Download PDF

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Pulse-width modulation wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Electric power system wikipedia , lookup

Transistor wikipedia , lookup

Power over Ethernet wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Power inverter wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Ground (electricity) wikipedia , lookup

Three-phase electric power wikipedia , lookup

Islanding wikipedia , lookup

Electrical ballast wikipedia , lookup

Ohm's law wikipedia , lookup

Power engineering wikipedia , lookup

Protective relay wikipedia , lookup

History of electric power transmission wikipedia , lookup

Current source wikipedia , lookup

Power electronics wikipedia , lookup

Rectifier wikipedia , lookup

Stepper motor wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Voltage regulator wikipedia , lookup

Ignition system wikipedia , lookup

Distribution management system wikipedia , lookup

Metadyne wikipedia , lookup

Earthing system wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Triode wikipedia , lookup

Power MOSFET wikipedia , lookup

Buck converter wikipedia , lookup

Opto-isolator wikipedia , lookup

Residual-current device wikipedia , lookup

Stray voltage wikipedia , lookup

Voltage optimisation wikipedia , lookup

Surge protector wikipedia , lookup

Alternating current wikipedia , lookup

Electrical substation wikipedia , lookup

Mains electricity wikipedia , lookup

Circuit breaker wikipedia , lookup

Transcript
TYPE VSA20B POWER CIRCUIT BREAKER
EQUIPMENT SPECIFICATIONS:
Air-insulated Power Circuit Breaker with vacuum interruption.
STANDARDS:
The circuit breaker covered by this specification shall be designed,
manufactured, and tested in accordance with ANSI/IEEE C37.04-1979,
ANSI/IEEE C37.06-1987, ANSI/IEEE C37.09-1979 and ANSI/IEEE C37.0121979.
QUALITY
The manufacturing facility shall be independently certified to meet ISO 9001
Standards.
RATINGS:
Maximum Design Voltage (kV)
Nominal Operating Voltage (kV)
Voltage Range Factor K
Rated Impulse Voltage (kV)
Trip Solenoid (Vdc)
Actuation time (cycles)
Close Solenoid (Vdc)
Actuation time (cycles)
15.5
2.4-14.4
1
110
24
1.25
24
1.5
MECHANICAL LIFE:
2500 Close-Open Operations
FEATURES:
Bushings will be of “wet” porcelain and will have a standard creepage
distance of 17" inches.
Bushing terminals will be threaded stud type, 1 1/4-12 UNF2A,
Current interruption will occur in vacuum interrupters, one interrupter per
phase.
It will be possible to replace one or all bushings without any re-alignment
or adjustment of the vacuum interrupters or operating mechanism.
The interrupting time will be 0.042 seconds
1
Resistance-type heaters will be provided in the interrupter and operating
mechanism cabinets, to prevent moisture condensation.
The breaker will be shipped mounted in a substation mounting frame.
The mounting frame extension will have a ground pad which will
accommodate two No. 2/0 to 250 MCM conductors
Sensing bushing current transformers, 2000:1 ratio, for use with an
electronic reclosing breaker, will be mounted internally in the breaker on
bushings 1, 3, and 5.
A 4 - digit counter will be provided in the operating mechanism.
The breaker will use a motor operator to charge opening and closing
springs; solenoids will be used for the tripping and closing operations.
A contact position indicator, externally visible, will be provided.
Separate external pull rings will be provided to manually trip and close the
breaker.
A spring operator condition indicator will be provided to indicate whether
the closing springs are energized. The indicator consists of a mechanical
flag for indication and will be visible from the front of the operator cabinet.
The breaker will be capable of manual trip and manual close on a
maximum fault. Closing springs can be charged manually by means of a
crank (150 turns), through a gear box.
SPRING CHARGING MOTOR:
STANDARD
Operating voltage (Vac)
Voltage Range (Vac)
Maximum Current RMSA (amperes)
Steady State Current (amperes)
Motor Running Time (cycles)
240
160-257
13
8
40
ACCESSORY
120
90-127
18
9
40
CONTROLS:
The breaker will be capable of operation with any of the following: Form 3, Form
3A, Form 4A, or Form 4C Type ME Breaker control.
2
rcn5/14/97
3