergency
lighting can be carried
out in parts to minimize
risk of loss of facility after
discharge testing.
• Uniform system
throughout hospital
• Not compliant with
current practice.
$75,000
• Necessary for protection
of electronic equipment
and computer.
$5,000
Replacement of emergency
lighting system on ground and
first
floors
with
computer
monitored single point system.
E4
Provide additional emergency
lighting in patient area where risk
to staff.
Provision of surge protection at
distribution switchboards.
E5
DE
E3
RTI Folio No. 20
$100,000
$15,000
- 21 -
5.
Rehabilitation Building (Block D) Electrical Services
5.1
General
Block D is the latest building on site and was constructed in 2001. Electrical equipment is
generally in good condition and complies with current practice and standards. The building has
basement, and levels ground to 3. Level 3 is not used but is available for future expansion. All
lifts can travel to level 3. The building is primarily used for rehabilitation wards and clinics,
endoscopy services and consultation rooms.
5.2
Electrical Reticulation
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
The building has a substation located on the basement level. A 1500 kVA transformer powers
block D and out buildings on the west of the complex. The substation is sized for expansion to
include an additional transformer.
A water leakage problem occurs in wet weather where water enters the building substation
through underground conduits which penetrate the building at the top level of the basement.
This is a major reliability and safety issue and need correction work. It is recommended that in
addition to sealing all conduit entries to the building and pits leading to the building that an
external conduit drainage pit with sump pump is installed adjacent to the building to collect any
water flowing along electrical conduits.
It was noted that the electricity HV supply conduits entering the building are not fire rated. All
electrical submains supporting emergency services are required to be fire rated by the BCA.
Recommended that fire rating is provided by a fire rated duct or sprinkler protection.
In addition several penetrations through fire rated walls and floors have been carried out
without maintaining the fire barrier integrity. It is recommended that these are filled with fire
rated sealant and certified.
5.3
Standby Generator
DE
A 350 kVA/ 280 kW Cummins Diesel engine with Stamford Newage Alternator standby
generator is located on basement level and supplies essential lighting, general power, fire
pumps and fans, lifts, FIP and ventilation. A single automatic transfer switch connects essential
loads to the generator in the event of mains supply failing.
The standby generator has a heat exchanger located on level 3. Exhaust pipes share the same
exhaust riser as the Tower block generators and the same 20,000 litre underground fuel storage
system as the Tower Generators.
The generator is in reasonable condition.
Block D Standby Generator
RTI Folio No. 21
- 22 -
5.4
Lighting
Fluorescent lighting is provided throughout with dimmable night lighting in wards, good levels of
illumination. Lighting is in good condition and no changes are recommended.
5.5
Emergency Lighting
Emergency lighting is single point system with computer monitoring and control. It is
recommended the system is extended to the Tower Block and the Psychiatric building.
5.6
General Outlets and Circuits
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
Body protected areas are provided for wards and procedure areas in compliance with AS 3003.
General socket outlets in other areas such as offices meeting rooms, corridors are provided with
RCD protection. Multiple circuits are provided to procedure areas.
Surge diverters, filtering or uninterruptible power supplies are not provided. It is recommended
as a minimum all socket outlets for IT equipment and electronic medical equipment are
protected by surge protection at each floor distribution switchboard.
5.7
Lifts
Three Liftronics lifts are provided with lifts 10 & 11 in one bank and lift 9 separate. All lifts
comply with the latest Building Code of Australia and the Lift standard for Facilities for Disabled
– AS 1735.12.
Lifts are in good condition, however a fault is being experience in the control logic. If one lift is
stoped on a level with a fault, it locks the remaining lift out.
5.8
Summary of Recommendations – Block D
Description
Reason
Repair water leak to basement
• Safety and Power supply
level and substation
reliability issue.
E2
Provide fire rating of conduits on
basement level.
• BCA compliance issue.
$10,000
E3
Fire rate pentrations.
• BCA compliance issue.
$5,000
E4
Provision of surge protection at
distribution switchboards.
• Necessary for protection
of electronic equipment
and computer.
$12,000
DE
Item
E1
RTI Folio No. 22
Budget
$50,000
- 23 -
6.
Other Buildings – Electrical Services
6.9
General
Buildings other than the three main buildings were not inspected in detail.
The electrical installation in Mitchell Court was noted to be in poor condition. External conduits
and switchboards were corroded and the switchboard was in disrepair. No RCD protection was
noted.
PA RT
RT I R
ME EL
E
N
W T AS
OR O E
KS F P
UB
LI
C
Accommodation building was noted as not complying with the BCA with regard to AS 2293 –
Emergency lighting.
DE
General recommendations at this stage for the minor buildings are as follows:
1.
Arrange where possible the removal of separate Energex electrical supplies and
connect power supplies to buildings to one of the three onsite substations.
2.
Provide RCD protection of socket outlets.
3.
Provide emergency lighting to BCA
RTI Folio No. 23