Download 3A1979

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Variable-frequency drive wikipedia , lookup

History of electric power transmission wikipedia , lookup

Rectifier wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Buck converter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Ohm's law wikipedia , lookup

Electrician wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Power over Ethernet wikipedia , lookup

Flexible electronics wikipedia , lookup

Automatic test equipment wikipedia , lookup

Rectiverter wikipedia , lookup

Electrical substation wikipedia , lookup

Electrical connector wikipedia , lookup

Opto-isolator wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Portable appliance testing wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

Electromagnetic compatibility wikipedia , lookup

Ground (electricity) wikipedia , lookup

Stray voltage wikipedia , lookup

Earthing system wikipedia , lookup

Electrical wiring wikipedia , lookup

Mains electricity wikipedia , lookup

National Electrical Code wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Surge protector wikipedia , lookup

Transcript
Surge Protection Made Simple™
ETHERNET DATA SIGNAL APPLICATIONS
Technical Data
Catalog number
Nominal voltage (UN)
Nominal current (IL)
Max. PoE watts / pair
Operating temperature range
Degree of protection
Test standards
Agency information
Hazardous Voltage
Will cause severe injury or death.
Working on or near energized circuits poses a
serious risk of electrical shock. De-energize all
circuits before installing or servicing this equipment
and follow all prescribed safety procedures.
Testing
BSPD48RJ45
48V
1A
25.5W/2, 51W/4 @ 57V max.
-40°C to +80°C
IP10
IEC 61643-21 / EN 61643-21
UL
1. Disconnect cables
before testing.
2. Test between these
connector pins:
1 & 2, 3 & 6,
4 & 5, 7 & 8.
≤ 20”
(0.5m)
Protected
side
Protected
side
OK
35mm DIN-Rail
cable lug
Unprotected
side
4.8mm Quick connect.
Use min. 16AWG
(15mm2) conductor
Connector Pin Assignments
Circuit Diagrams
Protected
side
d*
Unprotected cable
Wiring
RJ 45 Connector
1
2
3
4
5
6
7
8
4 Protected
pairs
* NOTE: Miminize chances of inductive coupling of interference voltages by
making separation distance to unprotected cables as far as possible.
UL Requirements
Applications
1.This device are intended for ordinary indoor us
on communication loop circuits that are
isolated from the Public Switched Telephone
Network.
2.The protector shall be secured using the
methods described in this instruction.
3.Proper grounding continuity shall be
determined.
4.Please install the protector in accordance with
the applicable requirements of the National
Electrical Code, Article 800 or other applicable
local codes.
5.The maximum circuit current for UL 497 B
applications is limited to 100mA.
Rack Mount
Panel Mount
ted de
vice
Equipment Chassis Mount
Class II grounding
protection
Protec
HUB /
Switch
osure
Encl
Protec
ted de
vice
Patch
OK
Ω
measurement
Installation Instructions
Mounting
MΩ
measurement
HUB /
Switch
Class I grounding
protection without
cable via direct DIN-Rail
mount on equipment chassis.
Replace
Safety Instructions
This Surge Protective Device (SPD) for
coaxial connection may only be installed
by qualified electrical personnel. All
applicable national and local electrical
standards and safety regulations must be
observed. The SPD must be checked for
external damage prior to installation.
If any damage or other defects are
detected, do not install the device.
The installation and application of this SPD
is only permitted within the limits shown
and stated in these installation
instructions.
The SPD and the equipment connected to
it can be destroyed by loads exceeding the
stated values.
Opening, modifying or otherwise
tampering with the SPD invalidates the
warranty.
panel
Use min. 16AWG
(1.5mm2) conductor
Patch
panel
Use min. 16AWG
(1.5mm2) conductor
Warranty
Connect to the
closest grounding
point. Use min. 16AWG
(1.5mm2) conductor.
See document 3A1502 at
www.cooperbussmann.com/surge
for details of limited warranty.
Tabulation Strike voltage in accordance with UL 497 B (Protectors for Data Communication and Fire Alarm Circuits)
Catalog Number
Strike voltage 100V
Strike voltage 100V / μsec
Shield-to-Ground
Line-to-Shield
Shield-to-Ground
Line-to-Shield
BSPD48RJ45
70V min 110V max
7V min
11V max
70V min
600V max
7V min
15V max
3A1979RevA © 2012 Cooper Bussmann St. Louis, MO 63178
Publication-No. DS1631/CB; ID-No. 066953
www.cooperbussmann.com