Download Timer and switching relay

Document related concepts

Nanogenerator wikipedia , lookup

Index of electronics articles wikipedia , lookup

TRIAC wikipedia , lookup

Transistor–transistor logic wikipedia , lookup

Analog-to-digital converter wikipedia , lookup

Integrating ADC wikipedia , lookup

Josephson voltage standard wikipedia , lookup

Ohm's law wikipedia , lookup

Multimeter wikipedia , lookup

CMOS wikipedia , lookup

Current source wikipedia , lookup

Valve RF amplifier wikipedia , lookup

Operational amplifier wikipedia , lookup

Power MOSFET wikipedia , lookup

Power electronics wikipedia , lookup

Current mirror wikipedia , lookup

Surge protector wikipedia , lookup

Schmitt trigger wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Voltage regulator wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Network analysis (electrical circuits) wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Opto-isolator wikipedia , lookup

Rectiverter wikipedia , lookup

Transcript
Timer and switching relay
Timer and switching relays
Timers
¾
¾
¾
¾
Power-on delayed
Power-off delayed
Power-on and power-off delayed
Switch-on and/or switch-off wiping (pulse shaper)
Function timer relay
¾
¾
¾
¾
¾
¾
Clock generator
Flasher relay
Relay for star-delta changeover
Pulse counter
Coupling relay
Tilting relay
Additional function relay
¾ is available in the product overview and on our home page
www.schleicher-electronic.com
45 x 75 mm
Page 25
2
Equipment sizes
2
72 x 72 mm
48 x 48 mm
2
22.5 x 90 mm
2
Subject to change without further notice
FUNCTIONAL RELAYS
CLOCK GENERATOR
TIMERS
VERSION
DZ 12-SL
DZN 12-SL
DZ 52-SL
DZA 52-SL
DZD 92 L
KPT 11 KD
KSP 12
KMZ 71
KMZ 72
KMZ 91
KMZ 92
KZTH 11
NGB 12
NGD 31
NGM 1004
NGM 1600
NGS 12
NGZ 11
NGZ 12
NGZ 12-S
NGZ 71
NGZ 110
NGZ 310
NGZ 710
NGZ 720
NGZP 32
SSP 56
SSY 12
UZD 51
Product overview timer and switching relays
Multi-function
Single function
Multi-range
Single range
•
Fixed time
Response delay
•
Power-on delay (pulse excitation)
Power-off delay
Power-off delay without auxiliary voltage
Power-on and power-off delay, symmetrical
Switch-on wiper
Switch-off wiper
Switch-on wiper and switch-off wiper
Start of pause, symmetrical and adjustable
Start of pause, pause and pulse can be adjusted
separately
Start of impulse, symmetrical and adjustable
Start of pulse, symmetrical and fixed setting
Start of pulse, pause and pulse can be adjusted
separately
Start of pause and pulse, sym. & fixed clock
time setting range
Pulse generator, power-on delay, pulse output
Pulse generator, start of pause, pause duration
adjustable, fixed pulse time
Pulse generator, alternating, pause or pulse
time adjustable
Pulse generator (switch-on wiper)
Continuation relay, function: On-off
Flasher relay, start of pause,
symmetrical and fixed setting
Coupling relay with immediate changer
Tilt relay, zero-voltage safe
Star-delta relay: Changeover, switch-on wiper
CONTACT S
Time changer
8
4 4 8 8
• •
5/6 6 7 10
• • •
10 16
•
•
•
7 7 7 7
3 8
•
•
•
•
•
• •
13
•
•
•
•
•
16 16
•
•
•
•
• • •
16 16
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
2
1
1 2
2
2
1 2 1
3
2
•
1 2
1
1 2 1 1 1 1 1 2 2
1 1 1 1 1
2
1
Immediate NO
1
2
1
1
2
1
1
2
1
1
3
Multi-voltage AC/DC 24 - 230V
Separated voltage ranges
CHARACTERISTIC
1 1
2
Closing / opening contact each
HOUSING
•
•
•
1 1 1 1 2
Immediate changer
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
+
•
•
+ + +
+ +
Immediate signal via B1 (B) or reset (R)
Setting digital (D) or analogue (A)
±
B
A A A A A/D A
A A A A A
R
A A A
A A A A A A A A A
D
48 x 48 mm
72 x 72 mm
22.5 mm
•
•
Zero-voltage safe
Adding (+) or adding or subtracting (±)
•
•
Remote potentiometer connection
Body housing
•
•
•
•
Time NO
Built-in housing
8
•
•
•
•
•
•
•
45 mm
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
1
= 1 timer and 1 immediate changer or 2 timers, depending on the function
= 1 timer and immediate changer or 2 time changers, adjustable
3
= semi-conductor
2
Page 26
Subject to change without further notice
DZ 12 - SL
DZ 12-SL
DZN 12-SL
Response-delayed single-domain time relay
•
•
•
•
Devices for Mono voltage
Function: response delay (AV), zero voltage-proof at DZN 12-S L
1 time domain
Contact assembly: 1 timed and 1 immediate contact
72 mm x 72 mm
Wiring diagram
Time domains
available setting ranges:
0.05 … 1 s
0.1 … 3 s
0.2 … 6 s
0.4 … 12 s
1 … 30 s
2 … 60 s
3.3 … 100 s
0.1 … 3 min
0.2 … 6 min
0.4 … 12 min
General information
• The electromechanical timed relays are equipped with a synchronous
motor and a magnet coupling.
• The infinitely adjustable time setting within a domain is performed
with the aid of the transparent knob.
The time elapse indicator runs during operation from the set time to 0.
Notes:
• By a frequency inversion on the bottom of the casing, the relay can be
adjusted to the respective frequency (50 or 60 Hz). The factory setting
is 50 Hz.
• The relays have separate motor and magnet connectors. This results in
various operation modes:
1. Time addition: Saving already elapsed times and/or adding various
time sections by separate actuation of the magnet coupling and the
motor.
2. Quick start:
Reduction of time Scatter to a minimum by constantly maintaining the motor's voltage and only exciting as well as deexciting the magnet coupling after the time elapse. This avoids the
motor fault. At elapsed times over 60 s, the quick start no longer affects the time Scatter.
3. Normal operation:
Simultaneous excitation and de-excitation
of the magnet coupling and the motor. Recommended for elapsed
times over 60 s.
• The greatest recurrence precision can be attained by selecting the
smallest possible time domain for the multi-domain version.
• The time domain toggle on the devices should only occur in the default position - since otherwise, time errors and faulty contact toggles
may occur.
1
2
4
0.1
0.2
0.4
1
2
4
…
…
…
…
…
…
…
…
…
30
60
120
3
6
12
30
60
120
min
min
min
h
h
h
h
h
h
Function
Upon excitation of the motor and the magnet, the immediate contact is
moved to the operating position, and the time elapse begins. If the
preselected time is attained, the time contact is activated and the motor
is powered off. After the de-excitation, the magnet, the timing element
and all contacts move to the default position. If a voltage interruption
occurs during the time elapse, then the magnet, immediate contact and
timing element fall into the default position.
For the zero voltage-proof timed relay DZN 12-S L, the function is as
described above; however, in the course of the excitation, the magnetic
valve is latched by a latch pin, so that even in the deenergized state, the
already elapsed time is maintained.
The time elapse can be interrupted any number of times. Even during the
voltage interruption, the immediate contact remains in the operating
position. If the preselected time is attained. The latch pin is released and
the timed contact is activated.
Impulse triggering: To activate the zero voltage-proof timed relay, an
impulse to the coupling suffices, since immediate latching occurs by way
of the latch pin (Motor and inductor connectors separate). The time elapse
begins upon motor excitation. The immediate contact moves to its operating position after the impulse triggering until the end of the time
elapse. After the time elapses, it moves back to the default position. The
time contact only opens for approx. 10 ms. A toggle of the time contact
to the "a" contact side does not transpire.
Reset: A mechanical Reset to 0 is possible for these devices.
Reset DZN 12-S L: An electrical and mechanical reset to 0 is only possible with this device when the mechanical latch is canceled. If a reset must
occur after an interruption of the time elapse, the knob is to be turned to
0.
DZ 12 SL
Page 27
DZ 12 SL
Function diagrams
Dimensional drawing
Accessories
Bushing plate
Plug-in socket
Adapter
B5
B7
BT 421
Cover
Recloseable cap
Seal
DA 1
V4
Z1
for installation and setup
for installation
for track assembly of the bushing
plate B 5
for switchboard cut-out
for switchboard installation
Device overview / Order numbers
Type
DZ 12-S L
Setting range
0.05 … 1 s
0.1 … 3 s
0.2 … 6 s
0.4 … 12 s
1 … 30 s
2 … 60 s
3.3 … 100 s
0.1 … 3 min
0.2 … 6 min
0.4 … 12 min
1 … 30 min
2 … 60 min
4 … 120 min
0.1 … 3 h
0.2 … 6 h
0.4 … 12 h
1 … 30 h
2 … 60 h
4 … 120 h
0.4 … 12 min
DZN 12-S L
Page 28
DZ 12 SL
Rated voltage
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 24 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 24 V 50/60 Hz
AC 48 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 230 V 50/60 Hz
AC 24 V 50/60 Hz
AC 230 V 50/60 Hz
Order number
R2.024.1029.0
R2.024.0109.0
R2.024.1769.0
R2.024.0629.0
R2.024.0839.0
R2.024.1959.0
R2.024.1009.0
R2.024.0819.0
R2.024.0099.0
R2.024.1019.0
R2.024.0789.0
R2.024.1229.0
R2.024.0449.0
R2.024.0539.0
R2.024.0129.0
R2.024.0799.0
R2.024.0909.0
R2.024.0849.0
R2.024.1529.0
R2.024.0549.0
R2.024.0859.0
R2.024.0529.0
R2.024.1169.0
R2.024.0559.0
R2.024.0399.0
R2.024.0349.0
R2.024.1129.0
R2.024.1079.0
R2.024.1899.0
R2.024.1069.0
R2.024.0729.0
R2.024.1519.0
R2.024.1089.0
R2.024.1639.0
R2.024.0709.0
R2.024.0379.0
R2.024.0809.0
R2.024.1139.0
R2.024.1499.0
R2.024.0979.0
DZ 12 - SL
Technical Data
Function type according to DIN VDE 0435 Section 110:04.89
Function indicator
Supply circuit
Nominal voltage UN
Rated output Motor at 50 Hz and UN (AC)
Rated output inductor at 50 Hz and UN (AC)
Nominal frequency
Operating voltage range
Timing circuit
Time setting / Quantity of time domains
Available time domains
Standby reactivation interval
Minimum power-on time
Fallback value
Parallel consumer loads permissible
Internal one-way rectification direction
Error (mean value of the scale end value)
Scatter
Setting range 0.03 to 1 s
Setting range 0.3 to 10 s
Setting range 3.3 to 100 s
End time ≥ 3 min
Output circuit
Contact allocation
Contact material
Switching nominal voltage Un
Max. steady current In
Usage category according to EN 60947-5-1:1991
Permissible frequency of operation
Mechanical service life
Response time
Fallback time
General Data
Air and creep sections between the power circuits
Rated surge voltage
Over-voltage category
Degree of contamination
Rated voltage
Testing voltage Ueff 50 Hz according to DIN VDE 0110-1, Table
A.1
Safety class for casing/terminals according to DIN VDE 0470 Section
1:11.92
Interference emission
Interference resistance
Ambient temperature, work area
Dimensional drawing
Wiring diagram
Weight
Accessories
DZ 12-S L
Electro-mechanical time relay for
Mono voltage
Item 3.13: Response-delayed time
relay
Indicator for elapsed time
FD 0008
DZN 12-S L
Electro-mechanical time relay for
Mono voltage
Item 3.14: Response-delayed, zero
voltage-proof timed relay
Indicator for elapsed time
FD 0033
see Device overview
approx. 1.3 VA / approx. 1.1 W
approx. 4.5 VA / approx. 3.8 W
50 and 60 Hz, can be toggled on the device
0.8 to 1.1 x UN
Analog / 1
s. Table "Time domains"
≤ 250 ms
–
≥ 15 % UN
yes
yes
In normal operation:
Setting range > 6 s; ± 1.5 %
Setting range
6 s; ± 2 %
Setting range
3 s; ± 3 %
Setting range
1 s; ± 8 %
Normal operation Quick start
± 0.045 s
± 0.015 s
± 0.09 s
± 0.06 s
± 0.54 s
± 0.51 s
± 0.5 % based on scale end value
30 ms
1 timed and 1 immediate contact
Ag Cu
AC/DC 230 V
5A
AC-15: Ue 230 V AC, Ie 2 A
DC-13: Ue 24 V DC, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles or
4
3 x 10 motor operation hours
≤ 30 ms
≤ 60 ms
according to DIN VDE 0110-1:04.97
4 kV
III
3 exterior, 2 interior
AC 250 V
2.21 kV
IP 30/IP 20
EN 50081-1:03.93. -2:03.94
EN 50082-2:1995
–10 to +55 °C
D 1-18
KS 5102/3
0.6 kg
B 5, B 7, BT 421, DA 1, V 4, Z 1
DZ 12 SL
Page 29
DZ
DZA / DZAN 52 / 53 L / SL
DZA 52-SL
DZA 53-SL
Response-delayed multi-domain time relay
•
•
•
•
•
•
•
72 mm x 72 mm
DZAN 52-SL
DZA 52 L
Devices for Mono voltage
Function: response delay (AV), zero voltage-proof at DZAN 52-S L
1 Setting range subdivided into 6 time domains contact assembly:
DZA 52-S L = 1 timed and 1 immediate contact
DZAN 52-S L = 1 timed and 1 immediate contact
DZA 53-S L = 2 timed contacts and 1 immediate "a" contact
DZA 52 L
= 2 timed contacts
Wiring diagram
Time domains
Available setting ranges:
0.1 s to 1000 s
subdivided into 6 time domains
0.1 … 3
s
0.3 … 10
1 … 30 s
3.3 … 100 s
10 … 300 s
33 … 1000 s
0.2 s to 60 h
subdivided into 6 time domains
0.2 … 6 s
2 … 60 s
0.2 … 6 min
2 … 60 min
0.2 … 6 h
2 … 60 h
0.1 s to 30 h
subdivided into 6 time domains
0.1 … 3
s
1 … 30 s
0.1 … 3
min
1 … 30 min
0.1 … 3
h
1 … 30 h
General information
Function
(continued)
Impulse triggering: To trigger the zero voltage-proof timed relay, an
impulse to the coupling suffices - since immediate latching occurs by
way of the latch pin (motor and inductor connectors separate). The time
elapse begins upon the motor excitation. After triggering the impulse,
the immediate contact moves to its working position, at which time
elapse has ended. After this time has elapsed, it falls back to the default
position. The timed contact opens only for approx. 10 ms. A toggle of
the time contacts to the "a" contact side does not transpire.
Reset: A mechanical Reset to 0 is possible for these devices.
Reset DZAN 52-S L: An electrical and mechanical Reset to 0 is only possible on this device when the mechanical latch is deactivated. If a Reset
must take place following an interruption of the time elapse, then the
extinguisher lever on the front plate (top right on the front plate) in the
direction of the arrow.
Accessories
Bushing plate
Plug-in socket
Adapter
B 5 or B 9
B 7 or B 8
BT 421
Cover
Recloseable cap
Seal
DA 1
V4
Z1
Page 30
for installation and setup
for installation
for track assembly of the bushing plate B 5
for switchboard cut-out
for switchboard installation
A / DZAN 52 / 53 L / SL
• The electromechanical timed relays are equipped with a synchronous
motor and magnetic coupling.
• The setting of the time domains occurs at the front, via a selector
switch,. The infinitely adjustable time setting within a domain is performed with the aid of the transparent knob.
• The time elapse indicator runs during operation from the set time
value to 0.
Function
Upon the excitation of the motor and the magnet, the immediate contact is set to the operating positions, and the time elapse begins. If the
preselected time is attained, the time contact is activated and the motor
powered off. After the de-excitation, the magnet, the timing element and
all contacts move to the default position. If a voltage interruption occurs
during the time elapse, then the magnet, the immediate contact and the
timing element fall into the default position.
For the zero voltage-proof timed relay DZAN 52-S L, the function is as
described above; however, during excitation, the magnetic flap is latched
shut by a latch pin, so that even in the deenergized state, the alreadyelapsed time is maintained.
The time elapse can be interrupted any number of times. The immediate
contact also remains in the operating position during the voltage interruption. If the preselected time has been attained, the latch pin is released,
the time contacts are activated and the motor powered off.
DZA / DZAN 52 / 53 L / SL
Function diagrams
Notes
• By way of a frequency toggle on the bottom of the casing, the relay
can be adjusted to the respective frequency (50 or 60 Hz). The plant's
default setting is 50 Hz.
• The relays have separate motor and magnet connectors. This results in
various operation modes:
1. Time addition: Saving already-elapsed times and/or adding different time sections by separate actuation of the magnet coupling and
the motor.
2. Quick start:
Reduction of time scatter to a minimum, by always
keeping the motor live (and only the magnet coupling is excited and
de-excited after the time elapses). This avoids the motor fault. For
elapsed times over 60 s, the quick start no longer affects time scatter.
3. Normal operation:
Simultaneous excitation and de-excitation
of the magnetic coupling and the motor. Recommended for elapsed
times over 60 s.
• The largest return precision is attainable by selecting the smallest
possible time domain in the multi-domain version.
• The time domain toggle on the devices should only occur in the default position - since otherwise, time errors and faulty toggle of the
contacts may occur.
Dimensional drawing
Device overview / Order numbers
Type
DZA 52-S L
Setting range
0.1 s … 1000 s
0.1 s … 30 h
0.2 s … 60 h
DZAN 52-S L
0.1 s … 1000 s
0.1 s … 30 h
0.2 s … 60 h
DZA 53-S L
DZA 52 L
0.2 s … 60 h
0.2 s … 60 h
Rated voltage
AC 24 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 125-127 V 50/60 Hz
AC 230 V 50/60 Hz
AC 24 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 125-127 V 50/60 Hz
AC 230 V 50/60 Hz
AC 24 V 50/60 Hz
AC 42 V 50/60 Hz
AC 48 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 125-127 V 50/60 Hz
AC 230 V 50/60 Hz
AC 24 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 24 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 24 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
AC 230 V 50/60 Hz
AC 24 V 50/60 Hz
AC 110-115 V 50/60 Hz
AC 230 V 50/60 Hz
Order number
R2.027.0219.0
R2.027.0039.0
R2.027.0049.0
R2.027.0099.0
R2.027.0329.0
R2.027.0279.0
R2.027.0309.0
R2.027.0079.0
R2.027.0339.0
R2.027.0179.0
R2.027.0229.0
R2.027.0259.0
R2.027.0279.0
R2.027.0059.0
R2.027.0289.0
R2.027.0239.0
R2.027.0199.0
R2.027.0119.0
R2.027.0129.0
R2.027.0089.0
R2.027.0149.0
R2.027.0189.0
R2.027.0029.0
R2.027.0269.0
R2.027.0209.0
R2.027.0139.0
R2.027.0069.0
DZA / DZAN 52 / 53 L / SL
Page 31
DZ
DZA / DZAN 52 / 53 L / SL
Technical Data
Function type according to DIN VDE 0435 Section 110:04.89
DZA 52-S L DZAN 52-S L DZA 53-S L DZA 52 L
Electro-mechanical time relay for Mono voltage
Responsedelayed time
relay
Responsedelayed time
relay
FD 0040
FD 0011
Function indicator
Function diagram
Responsedelayed, zero
voltage proof
time relay
Indicator for elapsed time
FD 0008
FD 0033
Supply circuit
Nominal voltage UN
Rated output (motor) at 50 Hz and UN (AC)
Rated output (inductor) at 50 Hz and UN (AC)
Nominal frequency
Operating voltage range
see Device overview
approx. 1.3 VA / approx. 1.1 W
approx. 1.0 VA / approx. 0.9 W
50 and 60 Hz, can be toggled on the device
0.8 to 1.1 x UN
Responsedelayed time
relay
Timing circuit
Time setting / Number of time domains
Available time domains
Standby reactivation interval
Minimum power-on time
Fallback value
Parallel consumer loads permissible
Internal one-way rectification direction
Fault (mean value of the scale end value)
Scatter
Setting range 0.3 to +6 s
Setting range 3 to +60 s
End time ≥ 60 s
Output circuit
Contact allocation
Contact material
Switching nominal voltage Un
max. steady current In
Usage category according to EN 60947-5-1:1991
Permissible frequency of operation
Mechanical service life
Response time
Fallback time
General Data
Air and creep sections between the electric circuits
Rated voltage impulse
Excess voltage category
Degree of contamination
Rated voltage
Testing voltage Ueff 50 Hz according to DIN VDE 0110-1, Table
A.1
Safety class for casing on the front side/casing on the rear side/flat plug
Interference emission
Interference resistance
Ambient temperature, work area
Dimensional drawing
Wiring diagram
Weight
Accessories
Page 32
A / DZAN 52 / 53 L / SL
analog / 6
s. Table "Time domains"
≤ 250 ms
–
30 ms
≥ 15 % UN
yes
yes
at normal operation:
Setting range > 6 s; ± 1.5 %
Setting range
6 s; ± 2 %
Normal operation Quick start
± 0.06 s
± 0.03 s
± 0.22 s
± 0.19 s
± 0.3 % based on scale end value
1 timed and
1 timed and
1 immediate
1 immediate
contact
contact
Ag Cd O
AC/DC 230 V
5A
AC-15: Ue 230 V AC, Ie 2 A
DC-13: Ue 24 V DC, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles or
4
3 x 10 Motor operation hours
≤ 25 ms
≤ 80 ms
–
–
2 time contact
2 time contact
and 1 immediate
"a" contact
according to DIN VDE 0110-1:04.97
4 kV
III
3 exterior, 2 interior
AC 250 V
2.21 kV
IP 54/IP 20/IP 00
EN 50081-1:03.93. -2:03.94
EN 50082-2:1995
–10 to +55 °C
D 1-25
KS 5102/3
KS 5102/3
KS 5151/2
0.4 kg
B 5, B 7, B 8, B 9, BT 421, DA 1, V 2, Z 2
KS 5153/2
DZD 92 L
DZD 92 L
Multi-Function - Multi-domain time relay
•
•
•
•
Mono voltage
8 Functions
Setting range 0.05 s to 100 h subdivided into 7 time domains
1 immediate-action and 1 time contact or 2 time contacts (adjustable)
72 mm x 72 mm
Wiring diagram
Time domains
Setting range 0.05 s to 100 h subdivided in:
0.05 s
… 1
s
3 min … 1
0.5 s
… 10
s
30 min … 10
3s
… 1
min
5 h … 100
30 s
… 10
min
h
h
h
Function
Dimensional drawing
The setting of the functions and the time domains as well as the fitting
with contacts occurs via a dual in-line switch on the rear of the device
(see Settings).
The infinitely adjustable time setting within a domain is made with the
aid of the transparent knob.
The set target value is indicated digitally, with a three-digit (7-Segment)
LED indicator.
The respective actual value is indicated during the time elapse in analog
mode (with 11 LEDs above the scale numbers) and also digitally (with the
LED indicator).
Functions:
• Response delay
(AV)
• Power-off delay
(RV)
• Switch-on wiper
(EW)
• Switch-off wiper
(AW)
• Response and fallback delay
(ARV)
• Impulse former
(IF)
• Pulse relay beginning with pause(TP)
• Pulse relay beginning with impulse(TI)
Indicators
B1
red LED, lit in presence of the
excitation
B2
red LED, lit in presence of the
excitation for additive operation
K
Accessories
Bushing plate
Plug-in socket
Cover
Recloseable cap
Seal
B5
B7
DA 1
V4
Z1
for installation and setup
for installation
for switchboard cut-out
for switchboard installation
red LED, lit upon the toggling
of the time contact
s; m; h red LEDs for the domain indicator; the lit section indicates the
set time domain and flashes
when the time elapses
3-digit LED indicator for the
set target value (and or during the countdown - indication of the actual value
DZD 92 L
Page 33
DZD 92 L
Function diagrams
Page 34
DZD 92 L
Function diagrams
DZD 92 L
Function diagrams
Function diagrams
Settings
The setting of the functions, the time domains and the contact assembly
occurs via a dual-in-line switch (equipped with 10 On/Off switches) on
the rear of the device.
Switch position
Time domain
0.05 s
to 1
s
0.5 s
to10
s
3
s
to 1
min
30 s
to 10 min
3
min to 1
h
30 min to 10 h
5
h to 100 h
Function
response delay
Power-off delay
Switch-on wiper
Switch-off wiper
Response and fallback delay
Impulse former
Pulse relay
beginning with pause
Pulse relay
beginning with
impulse
Contacts
1 timed and 1 immediate changer
2 time changer
Resolution
0.01 s
0.05 s
0.5 s
5
s
0.5 min
5
min
0.5 h
1
2
3
4
5
6
7
8
9
o o o
•o •o oo
•o •o •o
•o •o ••
o o o
•o •o oo
••o
o o •
•o•
o • •
•••
•
= ON (cam at top)
Switch position:
Switch, 8 to +0 available
DZD 92 L
o
•
Page 35
0
DZD 92 L
Technical Data
DZD 92 L
Function type according to IEC 60050 (445)
Function check
Analog-adjustable MultiFunction relay for Mono voltage
- Response-delayed time relay
- Fallback-delayed time relay with supply voltage
- Power- on interval time relay
- Power-off interval time relay
- Response and fallback delayed time relay
- Impulse former
- Pulse relay
6 LED red, 3-digit LED indicator, red, digit height: 7.6 mm
Supply circuit
Nominal voltage UN
Rated output at 50 Hz and UN (AC)
Rated output DC
Nominal frequency
Operating voltage range
Nominal current of the energizing quantity (B1)
see Device overview
4.7 VA / 4.6 W
2.6 W
50 to 60 Hz
0.8 to 1.1 x UN
8 mA
Timing circuit
Time setting/Number of time domains
Available setting range
Operate time of the energizing quantity (B1)
Fallback interval of the energizing quantity (B1)
Standby reactivation interval
Minimum power-on time
Fallback value
Parallel consumer loads permissible
Internal one-way rectification direction
Mean value of the fault
Scatter
Influence of energizing, supply voltage
Influence of the ambient temperature
analog/7
s. Table "Time domains"
≤ 20 ms; ≤ 2 ms at 24 V DC
≤ 20 ms; ≤ 3 ms at 24 V DC
≤ 40 / ≤ 60 ms; ≤ 40 / ≤ 10 ms at 24 V DC
≤ 40 ms; ≤ 5 ms at 24 V DC
≥ 15 % UN
yes
no
≤ 1 % ± 10 ms
≤ ± 0.5 % + ± 10 ms
≤ 0.005 % / % ∆ UN
≤ 0.005 % / K
Output circuit
Contact allocation
Contact material
Switching nominal voltage Un
max. steady current In
Usage category according to EN 60947-5-1:1991
Permissible frequency of operation
Mechanical service life
Operate time
Fallback time
General Data
Air and creep sections between the electric circuits
Rated surge voltage
Over-voltage category
Degree of contamination
Rated voltage
Testing voltage Ueff 50 Hz according to DIN VDE 0110-1, Table
A.1
Safety class for casing / terminals according to DIN VDE 0470 Section
1:11.92
Interference resistance according to IEC 61000-4
Ambient temperature, work area
Weight
Accessories
Approvals
1 immediate-action and 1 time changer or 2 time changers
Ag alloy; gold-plated
250/300 V AC/DC
5A
AC-15: Ue 230 V AC, Ie 2 A
DC-13: Ue 24 V DC, Ie 2 A
≤ 6000 switching cycles/h
6
30 x 10 switching cycles
approx. 10 ms
approx. 10 ms
according to DIN VDE 0110-1:04.97
4 kV
III
3 exterior, 2 interior
250 V AC
2.21 kV
IP 30 / IP 20
Test acuity 3
–20 to +60 °C
0.4 kg
B 5, B 7, DA 1, V 4, Z 1
–
Device overview / Order numbers
Type
DZD 92 L
Page 36
Time delay
s. Table "Time domains"
DZD 92 L
Rated voltage
DC 24 V
AC 24 V 50-60 Hz
AC 42 V 50-60 Hz
AC 115 V 50-60 Hz
AC 230 V 50-60 Hz
Order number
R2.054.0349.1
R2.054.0329.1
R2.054.0339.1
R2.054.0309.1
R2.054.0319.1
KPT 11 / 31 KD
KPT 11 KD
KPT 31 KD
Multi range repeat cycle timer
•
•
•
•
•
•
Dual voltage
1 function: KPT 11 KD: repeat cycle starting with OFF (TP)
KPT 31 KD: repeat cycle starting with ON (TI)
Setting range from 0.05 s to 10 h divided into 10 time ranges
1 change-over contact
2 LEDs for function display
Circuit diagram
Time ranges
Setting range from 0.05 s to 10 h divided into:
0.05 s
… 1
s
15 s
0.15 s
… 3
s
50 s
0.5 s
… 10
s
0.05 h
1.5 s
… 30
s
0.15 h
5s
… 100 s
0.5 h
…
…
…
…
…
300
1000
1
3
10
s
s
h
h
h
Function
Function diagrams
Different OFF and ON times can be selected in decimal increments on
the relay front by means of selector switches. The OFF and ON time
within a range is set using the selector wheel.
The different supply voltages have to be connected to their respective
assigned terminal.
Dimension diagram
KPT 11 / 31 KD
Page 37
DZ
KPT 11 / 31 KD
Technical data
Function type according to EN 60050
Function display
Function diagrams
Power supply circuit
Rated voltage UN
AC/DC
AC
Rated consumption at 50 Hz and UN (AC)
Rated consumption at 50 Hz and UN (AC)
Rated consumption DC
Starting current inrush stroke
Rated frequency
Operating voltage range
A / ms
Time circuit
Time setting / number of time ranges
Available setting range
Recovery time 1/2
Minimum on time
Release value
Repeat cycle starting with
Parallel loads permissible
Internal half-wave rectification
Mean value of the error
Dispersion
Influence of the energizing quantity, supply voltage
Influence of the ambient temperature
Output circuit
Contact assignment
Contact material
Rated operating voltage Un
Max. continuous current In
Application category according to EN 60947-5-1:1991
Permissible switching frequency
Mechanical life
Response time
Release time
General information
Creepage distances and clearances between the circuits
Rated impulse voltage
Overvoltage category
Degree of pollution
Rated voltage
Test voltage Ueff 50 Hz according to DIN VDE 0110-1. table A.1
Protection degree housing/terminal according to DIN VDE 0470 sec.
1:11.92
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram
Circuit diagram
Weight
Accessories
KPT 11 KD
KPT 31 KD
Electronic multi-range repeat cycle
timer starting with OFF.
For dual voltage.
Repeat cycle relay with two different supply voltage terminals
1 green LED, 1 red LED
FD 0069
Electronic multi-range repeat cycle
timer starting with ON.
For dual voltage.
Repeat cycle relay with two different
supply voltage terminals
24 V
115 V
5.5 VA
1.2 W
1.2 VA
1.0 W
0.7 W
1.5 / 2
0.5 / 2
50 – 60 Hz
0.8 – 1.1 x UN
24 V
1.2 VA
1.0 W
0.7 W
1.5 / 2
analogous/ 10
See table "Time ranges"
approx. 40 / approx. 80 ms
–
≥ 15 % UN
OFF
Yes
No
≤ ± 10 %
≤ ± 0.5 % + ± 10 ms
≤ 0.005 % / % ∆ UN
≤ 0.005 % / K
230 V
7.5 VA
1.5W
0.5 / 3
42 V
60 V
1.2 VA
1.0 W
0.8 W
0.1 / 6
1.5 VA
1.3 W
1.2 W
0.05 / 10
ON
1 change-over contacts
Ag alloy, gold-plated
230/230 V AC/DC
5A
AC-15: Ue 230 V AC, Ie 2 A
DC-13: Ue 24 V DC, Ie 2 A
≤ 6000 switching cycles/h
6
30 x 10 switching cycles
–
approx. 40 ms
according to DIN VDE 0110-1:04.97
4 kV
III
3 outside, 2 inside
250 V AC
2.21 kV
IP 30 / IP 20
Test severity 3
–20 to +60 °C
K1-8 W3
KS 0342/2
0.12 kg
–
Overview of devices / Part numbers
Type
KPT 11 KD
KPT 31 KD
Page 38
Rated voltage
AC/DC 24 V and AC 115 V 50-60 Hz
AC/DC 24 V and AC 230 V 50-60 Hz
AC/DC 42 V and AC 60 V 50-60 Hz
AC/DC 24 V and AC 115 V 50-60 Hz
AC/DC 24 V and AC 230 V 50-60 Hz
AC/DC 42 V and AC 60 V 50-60 Hz
DZD 92 L
ON-delay time
See table "Time ranges"
See table "Time ranges"
Part No.
R2.111.0019.3
R2.111.0029.3
R2.111.0039.3
R2.111.0049.1
R2.111.0059.1
R2.111.0069.1
KSP 12
KSP 12
Electronic flip-flop relay
• Mono voltage
• 1 Function: flip-flop relay
• 1 changer, 1 NO contact
Wiring diagram
Function
With the application of the supply voltage to the terminals A2/A3, the
contacts 11/14, 23/24 are closed. After the supply voltage is powered off,
the contact position is maintained.
With the application of the supply voltage to the terminals A1/A3 the
contacts toggle, 11/12 are closed and 23/24 open. After the supply
voltage is powered off, the contact position is maintained.
The relay can also be activated manually (at the front), by a lever.
The simultaneous excitation of both circuits is not permissible.
Function diagram
Dimensional drawing
KSP 12
Page 39
KSP 12
Technical Data
KSP 12
Function type according to IEC 60050
Electronic flip-flop relay for Mono voltage
- flip-flop relay
Switch position indicator
FD 0128
Function check
Function diagram
Supply circuit
Nominal voltage UN
Rated output at 50 Hz and UN (AC) (50 ms after activation))
Rated output DC (50 ms after activation))
Power-on current pulse
Peak current at 50 Hz and UN (AC) (activation))
Peak current at DC (activation))
Nominal frequency
Operating voltage range
AC/DC
Timing circuit
Time setting / Quantity of time domains
Available setting range
Standby reactivation interval
Minimum power-on time
fallback value
Parallel consumer loads permissible
Internal one-way rectification direction
Median value of the fault
Scatter
Influence of the energizing quantity, supply voltage
Influence of the ambient temperature
Output circuit
Contact assembly
Contact material
Switching nominal voltage Un
Max. steady current In
Usage category according to EN 60947-5-1:1991
Permissible frequency of operation
Mechanical useful life
Operate time
fallback time
General Data
Distances (sparking and "crawl") between the electric circuits
Rated voltage impulse
Excess voltage category
Degree of contamination
Rated voltage
Testing voltage Ueff 50 Hz according to DIN VDE 0110-1, Table
A.1
Safety class for casing / terminals according to DIN VDE 0470 Section
1:11.92
Interference resistance according to IEC 61000-4
Ambient temperature, work area
Dimensional drawing
Wiring diagram
Weight
Accessories
Approvals
24 V
0.6 VA / 0.4 W
0.4 W
–
≤ 110 mA
approx. 80 mA
50 to 60 Hz
0.8 to 1.1 x UN
42 to +48 V
0.8 VA / 0.6 W
0.4 W
–
≤ 110 mA
approx. 80 mA
110 to 120 V
1.1 VA / 0.7 W
0.5 W
–
≤ 40 mA
approx. 30 mA
–/–
–
3s
30 ms
–
yes
yes
–
–
–
–
1 contact, 1 "a" contact
Ag, gold-mist-plated
230/230 V AC/DC
5A
AC-15: Ue 230 V AC, Ie 3 A
DC-13: Ue 24 V DC, Ie 2 A
≤ 1200 switching cycles/h
6
1 x 10 switching cycles
≤ 25 ms at AC, ≤ 10 ms at DC
–
according to DIN VDE 0110-1:04.97
4 kV
III
3 exterior, 2 interior
250 V AC
2.21 kV
IP 30 / IP 20
Test acuity 3
–20 to +60 °C
K1-12 W3
KS 5189/2
0.12 kg
–
–
Device overview / Order numbers
Type
KSP 12
Page 40
Rated voltage
AC/DC 24 V 50-60 Hz
AC/DC 42-48 V 50-60 Hz
AC/DC 110-120 V 50-60 Hz
AC/DC 220-240 V 50-60 Hz
KSP 12
Order number
R2.156.0019.2
R2.156.0029.2
R2.156.0039.2
R2.156.0049.2
220 to 240 V
1.1 VA / 0.7 W
0.4 W
–
≤ 38 mA
approx. 25 mA
KMZ 71 / 72
KZL 72
KZL 71
KMZ 71
KMZ 72
Multi-function multi-range timer relay
Multi voltage for AC/DC 24 up to 230 V
4 functions
Setting range from 0.1 s to 120 h divided into 7 time ranges
KZL 72 =
1 instantaneous and 1 timed change-over contact or
2 timed change-over contacts (selectable)
• KZL 71 =
1 timed change-over contact
•
•
•
•
Circuit diagram
KMZ72
Time ranges
Setting range from 0.1 s to 120 h divided into:
0.1 s
… 1.2 s
0.1 h
1s
… 12
s
1h
0.1 min … 1.2 min
10 h
1 min … 12
min
… 1.2
… 12
… 120
h
h
h
General information
The functions and time ranges are set on the front through selector
switches.
KMZ71
Setting of the operating mode
Rotate the operating mode selector switch with a screwdriver until the
desired operating mode appears in the “MODE” display window.
Functions for KZL 72, KZL 71:
• A = ON-delay
• B2 = repeat cycle starting with ON
• E = interval ON
• J = one shot (ON-delay)
(AV)
(TI)
(EW)
(AI)
Setting of the time and time range factor
Rotate the time selector switch located in the upper right corner of the
control panel to set the desired time (sec., min. or hrs.) The time unit will
be shown in the display window over the time selecting wheel. The time
range factor (0.1 or 1) is set by rotating the selector switch located in the
upper left corner of the operating panel.
The selected time range factor will be shown in the display window
above the selector switch.
Setting of the operating time
Use the time selecting wheel (ratio 0 – 12) to set the desired operating
time.
Setting of the contact assignment
The function of the contacts for the model KZL 72 can be selected
through a switch located at the bottom of the housing: 2 timed changeover contacts or 1 instantaneous and 1 timed change-over contact.
KMZ 71 / 72
Page 41
KMZ 71 / 72
Function diagrams
Displays and operating components
1
2
3
4
5
6
7
time range switch
indicator (orange)
(Lit while Time relay output.)
Power ON LED (green)
(Lit while the Voltage supply.)
mode switch
only KMZ 72:
Switch INIT / TIME
(default setting for timed output) *
position for attaching the Users label
main command for setting development
time
* If you leave the switch between the settings, is a proper operation may
not be possible. Pay attention to the correct setting of the switch.
Note: The factory setting is mode A and 0.1 s.
Dimension diagram
Page 42
KMZ 71 / 72
KMZ 71 / 72
Technical data
Function type according to IEC 60050 (445)
KZL 72
KZL 71
Function display
Function diagrams
Multi-function relay with 4 functions for multi-voltage
– ON-delay timer relay
– Interval ON relay
– Repeat cycle starting with ON
– One shot (ON-delay) relay
1 LED green, 1 LED orange
FD 239-4/10 – 14
Power supply circuit
Rated voltage UN
Rated consumption at 50 Hz and UN 24 V AC
Rated consumption at UN 24 V DC
Rated consumption at 50 Hz and UN 230 V AC
Rated consumption at UN 230 V DC
Starting current inrush A1/A2 at 24 V DC
Rated frequency
Operating voltage range
Release value der Excitation voltage A1/A2
AC/DC 24 – 230 V
1.1 VA / 0.9 W
0.9 W
2.7 VA / 1.7 W
1.4 W
approx. 250 mA
50 – 60 Hz
0.85 – 1.1 x UN
< 8 V AC/DC
Time circuit
Time setting / number of time ranges
Available setting range
Recovery time
Repeatability
Setting tolerance
Influence of the energizing quantity or supply voltage
Influence of the ambient temperature
Analog / 7
See table "Time ranges"
≥ 100 ms
± 1 % + ± 10 ms average value of all measured values
± 10 % + ± 50 ms
± 0.5 % + ± 10 ms
± 2 % + ± 10 ms
Output circuit
Contact assignment
Contact material
Rated operating voltage Un
Max. continuous current In
Application category according to EN 60947-5-1:1991
Permissible switching frequency
Mechanical life
Electrical life
General information
Creepage distances and clearances between the circuits
Rated impulse voltage
Overvoltage category
Degree of pollution
Rated voltage
Test voltage Ueff 50 Hz according to DIN VDE 0110-1, table A.1
Protection degree housing/terminal according to DIN VDE 0470 sec.
1:11.92
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram
Circuit diagram
Weight
Accessories
0.7 VA / 0.6 W
0.6 W
2.3 VA / 1.4 W
1.4 W
1 timed change-over contact
1 instantaneous and 1 timed
change-over contact or 2 timed
change-over contacts
AgNi gold-flashed
230/125 V AC/DC
5A
AC-13: Ue 250 V AC, Ie 5 A
DC-13: Ue 24 V DC, Ie 0.1 A
AC-15: Ue 250 V AC, Ie 3 A
≤ 3600 switching cycles/h
6
10 x 10 switching cycles
4
80 x 10 switching cycles at AC 5 A, 250 V, 360 switching cycles/h
according to DIN VDE 0110-1:04.97
4 kV
III
3 outside, 2 inside
250 V AC
2.21 kV
IP 30 / IP 20
Test severity 3
–10 to +55 °C
K1-16
KS 0328/4
0.12 kg
–
KS 0328/3
Overview of devices / Part numbers
Type
KMZ 71
KMZ 72
Rated voltage
AC/DC 24-230 V 50-60 Hz
AC/DC 24-230 V 50-60 Hz
ON-delay time
See table "Time ranges"
See table "Time ranges"
Part No.
R2.066.0019.0
R2.066.0029.0
KMZ 71 / 72
Page 43
KMZ 91 / 92
KZL 92
KZL 91
KMZ 92
KMZ 91
Multi-function multi-range timer relay
Multi voltage for AC/DC 24 up to 230 V
8 functions
Setting range from 0.1 s to 120 h divided into 7 time ranges
KMZ 92 = 1 instantaneous and 1 timed change-over contact or
2 timed change-over contacts (selectable)
• KMZ 91 = 1 timed change-over contact
•
•
•
•
Circuit diagram
Time ranges
Setting range from 0.1 s to 120 h divided into:
0.1 s
… 1.2 s
0.1 h
1s
… 12
s
1h
0.1 min … 1.2 min
10 h
1 min … 12
min
KMZ92
… 1.2
… 12
… 120
h
h
h
General information
The functions and time ranges are set on the front through selector
switches.
Setting of the operating mode
Rotate the operating mode selector switch with a screwdriver until the
desired operating mode appears in the “MODE” display window.
KMZ91
Functions for KMZ 92, KMZ 91:
• A = ON-delay
• B = repeat cycle starting with OFF
• B2 = repeat cycle starting with ON
• C = interval ON/OFF
• D = OFF-delay
• E = interval ON
• G = ON-delay and OFF-delay
• J = one shot (ON-delay)
(AV)
(TP)
(TI)
(EAW)
(RV)
(EW)
(ARV)
(AI)
Setting of the time and time range factor
Rotate the time selector switch located in the upper right corner of the
operating panel to set the desired time (sec., min. or hrs.) The time unit
will be shown in the display window over the time selecting wheel. The
time range factor (0.1 or 1) is set by rotating the selector switch located
in the upper left corner of the operating panel.
The selected time range factor will be shown in the display window
above the selector switch.
Setting of the operating time
Use the time selecting wheel (ratio 0 – 12) to set the desired operating
time.
Setting of the contact assignment
The function of the contacts for the model KZL 92 can be selected
through a switch located at the bottom of the housing: 2 timed changeover contacts or 1 instantaneous and 1 timed change-over contact.
Page 44
KMZ 91 / 92
KMZ 91 / 92
Function diagrams
Function diagrams
Displays and operating components
1
2
3
4
5
6
7
time range switch
indicator (orange)
(Lit while Time relay output.)
Power ON LED (green)
(Lit while the Voltage supply.)
mode switch
only KMZ 92:
Switch INIT / TIME
(default setting for timed output) *
position for attaching the Users label
main command for setting development
time
* If you leave the switch between the settings, is a proper operation may
not be possible. Pay attention to the correct setting of the switch.
Note: The factory setting is mode A and 0.1 s.
Dimension diagram
KMZ 91 / 92
Page 45
KMZ 91 / 92
Technical data
KZL 92
KZL 91
Function display
Function diagrams
Multi-function relay with 8 functions for multi-voltage
– ON-delay timer relay
– OFF-delay timer relay with supply voltage
– Interval ON relay
– ON-delay and OFF-delay timer relay
– Repeat cycle starting with OFF/ON
– Interval ON and OFF relay
– One shot (ON-delay) relay
1 LED green, 1 LED orange
FD 239-4/1 – 9
Power supply circuit
Rated voltage UN
Rated consumption at 50 Hz and UN 24 V AC
Rated consumption at UN 24 V DC
Rated consumption at 50 Hz and UN 230 V AC
Rated consumption at UN 230 V DC
Starting current inrush A1/A2 at 24 V DC
Rated frequency
Operating voltage range
Rated current B1 - Input at 50 Hz and UN 24 V AC
Rated current B1 - Input at UN 24 V DC
Rated current B1 - Input at 50 Hz and UN 230 V AC
Rated current B1 - Input at UN 230 V DC
Minimum ON time B1
Excitation voltage B1
Release value of the Excitation voltage B1
AC/DC 24 – 230 V
1.1 VA / 0.9 W
0.7 VA / 0.5 W
0.8 W
0.5 W
2.8 VA / 1.6 W
2.3 VA / 1.5 W
1.6 W
1.4 W
approx. 250 mA
50 – 60 Hz
0.85 to 1.1 x UN
0.1 mA
0.2 mA
0.8 mA
1.5 mA
50 ms
High: 20.4 – 253 V AC/DC; Low: 0 – 2.4 V AC/DC
< 8 V AC/DC
Time circuit
Time setting / number of time ranges
Available setting range
Recovery time
Repeatability
Setting tolerance
Influence of the energizing quantity or supply voltage
Influence of the ambient temperature
Analog / 7
See table "Time ranges"
≥ 100 ms
± 1 % + ± 10 ms average value of all measured values
± 10 % + ± 50 ms
± 0.5 % + ± 10 ms
± 2 % + ± 10 ms
Function type according to IEC 60050 (445)
Output circuit
Contact assignment
Contact material
Rated operating voltage Un
Max. continuous current In
Application category according to EN 60947-5-1:1991
Permissible switching frequency
Mechanical life
Electrical life
General information
Creepage distances and clearances between the circuits
Rated impulse voltage
Overvoltage category
Degree of pollution
Rated voltage
Test voltage Ueff 50 Hz according to DIN VDE 0110-1, table A.1
Protection degree housing/terminal according to DIN VDE 0470 sec.
1:11.92
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram
Circuit diagram
Weight
Accessories
1 timed change-over contact
1 instantaneous and 1 timed
change-over contact or
2 timed change-over contacts
AgNi gold-flashed
230/125 V AC/DC
5A
AC-13: Ue 250 V AC, Ie 5 A
DC-13: Ue 24 V DC, Ie 0.1 A
AC-15: Ue 250 V AC, Ie 3 A
≤ 3600 switching cycles/h
6
10 x 10 switching cycles
4
80 x 10 switching cycles at AC 5 A, 250 V, 360 switching cycles/h
according to DIN VDE 0110-1:04.97
4 kV
III
2 outside, 2 inside
250 V AC
2.21 kV
IP 30 / IP 20
Test severity 3
–10 to +55 °C
K1-16
KS 0328/2
0.12 kg
–
KS 0328/1
Overview of devices / Part numbers
Type
KMZ 91
KMZ 92
Page 46
Rated voltage
AC/DC 24-230 V 50-60 Hz
AC/DC 24-230 V 50-60 Hz
KMZ 91 / 92
ON-delay time
See table "Time ranges"
See table "Time ranges"
Part No.
R2.066.0039.1
R2.066.0049.0
KZTH 11
KZTH 11
ON-delay single-range timer relay with semiconductor output (two-wire)
•
•
•
•
Multi voltage AC/DC 24 to 110 or 60 to 230 V
1 function: ON-delay (AV)
1 time range
1 semiconductor output
Circuit diagram
Time ranges
Available time ranges:
0.05 s
… 1
s
0.15 s
… 3
s
0.5 s
… 10 s
1.5 s
… 30 s
5s
… 100 s
Function
Function diagrams
Infinitely variable time setting is selected with a thumbwheel disc. The scale
values are absolute values related to the selected time unit.
Application example
Dimension diagram
When the control contact S is closed, the KZTH 11 is energized through
the load L and the countdown starts (see “Function diagram”). After the
timing period has elapsed, the KZTH 11 connects the load L. The load L
must be chosen so that even with lower supply voltage the holding
current will not fall below 10 mAeff and the maximum load current is ≤
0.8 Aeff. At max. load current, a voltage drop ≤ 3.5 Veff must be considered due to the KZTH.
KZTH 11
Page 47
DZ
KZTH 11
Technical data
KZTH 11
Function type according to IEC 60050 (445)
Function display
Function diagrams
ON-delay timer relay with semiconductor output for multi-voltage
–
FD 0034
Power supply circuit
Rated voltage UN
Rated consumption at 50 Hz and UN (AC)
Rated consumption DC
Starting current inrush stroke
Rated frequency
Operating voltage range
AC/DC
24 – 110 V
–
–
–
50 – 60 Hz
0.8 – 1.1 x UN
60 – 230 V
–
–
–
Time circuit
Time setting / number of time ranges
Available setting range
Recovery time 1/2
Minimum on time
Release value
Parallel loads permissible
Internal half-wave rectification
Mean value of the error
Dispersion
Influence of the energizing quantity, supply voltage
Influence of the ambient temperature
analogous/ 1
See table "Time ranges"
approx. 50 / approx. 300 ms
–
–
No
No
–
≤ ± 1 % + ± 10 ms
–
≤ 0.15 % / K
Output circuit
Contact assignment
Contact material
Rated operating voltage Un
Max. load current
Max. impulse current, 1 half wave 50 Hz
Holding current
Voltage drop in the device
Permissible switching frequency
Response time
Release time
1 semiconductor
–
–
0.8 Aeff
30 As
≤ 15 mAeff
≤ 3.5 mVeff
≤ 3600 switching cycles/h
–
–
General information
Creepage distances and clearances between the circuits
Rated impulse voltage
Overvoltage category
Degree of pollution
Rated voltage
Test voltage Ueff 50 Hz according to DIN VDE 0110-1, table A.1
Protection degree housing/terminal according to DIN VDE 0470 sec.
1:11.92
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram
Circuit diagram
Weight
Accessories
Approvals
according to DIN VDE 0110-1:04.97
–
–
3 outside, 2 inside
–
–
IP 30 / IP 20
Test severity 3
–20 to +60 °C
K1-7
KS 0164/2
0.11 kg
–
–
Overview of devices / Part numbers
Type
KZTH 11
Page 48
Rated voltage
AC/DC 60-230 V
AC/DC 24-110 V
AC/DC 60-230 V
AC/DC 24-110 V
AC/DC 60-230 V
AC/DC 60-230 V
AC/DC 60-230 V
KZTH 11
50-60 Hz
50-60 Hz
50-60 Hz
50-60 Hz
50-60 Hz
50-60 Hz
50-60 Hz
ON-delay time
0.05 ... 1 s
0.15 ... 3 s
0.5 ... 10 s
1.5 ... 30 s
5 … 100 s
Part No.
R2.060.0069.2
R2.060.0089.2
R2.060.0099.2
R2.060.0049.2
R2.060.0059.2
R2.060.0079.2
R2.060.0039.2
NGB 12
NGB 12
Fixed time flasher relay
•
•
•
•
•
Multi-voltage for AC/DC 24 to 240 V
1 function: symmetrical flashing, starts OFF
Fixed time 0.5 s / 0.5 s
2 change-over contact
2 LEDs for function display
Circuit diagram
Time ranges
Fixed time 0.5 s / 0.5 s
Function
ON-delay time
The NGB 12 timer relay is available with fixed ON and OFF time.
ON time = 0.5 s
OFF time = 0.5 s
Function diagrams
LEDs show the state of the excitation input and the position of the contacts. You can monitor the countdown on a flashing LED.
Notes
The device is designed for multi-voltage. Phase L1 or L+ must be connected to terminal A1; neutral conductor N or M must be connected to
terminal A2.
Dimension diagram
NGB 12
Page 49
NGB 12
Technical data
NGB 12
Product standard (timer relays)
Function type of the relay according to IEC 60050
Function display
Function diagrams
EN 61812-1:1999-08
445-01-06
2 LEDs green
FD 250-33
Input circuit
Rated voltage A1-A2
Rated consumption AC
Rated consumption DC
Rated voltage limits
Rated frequency fn
Release value of the input voltage (power capacity approx. 150 pF/m)
Rated current on control connection (A1)
Rated consumption on control connection (A1)
Parallel loads permissible
Internal half-wave rectification
AC/DC 24 – 240 V
3.5 VA / 1.7 W
1.6 W
70 – 110 %
50 – 60 Hz ± 5 %
≥ AC/DC 10 V; permissible line capacity 0.2 µF
1 mA
< 0.25 W
A1-A2 yes
A1-A2 no
Time circuit
Time setting / number of time ranges
Setting ranges for time delay
Cycle start
Recovery time 1/2
Repeatability (to set value)
Influence of temperature (within range)
Influence of voltage (within range)
analog / 1 Fixed time
0.5 s / 0.5 s
Pause
≤ 50 / ≤ 50 ms
≤ ± 0.01 % + ± 10 ms
≤ ± 0.002 %
≤ ± 0.002 %
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Minimum contact load
Application category according to IEC 60947-5-1
Permissible switching frequency
Mechanical life
Electrical life 20/2 A, AC 250 V, cos ϕ = 0.3
Response time / release time at excitation of A1-A2
2 change-over contacts
AgNi 90/10
AC/DC 24 – 240 V
5A
≥ AC/DC 5 V / ≥ 10 mA
AC-15 Ue AC 230 V, Ie 3 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles
6
0.12 x 10 switching cycles AC-15
40 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
according to IEC 60664-1
3 outside, 2 inside
III
AC/DC 275 V
IP 40 / IP 20
Test severity 3
-25 – +60 °C
K 3-2
KS 250-20
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0.11 kg
–
Overview of devices / Part numbers
Type
NGB 12
Page 50
Rated voltage
AC/DC 24-240 V 50-60 Hz
NGB 12
ON-delay time
0.5 s / 0.5 s
Part No.
R2.105.0029.0
NGD 31
NGD 31
Interval ON star-delta relay
•
•
•
•
•
Multi voltage for AC/DC 24 up to 240 V
1 function: star-delta switching, interval ON (EW)
4 time ranges available from 0.1 s to 100 s
2 normally open contacts
2 LEDs for function display
Circuit diagram
Time ranges
Available time ranges:
<0.1 ... 1
0.5 ... 10
1.5 ... 30
5 ... 100
s
s
s
s
Function
Setting the time delay
The desired delay time is set with a selecting wheel. It can be set using a
screwdriver.
Function diagrams
Method of operation: The NGD 31 has two sequentially switching delayed outputs for starting motors in star-delta mode. After expiration of
the pre-selected acceleration time tH for the star mode and a fixed transit
time tU the second contact switches into the operating position for the
delta mode. When the energizing quantity switches off the contact
switches into the OFF position.
The LEDs shows the switching position of the contacts. The countdown
can be monitored on the LEDs.
Notes
The device is designed for multi-voltage. Phase L1 or L+ must be connected to terminal A1; neutral conductor N or M must be connected to
terminal A2.
You can change the delay time during operation. The change is effective
immediately.
Dimension diagram
NGD 31
Page 51
NGD 31
Technical data
NGD 31
Product standard (timer relays)
Function type of the relay according to IEC 60050
Function display
Function diagrams
EN 61812-1:1999-08
445-01-10 + 445-01-08
2 LEDs green
FD 250-44
Input circuit
Rated voltage A1-A2
Rated consumption AC
Rated consumption DC
Rated voltage limits
Rated frequency fn
Release value of the input voltage (power capacity approx. 150 pF/m)
Rated current on control connection (A1)
Rated consumption on control connection (A1)
Parallel loads permissible
Internal half-wave rectification
AC/DC 24 – 240 V
3.5 VA / 1.7 W
1.6 W
70 – 110 %
50 – 60 Hz ± 5 %
≥ AC/DC 10 V; permissible line capacity 0.2 µF
1 mA
< 0.25 W
A1-A2 yes
A1-A2 no
Time circuit
Time setting / number of time ranges
Setting ranges for time delay
Constant fixed transition time
Setting tolerance
Repeatability (to set value)
Influence of temperature (within range)
Influence of voltage (within range)
analogous/ 1
See table "Time ranges"
100 ms ≤ ± 2 %
≤±5%
≤ ± 0.01 % + ± 10 ms
≤ ± 0.002 %
≤ ± 0.002 %
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Minimum contact load
Application category according to IEC 60947-5-1
Permissible switching frequency
Mechanical life
Electrical life 20/2 A, AC 250 V, cos ϕ = 0.3
Response time / release time at excitation of A1-A2
2 normally open contacts
AgNi 90/10
AC/DC 24 – 240 V
5A
≥ AC/DC 5 V / ≥ 10 mA
AC-15 Ue AC 230 V, Ie 3 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles
6
0.12 x 10 switching cycles AC-15
40 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
according to IEC 60664-1
3 outside, 2 inside
III
AC/DC 275 V
IP 40 / IP 20
Test severity 3
-25 – +60 °C
K 3-2
KS 250-21
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0.11 kg
–
Overview of devices / Part numbers
Type
NGD 31
Page 52
Rated voltage
AC/DC 24-240 V 50-60 Hz
NGD 31
ON-delay time
<0.1
...
1
0.5
...
10
1.5
...
30
5
... 100
s
s
s
s
Part No.
R2.062.0039.0
R2.062.0029.0
R2.062.0049.0
R2.062.0019.0
NGM 1004
NGM 1004
Multi-function multi-range timer relay
•
•
•
•
•
Multi voltage for AC/DC 24 up to 240 V
10 functions
Setting range from 0.1 s to 300 h divided into 16 selectable time ranges
1 change-over contact
2 LEDs for function display
Circuit diagram
Time ranges
Setting range from 0.1 s to 300 h divided into:
<0.1 ... 1 s
5 ... 100 s
1.5 ... 30 min
0.15 ... 3 s
15 ... 300 s
3 ... 60 min
0.5 ... 10 s
50 ... 1000 s
5 ... 100 min
1.5 ... 30 s
0.5 ... 10 min
0.15 ... 3 h
0.5 ...
1.5 ...
5 ...
15 ...
10
30
100
300
h
h
h
h
Function
Function diagrams
See the following pages for the function diagrams
Setting the function
The function is set with the MODE selector switch and displayed by the
function code in the window next to it. The code designation for the
function can be found in the column “Function diagrams”.
Setting the time delay
The time range is set with the RANGE selector switch and displayed in the
window next to it. The desired delay time is set with a selecting wheel.
LEDs show the state of the excitation input and the position of the contacts. You can monitor the countdown on a flashing LED.
Notes
• The device is designed for multi-voltage. Connect phase L1 or L+ to
terminal A1 and B1 and neutral N and/or M to terminal A2.
• You can change the function or delay time during operation. The change
is effective immediately.
Dimension diagram
NGM 1004
Page 53
NGM 1004
Function diagrams
Page 54
NGM 1004
Function diagrams
NGM 1004
Function diagrams
Function codes / times
Functioncode
11
11-C
12
21
22
44
81C-1s
81C-2s
82
83-1s
Functiondiagram
250-6
250-7
250-10
250-26
250-28
250-43
250-55
250-55
250-56
250-59
Recovery time (ms)
1
≤ 50
≤ 50
0
≤ 50
–
≤ 50
≤ 50
≤ 50
0
≤ 50
2
≤ 50
≤ 25
0
≤ 50
–
–
≤ 25
≤ 25
0
–
3
–
–
–
–
–
–
0
0
–
–
Minimum
ON time (ms)
1
2
≤ 25
–
–
–
≤ 25
–
≤ 25
–
≤ 25
≤ 50
≤ 25
–
–
–
–
–
≤ 25
–
≤ 25
–
NGM 1004
Page 55
NGM 1004
Technical data
NGM 1004
Product standard (timer relays)
Relay function according to IEC 60050 (445)
Function display
Function diagrams
EN 61812-1:1999-08
Multi-function relay with multi-time range
2 LEDs green
See column "Function diagrams"
Input circuit
Rated voltage A1-A2
Rated consumption AC
Rated consumption DC
Rated voltage limits
Rated frequency fn
Release value of the input voltage (power capacity approx. 150 pF/m)
Rated current on control connection (B1-A2)
Rated consumption on control connection (B1-A2)
Parallel loads permissible
Internal half-wave rectification
AC/DC 24 – 240 V
3.5 VA / 1.7 W
1.6 W
70 – 110 %
50 – 60 Hz ± 5 %
≥ AC/DC 10 V; permissible line capacity 0.2 µF
1 mA
< 0.25 W
A1-A2 yes / B1-A2 yes
A1-A2 no / B1-A2 yes
Time circuit
Time setting / number of time ranges
Setting ranges for time delay
Recovery time 1/2/3
Minimum ON time 1/2
Setting tolerance
Repeatability (to set value)
Influence of temperature (within range)
Influence of voltage (within range)
analogous/ 16
See table "Time ranges"
See table "Function codes / times"
See table "Function codes / times"
≤±5%
≤ ± 0.01 % + ± 10 ms
≤ ± 0.002 %
≤ ± 0.002 %
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Minimum contact load
Application category according to IEC 60947-5-1
Permissible switching frequency
Mechanical life
Electrical life 20/2 A, AC 250 V, cos ϕ = 0.3
Response time / release time at excitation of A1-A2
Response time / release time at excitation of B1-A2
1 change-over contacts
AgNi 90/10
AC/DC 24 – 240 V
5A
≥ AC/DC 5 V / ≥ 10 mA
AC-15 Ue AC 230 V, Ie 3 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles
6
0.12 x 10 switching cycles AC-15
40 ms
20 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
according to IEC 60664-1
3 outside, 2 inside
III
AC/DC 275 V
IP 40 / IP 20
Test severity 3
-25 – +60 °C
K 3-1
KS 250-30
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0.1 kg
–
Overview of devices / Part numbers
Type
NGM 1004
Page 56
Rated voltage
AC/DC 24-240 V 50-60 Hz
NGM 1004
ON-delay time
See table "Time ranges"
Part No.
R2.065.0039.0
NGM 1600
NGM 1600
Multi-function multi-range timer relay
Multi voltage for AC/DC 24 up to 240 V
16 functions
Setting range from 0.1 s to 300 h divided into 16 selectable time ranges
2 change-over contacts or 1 instantaneous change-over contact and
1 timed change-over contact (function-dependent)
• 3 LEDs for function display
•
•
•
•
Circuit diagram
Time ranges
Setting range from 0.1 s to 300 h divided into:
<0.1 ... 1 s
5 ... 100 s
1.5 ... 30 min
0.15 ... 3 s
15 ... 300 s
3 ... 60 min
0.5 ... 10 s
50 ... 1000 s
5 ... 100 min
1.5 ... 30 s
0.5 ... 10 min
0.15 ... 3 h
0.5 ...
1.5 ...
5 ...
15 ...
10
30
100
300
h
h
h
h
Function
Setting the function
The function is set with the MODE selector switch and displayed by the
function code in the window next to it. The code designation for the
function can be found in the column “Function diagrams”.
Function diagrams
See the following pages for the function diagrams
Setting the time delay
The time range is set with the RANGE selector switch and displayed in the
window next to it. The desired delay time is set with a selecting wheel.
LEDs show the state of the excitation input and the position of the contacts. You can monitor the countdown on a flashing LED.
Notes
• The device is designed for multi-voltage. Connect phase L1 or L+ to
terminal A1 and B1 and neutral N and/or M to terminal A2.
• You can change the function or delay time during operation.
The change is effective immediately.
Dimension diagram
NGM 1600
Page 57
NGM 1600
Function diagrams
Page 58
NGM 1600
Function diagrams
NGM 1600
Function diagrams
Function diagrams
Function codes / times
Function code
11
11-ON
11C-ON
12
12-ON
11-12
12-22
21
21-ON
21-22
22-ON
43-44
51
81-1s-ON
82-ON
83-84-1s
Function diagram
250-3
250-5
250-8
250-12
205-13
250-14
250-15
250-21
250-25
250-27
250-29
250-41
250-46
250-53
250-57
250-60
Recovery time (ms)
1
≤ 50
≤ 50
≤ 50
0
0
≤ 25
0
≤ 50
≤ 50
≤ 25
≤ 50
≤ 50
2
≤ 50
≤ 50
≤ 50
0
0
0
tWA+0
≤ 50
≤ 50
–
≤ 50
≤ 50
≤ 50
0
≤ 50
≤ 50
0
–
NGM 1600
3
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Minimum
ON time (ms)
1
2
–
–
–
–
–
–
≤ 25
≤ 25
≤ 25
≤ 25
≤ 25
–
≤ 25
–
–
–
–
–
≤ 25
–
–
–
–
–
–
–
–
–
≤ 25
–
–
–
Page 59
NGM 1600
Technical data
NGM 1600
Product standard (timer relays)
Relay function according to IEC 60050 (445)
Function display
Function diagrams
EN 61812-1:1999-08
Multi-function relay with multi-time range
3 LEDs green
See column "Function diagrams"
Input circuit
Rated voltage A1-A2
Rated consumption AC
Rated consumption DC
Rated voltage limits
Rated frequency fn
Release value of the input voltage (power capacity approx. 150 pF/m)
Rated current on control connection (B1-A2)
Rated consumption on control connection (B1-A2)
Parallel loads permissible
Internal half-wave rectification
AC/DC 24 – 240 V
3.5 VA / 1.7 W
1.6 W
70 – 110 %
50 – 60 Hz ± 5 %
≥ AC/DC 10 V; permissible line capacity 0.2 µF
1 mA
< 0.25 W
A1-A2 yes / B1-A2 yes
A1-A2 no / B1-A2 yes
Time circuit
Time setting / number of time ranges
Setting ranges for time delay
Recovery time 1/2/3
Minimum ON time 1/2
Setting tolerance
Repeatability (to set value)
Influence of temperature (within range)
Influence of voltage (within range)
analogous/ 16
See table "Time ranges"
See table "Function codes / times"
See table "Function codes / times"
≤±5%
≤ ± 0.01 % + ± 10 ms
≤ ± 0.002 %
≤ ± 0.002 %
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Minimum contact load
Application category according to IEC 60947-5-1
Permissible switching frequency
Mechanical life
Electrical life 20/2 A, AC 250 V, cos ϕ = 0.3
Response time / release time at excitation of A1-A2
Response time / release time at excitation of B1-A2
2 change-over contacts
AgNi 90/10
AC/DC 24 – 240 V
5A
≥ AC/DC 5 V / ≥ 10 mA
AC-15 Ue AC 230 V, Ie 3 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles
6
0.12 x 10 switching cycles AC-15
40 ms
20 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
according to IEC 60664-1
3 outside, 2 inside
III
AC/DC 275 V
IP 40 / IP 20
Test severity 3
–25 to +60 °C
K 3-3
KS 250-31
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0.13 kg
–
Overview of devices / Part numbers
Type
NGM 1600
Page 60
Rated voltage
AC/DC 24-240 V 50-60 Hz
NGM 1600
ON-delay time
See table "Time ranges"
Part No.
R2.065.0040.0
NGS 12
NGS 12
Electronic coupling relays
•
•
•
•
4 mono voltages AC/DC available
1 function: coupling relay
2 change-over contacts
1 LED for function control
Circuit diagram
Function
By applying supply voltage to terminals A1 and A2, the two change-over
contacts switch into the ON position. If the supply voltage is switched
off, they will switch back into the OFF position.
The LED shows the switching position of the contacts.
Notes
Phase L1 or L+ must be connected to terminal A1; neutral conductor N
or M must be connected to terminal A2.
Function diagrams
The internal switching relays are controlled electronically in order to
ensure safe switching of the coupling relays even under the most difficult
conditions.
External connection to freewheeling diodes or RC combinations is not
required, as the relays are wired internally accordingly.
Dimension diagram
NGS 12
Page 61
NGS 12
Technical data
Product standard
Function type according to IEC 60050
Function display
Function diagrams
NGS 12
EN 618122-1:1999-08
Item 2.1: switching relays
1 LED green
FD 242-1
Input circuit
Rated voltage UN
Rated consumption at 50 Hz
Rated consumption at 60 Hz
Rated consumption DC
Switch-on peak
Rated voltage limits
Rated frequency fn
Release value of the input voltage (power capacity approx. 150 pF/m)
Parallel loads permissible
Internal half-wave rectification
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Minimum contact voltage
Application category according to IEC 60947-5-1
AC/DC
AC/DC
AC/DC
24 V
28 V
110-127 V
1.1 VA / 1.0 W
1.2 VA / 1.0 W
1.7 VA / 1.4 W
1.1 VA / 1.0 W
1.2 VA / 1.0 W
1.7 VA / 1.4 W
1.0 W
1.1 W
1.1 W
0.3 A / 0.5 ms
0.3 A / 0.5 ms
0.3 A / 0.2 ms
80 – 110 %
50 – 60 Hz ± 5 %
≥ 15 % UN; permissible line capacity 0.2 µF
A1-A2 yes
A1-A2 no
Permissible switching frequency
Mechanical life
Electrical life 20/2 A, AC 250 V, cos ϕ = 0.3
Response time / release time at excitation of A1-A2
2 change-over contacts
Ag with 2 to 5 μm Au
AC/DC 250 V
5A
AC/DC 15 V
AC-15 Ue AC 230 V, Ie 3 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles
6
0.12 x 10 switching cycles AC-15
10 ms / 13 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
Approvals
according to IEC 60664-1
3 outside, 2 inside
III
250 V
IP 40 / IP 20
-25 – +60 °C
K 3-3
KS 242-1
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0.12 kg
–
–
Overview of devices / Part numbers
Type
NGS 12
Page 62
Rated voltage
AC/DC 24 V 50-60 Hz
AC/DC 28 V 50-60 Hz
AC/DC 220-240 V 50-60 Hz
AC 110-127 V 50-60 Hz
NGS 12
ON-delay time
–
–
–
–
Part No.
R2.154.0039.0
R2.154.0049.0
R2.154.0029.0
R2.154.0019.0
AC/DC
220-240 V
1.9 VA / 1.6 W
2.0 VA / 1.7 W
1.6 W
0.2 A / 0.1 ms
NGZ 11
NGZ 11
ON-delay single-range timer relay
•
•
•
•
•
Multi voltage for AC/DC 24 up to 240 V
1 function: ON-delay (AV)
13 time ranges available from 0.1 s to 100 h
1 change-over contact
2 LEDs for function display
Circuit diagram
Time ranges
Available time ranges:
<0.1 ... 1 s
5 ... 100 s
0.15 ... 3 s
15 ... 300 s
0.5 ... 10 s
50 ... 1000 s
1.5 ... 30 s
0.5 ... 10 min
1.5 ... 30 min
3 ... 60 min
0.5 ... 10 h
1.5 ... 30 h
5 ... 100 h
Function
Setting the time delay
The desired delay time is set with a selecting wheel. It can be set using a
screwdriver.
Function diagrams
LEDs show the state of the excitation input and the position of the contacts. You can monitor the countdown on a flashing LED.
Notes
The device is designed for multi-voltage. Phase L1 or L+ must be connected to terminal A1; neutral conductor N or M must be connected to
terminal A2.
You can change the delay time during operation. The change is effective
immediately.
Dimension diagram
Subject to change without further notice
NGZ 11
Page 63
NGZ 11
Technical data
NGZ 11
Product standard (timer relays)
Function type of the relay according to IEC 60050
Function display
Function diagrams
EN 61812-1:1999-08
445-01-02
2 LEDs green
FD 250-1
Input circuit
Rated voltage A1-A2
Rated consumption AC
Rated consumption DC
Rated voltage limits
Rated frequency fn
Release value of the input voltage (power capacity approx. 150 pF/m)
Rated current on control connection (A1)
Rated consumption on control connection (A1)
Parallel loads permissible
Internal half-wave rectification
AC/DC 24 – 240 V
3.5 VA / 1.7 W
1.6 W
70 – 110 %
50 – 60 Hz ± 5 %
≥ AC/DC 10 V; permissible line capacity 0.2 µF
1 mA
< 0,25 W
A1-A2 yes
A1-A2 no
Time circuit
Time setting / number of time ranges
Setting ranges for time delay
Recovery time 1/2
Minimum ON time 1/2
Setting tolerance
Repeatability (to set value)
Influence of temperature (within range)
Influence of voltage (within range)
analogous/ 1
See table "Time ranges"
≤ 50 / ≤ 50 ms
– / – ms
≤±5%
≤ ± 0,01 % + ± 10 ms
≤ ± 0,002 %
≤ ± 0,002 %
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Minimum contact load
Application category according to IEC 60947-5-1
Permissible switching frequency
Mechanical life
Electrical life 20/2 A, AC 250 V, cos ϕ = 0.3
Response time / release time at excitation of A1-A2
1 change-over contacts
AgNi 90/10
AC/DC 24 – 240 V
5A
≥ AC/DC 5 V / ≥ 10 mA
AC-15 Ue AC 230 V, Ie 3 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles
6
0.12 x 10 switching cycles AC-15
40 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
according to IEC 60664-1
3 outside, 2 inside
III
AC/DC 275 V
IP 40 / IP 20
Test severity 3
-25 – +60 °C
K 3-1
KS 250-1
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0.1 kg
–
Overview of devices / Part numbers
Type
NGZ 11
Page 64
Rated voltage
AC/DC 24-240 V 50-60 Hz
NGZ 11
ON-delay time
<0.1
...
1
0.15
...
3
0.5
...
10
1.5
...
30
5
... 100
15
... 300
50
... 1000
0.5
...
10
1.5
...
30
3
...
60
0.5
...
10
1.5
...
30
5
... 100
s
s
s
s
s
s
s
min
min
min
h
h
h
Part No.
R2.064.0079.0
R2.064.0129.0
R2.064.0069.0
R2.064.0119.0
R2.064.0079.0
R2.064.0039.0
R2.064.0019.0
R2.064.0059.0
R2.064.0109.0
R2.064.0139.0
R2.064.0049.0
R2.064.0099.0
R2.064.0029.0
Subject to change without further notice
NGZ 12
NGZ 12
ON-delay single-range timer relay
•
•
•
•
•
Multi voltage for AC/DC 24 up to 240 V
1 function: ON-delay (AV)
13 time ranges available from 0.1 s to 100 h
2 change-over contact
2 LEDs for function display
Circuit diagram
Time ranges
Available time ranges:
<0.1 ... 1 s
5 ... 100 s
0.15 ... 3 s
15 ... 300 s
0.5 ... 10 s
50 ... 1000 s
1.5 ... 30 s
0.5 ... 10 min
1.5 ... 30 min
3 ... 60 min
0.5 ... 10 h
1.5 ... 30 h
5 ... 100 h
Function
Setting the time delay
The desired delay time is set with a selecting wheel. It can be set using a
screwdriver.
Function diagrams
LEDs show the state of the excitation input and the position of the contacts. You can monitor the countdown on a flashing LED.
Notes
The device is designed for multi-voltage. Phase L1 or L+ must be connected to terminal A1; neutral conductor N or M must be connected to
terminal A2.
You can change the delay time during operation. The change is effective
immediately.
Dimension diagram
Subject to change without further notice
NGZ 12
Page 65
NGZ 12
Technical data
NGZ 12
Product standard (timer relays)
Function type of the relay according to IEC 60050
Function display
Function diagrams
EN 61812-1:1999-08
445-01-02
2 LEDs green
FD 250-2
Input circuit
Rated voltage A1-A2
Rated consumption AC
Rated consumption DC
Rated voltage limits
Rated frequency fn
Release value of the input voltage (power capacity approx. 150 pF/m)
Rated current on control connection (A1)
Rated consumption on control connection (A1)
Parallel loads permissible
Internal half-wave rectification
AC/DC 24 – 240 V
3.5 VA / 1.7 W
1.6 W
70 – 110 %
50 – 60 Hz ± 5 %
≥ AC/DC 10 V; permissible line capacity 0.2 µF
1 mA
< 0.25 W
A1-A2 yes
A1-A2 no
Time circuit
Time setting / number of time ranges
Setting ranges for time delay
Recovery time 1/2
Minimum ON time 1/2
Setting tolerance
Repeatability (to set value)
Influence of temperature (within range)
Influence of voltage (within range)
analogous/ 1
See table "Time ranges"
≤ 50 / ≤ 50 ms
–/–
≤±5%
≤ ± 0.01 % + ± 10 ms
≤ ± 0.002 %
≤ ± 0.002 %
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Minimum contact load
Application category according to IEC 60947-5-1
Permissible switching frequency
Mechanical life
Electrical life 20/2 A, AC 250 V, cos ϕ = 0.3
Response time / release time at excitation of A1-A2
2 change-over contacts
AgNi 90/10
AC/DC 24 – 240 V
5A
≥ AC/DC 5 V / ≥ 10 mA
AC-15 Ue AC 230 V, Ie 3 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles
6
0.12 x 10 switching cycles AC-15
40 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
according to IEC 60664-1
3 outside, 2 inside
III
AC/DC 275 V
IP 40 / IP 20
Test severity 3
-25 – +60 °C
K 3-2
KS 250-3
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0.11 kg
–
Overview of devices / Part numbers
Type
NGZ 12
Page 66
Rated voltage
AC/DC 24-240 V 50-60 Hz
NGZ 12
ON-delay time
<0.1
...
1
0.15
...
3
0.5
...
10
1.5
...
30
5
... 100
15
... 300
50
... 1000
0.5
...
10
1.5
...
30
3
...
60
0.5
...
10
1.5
...
30
5
... 100
s
s
s
s
s
s
s
min
min
min
h
h
h
Part No.
R2.064.0219.0
R2.064.0269.0
R2.064.0209.0
R2.064.0259.0
R2.064.0179.0
R2.064.0229.0
R2.064.0159.0
R2.064.0199.0
R2.064.0249.0
R2.064.0279.0
R2.064.0189.0
R2.064.0239.0
R2.064.0169.0
Subject to change without further notice
NGZ 12 S
NGZ 12 S
ON-delay single-range timer relay
•
•
•
•
•
Multi voltage for AC/DC 24 up to 240 V
1 function: ON-delay (AV)
13 time ranges available from 0.1 s to 100 h
1 instantaneous and 1 timed change-over contact
2 LEDs for function display
Circuit diagram
Time ranges
Available time ranges:
<0.1 ... 1 s
5 ... 100 s
0.15 ... 3 s
15 ... 300 s
0.5 ... 10 s
50 ... 1000 s
1.5 ... 30 s
0.5 ... 10 min
1.5 ... 30 min
3 ... 60 min
0.5 ... 10 h
1.5 ... 30 h
5 ... 100 h
Function
Setting the time delay
The desired delay time is set with a selecting wheel. It can be set using a
screwdriver.
Function diagrams
LEDs show the state of the excitation input and the position of the contacts. You can monitor the countdown on a flashing LED.
Notes
The device is designed for multi-voltage. Phase L1 or L+ must be connected to terminal A1; neutral conductor N or M must be connected to
terminal A2.
You can change the delay time during operation. The change is effective
immediately.
Dimension diagram
Subject to change without further notice
NGZ 12 S
Page 67
DZ
NGZ 12 S
Technical data
NGZ 12-S
Product standard (timer relays)
Function type of the relay according to IEC 60050
Function display
Function diagrams
EN 61812-1:1999-08
445-01-02 + 445-04-05
2 LEDs green
FD 250-4
Input circuit
Rated voltage A1-A2
Rated consumption AC
Rated consumption DC
Rated voltage limits
Rated frequency fn
Release value of the input voltage (power capacity approx. 150 pF/m)
Rated current on control connection (A1)
Rated consumption on control connection (A1)
Parallel loads permissible
Internal half-wave rectification
AC/DC 24 – 240 V
3.5 VA / 1.7 W
1.6 W
70 – 110 %
50 – 60 Hz ± 5 %
≥ AC/DC 10 V; permissible line capacity 0.2 µF
1 mA
< 0.25 W
A1-A2 yes
A1-A2 no
Time circuit
Time setting / number of time ranges
Setting ranges for time delay
Recovery time 1/2
Minimum ON time 1/2
Setting tolerance
Repeatability (to set value)
Influence of temperature (within range)
Influence of voltage (within range)
analogous/ 1
See table "Time ranges"
≤ 50 / ≤ 50 ms
– / – ms
≤±5%
≤ ± 0.01 % + ± 10 ms
≤ ± 0.002 %
≤ ± 0.002 %
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Minimum contact load
Application category according to IEC 60947-5-1
Permissible switching frequency
Mechanical life
Electrical life 20/2 A, AC 250 V, cos ϕ = 0.3
Response time / release time at excitation of A1-A2
1 instantaneous and 1 timed change-over contact
AgNi 90/10
AC/DC 24 – 240 V
5A
≥ AC/DC 5 V / ≥ 10 mA
AC-15 Ue AC 230 V, Ie 3 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles
6
0.12 x 10 switching cycles AC-15
40 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
according to IEC 60664-1
3 outside, 2 inside
III
AC/DC 275 V
IP 40 / IP 20
Test severity 3
-25 – +60 °C
K 3-2
KS 250-5
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0.1 kg
–
Overview of devices / Part numbers
Type
NGZ 12-S
Page 68
Rated voltage
AC/DC 24-240 V 50-60 Hz
NGZ 12 S
ON-delay time
<0.1
...
1
0.15
...
3
0.5
...
10
1.5
...
30
5
... 100
15
... 300
50
... 1000
0.5
...
10
1.5
...
30
3
...
60
0.5
...
10
1.5
...
30
5
... 100
s
s
s
s
s
s
s
min
min
min
h
h
h
Part No.
R2.064.0349.0
R2.064.0399.0
R2.064.0339.0
R2.064.0389.0
R2.064.0309.0
R2.064.0359.0
R2.064.0289.0
R2.064.0329.0
R2.064.0379.0
R2.064.0409.0
R2.064.0319.0
R2.064.0369.0
R2.064.0299.0
Subject to change without further notice
NGZ 71
NGZ 71
ON-delay multi-range timer relay
•
•
•
•
•
Multi voltage for AC/DC 24 up to 240 V
1 function: ON-delay (AV)
Setting range from 0.1 s to 300 h divided into 16 selectable time ranges
1 change-over contacts
2 LEDs for function display
Circuit diagram
Time ranges
Setting range from 0.1 s to 300 h divided into:
<0.1 ... 1 s
5 ... 100 s
1.5 ... 30 min
0.15 ... 3 s
15 ... 300 s
3 ... 60 min
0.5 ... 10 s
50 ... 1000 s
5 ... 100 min
1.5 ... 30 s
0.5 ... 10 min
0.15 ... 3 h
0.5 ...
1.5 ...
5 ...
15 ...
10
30
100
300
h
h
h
h
Function
Setting the time delay
The time range is set with the RANGE selector switch and displayed in the
window next to it. The desired delay time is set with a selecting wheel.
Function diagrams
LEDs show the state of the excitation input and the position of the contacts. You can monitor the countdown on a flashing LED.
Notes
The device is designed for multi-voltage. Phase L1 or L+ must be connected to terminal A1; neutral conductor N or M must be connected to
terminal A2.
You can change the delay time during operation. The change is effective
immediately.
Dimension diagram
Subject to change without further notice
NGZ 71
Page 69
DZ
NGZ 71
Technical data
NGZ 71
Product standard (timer relays)
Function type of the relay according to IEC 60050
Function display
Function diagrams
EN 61812-1:1999-08
445-01-02
2 LEDs green
FD 250-1
Input circuit
Rated voltage A1-A2
Rated consumption AC
Rated consumption DC
Rated voltage limits
Rated frequency fn
Release value of the input voltage (power capacity approx. 150 pF/m)
Rated current on control connection (A1)
Rated consumption on control connection (A1)
Parallel loads permissible
Internal half-wave rectification
AC/DC 24 – 240 V
3.5 VA / 1.7 W
1.6 W
70 – 110 %
50 – 60 Hz ± 5 %
≥ AC/DC 10 V; permissible line capacity 0.2 µF
1 mA
< 0.25 W
A1-A2 yes
A1-A2 no
Time circuit
Time setting / number of time ranges
Setting ranges for time delay
Recovery time 1/2
Minimum ON time 1/2
Setting tolerance
Repeatability (to set value)
Influence of temperature (within range)
Influence of voltage (within range)
analogous/ 16
See table "Time ranges"
≤ 50 / ≤ 50 ms
– / – ms
≤±5%
≤ ± 0.01 % + ± 10 ms
≤ ± 0.002 %
≤ ± 0.002 %
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Minimum contact load
Application category according to IEC 60947-5-1
Permissible switching frequency
Mechanical life
Electrical life 20/2 A, AC 250 V, cos ϕ = 0.3
Response time / release time at excitation of A1-A2
1 change-over contacts
AgNi 90/10
AC/DC 24 – 240 V
5A
≥ AC/DC 5 V / ≥ 10 mA
AC-15 Ue AC 230 V, Ie 3 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles
6
0.12 x 10 switching cycles AC-15
40 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
according to IEC 60664-1
3 outside, 2 inside
III
AC/DC 275 V
IP 40 / IP 20
Test severity 3
-25 – +60 °C
K 3-1
KS 250-1
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0.1 kg
–
Overview of devices / Part numbers
Type
NGZ 71
Page 70
Rated voltage
AC/DC 24-240 V 50-60 Hz
NGZ 71
ON-delay time
See table "Time ranges"
Part No.
R2.065.0069.0
Subject to change without further notice
NGZ 110
Timer and switching relays
Zeitrelais
Rückfallverzögerung
Register:
NGZ 110
OFF-delay single-range timer relay without auxiliary supply
•
•
•
•
•
3 Single supply voltages for AC/DC available
1 Function: OFF-delay (RV)
6 time ranges available from 0,05 to 300 s
1 change-over contacts
1 LED for function display
Circuit diagram
Time ranges
Available time ranges:
0,05 ... 1 s
0,15 ... 3 s
0,5 ... 10 s
1,5 ... 30 s
5 ... 100 s
15 ... 300 s
Function
Setting the time delay
The desired delay time is set with a selecting wheel. It can be set using a
screwdriver.
Function diagrams
The LED indicates the status of the input excitation.
Notes
The unit is designed for single voltage. Terminal A1 must be connected
to phase L1 or L+. Terminal A2 must be connected to the neutral conductor N or M.
An adjustment of the ON-delay time during the operational sequence is
admissible, the adjustment is effective immediately.
Dimension diagram
Subject to change without further notice
NGZ 110
Page 71
NGZ 110
Technical data
Product standard (timer relays)
Function type of the relay according to IEC 60050
Function display
Function diagrams
Input circuit
NGZ 110
EN 61812-1:1999-08
445-01-03
1 LED grün
FD 250-16
Rated voltage A1-A2
Rated consumption AC
Rated consumption at 50 Hz und UA1/A2 (AC)
Rated consumption DC
Starting current inrushstoß
Rated voltage limits
Rated frequency fn
Release value of the input voltage
Parallel loads permissible
Internal half-wave rectification
AC/DC
AC
24 V
110-127 V
0,1 VA
0,8 VA
0,06 W
0,5 W
0,06 W
0,4 A / 40 ms
0,1 A / 40 ms
80 bis 110 %
50 – 60 Hz ± 5 %
–
A1-A2 yes
A1-A2 yes
Time circuit
Time setting / number of time ranges
Setting ranges for time delay
Recovery time 1
Minimum ON time 1/2
Setting tolerance
Repeatability (to set value)
Influence of temperature (within range)
Influence of voltage (within range)
analogous/ 1
See table "Time ranges"
approx. 250 ms
approx. 200 / approx. 200 ms (bei 300 s: approx. 500 / approx. 500 ms)
≤±5%
≤ ± 1 % + ± 10 ms
≤ ± 0,04 %
≤ ± 0,05 %
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Application category according to IEC 60947-5-1
AC
230-240 V
1,3 VA
0,9 W
0,05 A / 150 ms
Permissible switching frequency
Mechanical life
Electrical life
Response time / release time at excitation of A1-A2
1 change-over contacts
AgNi 0,15+HVT
AC/DC 230/230 V
5A
AC-15 Ue AC 230 V, Ie 2 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
10 x 10 switching cycles
5
1 x 10 switching cycles bei Nennlast
15 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
according to IEC 60664-1
3 outside, 2 inside
III
AC/DC 275 V
IP 40 / IP 20
Test severity 3
-25 – +60 °C
K 3-1
KS 250-10
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0,11 kg
–
Overview of devices / Part numbers
Typ
NGZ 110
Nennspannung
AC/DC 24 V 50-60 Hz
AC/DC 110-127 V 50-60 Hz
AC/DC 230-240 V 50-60 Hz
Page 72
Zeitverzögerung
0,05 ...
1
0,15 ...
3
0,5 ...
10
1,5 ...
30
5
... 100
15
... 300
0,05 ...
1
0,15 ...
3
0,5 ...
10
1,5 ...
30
5
... 100
15
... 300
0,05 ...
1
0,15 ...
3
0,5 ...
10
1,5 ...
30
5
... 100
15
... 300
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
Bestellnummer
R2.067.0099.0
R2.067.0189.0
R2.067.0069.0
R2.067.0159.0
R2.067.0039.0
R2.067.0129.0
R2.067.0079.0
R2.067.0169.0
R2.067.0049.0
R2.067.0139.0
R2.067.0019.0
R2.067.0109.0
R2.067.0089.0
R2.067.0179.0
R2.067.0059.0
R2.067.0149.0
R2.067.0029.0
R2.067.0119.0
Subject to change without further notice
NGZ 310
Timer and switching relays
Zeitrelais
Rückfallverzögerung
Register:
NGZ 310
OFF-delay single-range timer relay with auxiliary supply
•
•
•
•
•
Multi voltage for AC/DC 24 up to 240 V
1 function: OFF-delay (RV)
13 time ranges available from 0.1 s to 100 h
1 change-over contact
2 LEDs for function display
Circuit diagram
Time ranges
Available time ranges:
<0.1 ... 1 s
5 ... 100 s
0.15 ... 3 s
15 ... 300 s
0.5 ... 10 s
50 ... 1000 s
1.5 ... 30 s
0.5 ... 10 min
1.5 ... 30 min
3 ... 60 min
0.5 ... 10 h
1.5 ... 30 h
5 ... 100 h
Function
Setting the time delay
The desired delay time is set with a selecting wheel. It can be set using a
screwdriver.
Function diagrams
LEDs show the state of the excitation input and the position of the contacts. You can monitor the countdown on a flashing LED.
Notes
The device is designed for multi-voltage. Phase L1 or L+ must be connected to terminal A1; neutral conductor N or M must be connected to
terminal A2.
You can change the delay time during operation. The change is effective
immediately.
Dimension diagram
Subject to change without further notice
NGZ 310
Page 73
NGZ 310
Technical data
NGZ 310
Product standard (timer relays)
Function type of the relay according to IEC 60050
Function display
Function diagrams
EN 61812-1:1999-08
445-01-04 + 445-03-02
2 LEDs green
FD 250-10
Input circuit
Rated voltage A1-A2
Rated consumption AC
Rated consumption DC
Rated voltage limits
Rated frequency fn
Release value of the input voltage (power capacity approx. 150 pF/m)
Rated current on control connection (B1-A2)
Rated consumption on control connection (B1-A2)
Parallel loads permissible
Internal half-wave rectification
AC/DC 24 – 240 V
3.5 VA / 1.7 W
1.6 W
70 – 110 %
50 – 60 Hz ± 5 %
≥ AC/DC 10 V; permissible line capacity 0.2 µF
1 mA
< 0.25 W
A1-A2 yes / B1-A1 yes
A1-A2 no / B1-A1 yes
Time circuit
Time setting / number of time ranges
Setting ranges for time delay
Recovery time 1/2
Minimum ON time 1/2
Setting tolerance
Repeatability (to set value)
Influence of temperature (within range)
Influence of voltage (within range)
analogous/ 1
See table "Time ranges"
0 / 0 ms
≤ 25 / – ms
≤±5%
≤ ± 0.01 % + ± 10 ms
≤ ± 0.002 %
≤ ± 0.002 %
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Minimum contact load
Application category according to IEC 60947-5-1
Permissible switching frequency
Mechanical life
Electrical life 20/2 A, AC 250 V, cos ϕ = 0.3
Response time / release time at excitation of A1-A2
Response time / release time at excitation of B1-A2
1 change-over contacts
AgNi 90/10
AC/DC 24 – 240 V
5A
≥ AC/DC 5 V / ≥ 10 mA
AC-15 Ue AC 230 V, Ie 3 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles
6
0.12 x 10 switching cycles AC-15
40 ms
20 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
according to IEC 60664-1
3 outside, 2 inside
III
AC/DC 275 V
IP 40 / IP 20
Test severity 3
-25 – +60 °C
K 3-1
KS 250-8
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0.1 kg
–
Overview of devices / Part numbers
Type
NGZ 310
Page 74
Rated voltage
AC/DC 24-240 V 50-60 Hz
NGZ 310
ON-delay time
<0.1
...
1
0.15
...
3
0.5
...
10
1.5
...
30
5
... 100
15
... 300
50
... 1000
0.5
...
10
1.5
...
30
3
...
60
0.5
...
10
1.5
...
30
5
... 100
s
s
s
s
s
s
s
min
min
min
h
h
h
Part No.
R2.067.0329.0
R2.067.0379.0
R2.067.0319.0
R2.067.0369.0
R2.067.0289.0
R2.067.0339.0
R2.067.0269.0
R2.067.0309.0
R2.067.0359.0
R2.067.0389.0
R2.067.0299.0
R2.067.0349.0
R2.067.0279.0
Subject to change without further notice
NGZ 710
NGZ 710
OFF-delay multi-range timer relay with auxiliary supply
•
•
•
•
•
Multi voltage for AC/DC 24 up to 240 V
1 function: OFF-delay (RV) with auxiliary supply
Setting range from 0.1 s to 300 h divided into 16 selectable time ranges
1 change-over contact
2 LEDs for function display
Circuit diagram
Time ranges
Setting range from 0.1 s to 300 h divided into:
<0.1 ... 1 s
5 ... 100 s
1.5 ... 30 min
0.15 ... 3 s
15 ... 300 s
3 ... 60 min
0.5 ... 10 s
50 ... 1000 s
5 ... 100 min
1.5 ... 30 s
0.5 ... 10 min
0.15 ... 3 h
0.5 ...
1.5 ...
5 ...
15 ...
10
30
100
300
h
h
h
h
Function
Function diagrams
Setting the time delay
The time range is set with the RANGE selector switch and displayed in the
window next to it. The desired delay time is set with a selecting wheel.
LEDs show the state of the excitation input and the position of the contacts. You can monitor the countdown on a flashing LED.
Notes
The device is designed for multi-voltage. Phase L1 or L+ must be connected to terminal A1; neutral conductor N or M must be connected to
terminal A2.
You can change the delay time during operation. The change is effective
immediately.
Dimension diagram
Subject to change without further notice
NGZ 710
Page 75
NGZ 710
Technical data
NGZ 710
Product standard (timer relays)
Function type of the relay according to IEC 60050
Function display
Function diagrams
EN 61812-1:1999-08
445-01-04 + 445-03-02
2 LEDs green
FD 250-10
Input circuit
Rated voltage A1-A2
Rated consumption AC
Rated consumption DC
Rated voltage limits
Rated frequency fn
Release value of the input voltage (power capacity approx. 150 pF/m)
Rated current on control connection (B1-A2)
Rated consumption on control connection (B1-A2)
Parallel loads permissible
Internal half-wave rectification
AC/DC 24 – 240 V
3.5 VA / 1.7 W
1.6 W
70 – 110 %
50 – 60 Hz ± 5 %
≥ AC/DC 10 V; permissible line capacity 0.2 µF
1 mA
< 0.25 W
A1-A2 yes / B1-A2 yes
A1-A2 no / B1-A2 yes
Time circuit
Time setting / number of time ranges
Setting ranges for time delay
Recovery time 1/2/3
Minimum ON time 1/2
Setting tolerance
Repeatability (to set value)
Influence of temperature (within range)
Influence of voltage (within range)
analogous/ 16
See table "Time ranges"
0 / 0 / – ms
≤ 25 / – ms
≤±5%
≤ ± 0.01 % + ± 10 ms
≤ ± 0.002 %
≤ ± 0.002 %
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Minimum contact load
Application category according to IEC 60947-5-1
Permissible switching frequency
Mechanical life
Electrical life 20/2 A, AC 250 V, cos ϕ = 0.3
Response time / release time at excitation of A1-A2
Response time / release time at excitation of B1-A2
1 change-over contacts
AgNi 90/10
AC/DC 24 – 240 V
5A
≥ AC/DC 5 V / ≥ 10 mA
AC-15 Ue AC 230 V, Ie 3 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles
6
0.12 x 10 switching cycles AC-15
40 ms
20 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
according to IEC 60664-1
3 outside, 2 inside
III
AC/DC 275 V
IP 40 / IP 20
Test severity 3
-25 – +60 °C
K 3-1
KS 250-8
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0.1 kg
–
Overview of devices / Part numbers
Type
NGZ 710
Page 76
Rated voltage
AC/DC 24-240 V 50-60 Hz
NGZ 710
ON-delay time
See table "Time ranges"
Part No.
R2.065.0079.0
Subject to change without further notice
NGZ 720
Timer and switching relays
Zeitrelais
Rückfallverzögerung
Register:
NGZ 720
OFF-delay multi-range timer relay with auxiliary supply
•
•
•
•
•
Multi voltage for AC/DC 24 up to 240 V
1 function: OFF-delay (RV) with auxiliary supply
Setting range from 0.1 s to 300 h divided into 16 selectable time ranges
2 change-over contact
2 LEDs for function display
Circuit diagram
Time ranges
Setting range from 0.1 s to 300 h divided into:
<0.1 ... 1 s
5 ... 100 s
1.5 ... 30 min
0.15 ... 3 s
15 ... 300 s
3 ... 60 min
0.5 ... 10 s
50 ... 1000 s
5 ... 100 min
1.5 ... 30 s
0.5 ... 10 min
0.15 ... 3 h
0.5 ...
1.5 ...
5 ...
15 ...
10
30
100
300
h
h
h
h
Function
Setting the time delay
The time range is set with the RANGE selector switch and displayed in the
window next to it. The desired delay time is set with a selecting wheel.
Function diagrams
LEDs show the state of the excitation input and the position of the contacts. You can monitor the countdown on a flashing LED.
Notes
The device is designed for multi-voltage. Phase L1 or L+ must be connected to terminal A1; neutral conductor N or M must be connected to
terminal A2.
You can change the delay time during operation. The change is effective
immediately.
Dimension diagram
Subject to change without further notice
NGZ 720
Page 77
NGZ 720
Technical data
NGZ 720
Product standard (timer relays)
Function type of the relay according to IEC 60050
Function display
Function diagrams
EN 61812-1:1999-08
445-01-04 + 445-03-02
2 LEDs green
FD 250-11
Input circuit
Rated voltage A1-A2
Rated consumption AC
Rated consumption DC
Rated voltage limits
Rated frequency fn
Release value of the input voltage (power capacity approx. 150 pF/m)
Rated current on control connection (B1-A2)
Rated consumption on control connection (B1-A2)
Parallel loads permissible
Internal half-wave rectification
AC/DC 24 – 240 V
3.5 VA / 1.7 W
1.6 W
70 – 110 %
50 – 60 Hz ± 5 %
≥ AC/DC 10 V; permissible line capacity 0.2 µF
1 mA
< 0.25 W
A1-A2 yes / B1-A2 yes
A1-A2 no / B1-A2 yes
Time circuit
Time setting / number of time ranges
Setting ranges for time delay
Recovery time 1/2/3
Minimum ON time 1/2
Setting tolerance
Repeatability (to set value)
Influence of temperature (within range)
Influence of voltage (within range)
analogous/ 16
See table "Time ranges"
0 / 0 / – ms
≤ 25 / – ms
≤±5%
≤ ± 0.01 % + ± 10 ms
≤ ± 0.002 %
≤ ± 0.002 %
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Minimum contact load
Application category according to IEC 60947-5-1
Permissible switching frequency
Mechanical life
Electrical life 20/2 A, AC 250 V, cos ϕ = 0.3
Response time / release time at excitation of A1-A2
Response time / release time at excitation of B1-A2
2 change-over contacts
AgNi 90/10
AC/DC 24 – 240 V
5A
≥ AC/DC 5 V / ≥ 10 mA
AC-15 Ue AC 230 V, Ie 3 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles
6
0.12 x 10 switching cycles AC-15
40 ms
20 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
according to IEC 60664-1
3 outside, 2 inside
III
AC/DC 275 V
IP 40 / IP 20
Test severity 3
-25 – +60 °C
K 3-3
KS 250-9
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0.13 kg
–
Overview of devices / Part numbers
Type
NGZ 720
Page 78
Rated voltage
AC/DC 24-240 V 50-60 Hz
NGZ 720
ON-delay time
See table "Time ranges"
Part No.
R2.065.0099.0
Subject to change without further notice
NGZP 32
NGZP 32
ON-delay single-range timer relay with remote potentiometer connection
•
•
•
•
•
•
Multi voltage for AC/DC 24 to 240 V
1 function: ON-delay (AV)
13 time ranges available from 0.1 s to 100 h
Remote potentiometer connection
2 change-over contact
2 LEDs for function display
Circuit diagram
Time ranges
Available time ranges:
<0.1 ... 1 s
5 ... 100 s
0.15 ... 3 s
15 ... 300 s
0.5 ... 10 s
50 ... 1000 s
1.5 ... 30 s
0.5 ... 10 min
1.5 ... 30 min
3 ... 60 min
0.5 ... 10 h
1.5 ... 30 h
5 ... 100 h
Function
Setting the time delay
The desired delay time is set with a selecting wheel. It can be set using a
screwdriver.
Function diagrams
Connecting a remote potentiometer allows you to set parameters at
greater distances. When a remote potentiometer is used, the time selecting wheel is to be set to the right-hand stop above the largest value.
Operation without remote potentiometer does not require a jumper on
the device.
LEDs show the state of the excitation input and the position of the contacts. You can monitor the countdown on a flashing LED.
Notes
The device is designed for multi-voltage. Phase L1 or L+ must be connected to terminal A1; neutral conductor N or M must be connected to
terminal A2.
You can change the delay time during operation. The change is effective
immediately.
Dimension diagram
Accessories
Accessories:
Remote potentiometer FP 10 k
Subject to change without further notice
NGZP 32
Page 79
NGZP 32
Technical data
NGZP 32
Product standard (timer relays)
Function type of the relay according to IEC 60050
Function display
Function diagrams
EN 61812-1:1999-08
445-01-02
2 LEDs green
FD 250-2
Input circuit
Rated voltage A1-A2
Rated consumption AC
Rated consumption DC
Rated voltage limits
Rated frequency fn
Release value of the input voltage (power capacity approx. 150 pF/m)
Rated current on control connection (A1)
Rated consumption on control connection (A1)
Parallel loads permissible
Internal half-wave rectification
AC/DC 24 – 240 V
3.5 VA / 1.7 W
1.6 W
70 – 110 %
50 – 60 Hz ± 5 %
≥ AC/DC 10 V; permissible line capacity 0.2 µF
1 mA
< 0.25 W
A1-A2 yes
A1-A2 no
Time circuit
Time setting / number of time ranges
Setting ranges for time delay
Recovery time 1/2
Minimum ON time 1/2
Setting tolerance
Repeatability (to set value)
Influence of temperature (within range)
Influence of voltage (within range)
analog (intern + extern) / 1
See table "Time ranges"
≤ 50 / ≤ 50 ms
–/–
≤±5%
≤ ± 0.01 % + ± 10 ms
≤ ± 0.002 %
≤ ± 0.002 %
Output circuit
Contact assignment
Contact material
Rated operating voltage
Rated value for limiting continuous current Ith
Minimum contact load
Application category according to IEC 60947-5-1
Permissible switching frequency
Mechanical life
Electrical life 20/2 A, AC 250 V, cos ϕ = 0.3
Response time / release time at excitation of A1-A2
2 change-over contacts
AgNi 90/10
AC/DC 24 – 240 V
5A
≥ AC/DC 5 V / ≥ 10 mA
AC-15 Ue AC 230 V, Ie 3 A
DC-13 Ue DC 24 V, Ie 2 A
≤ 3600 switching cycles/h
6
30 x 10 switching cycles
6
0.12 x 10 switching cycles AC-15
40 ms
Other data
Creepage distances and clearances
Degree of pollution
Overvoltage category
Rated voltage
Degree of protection according to IEC 60529 housing/terminals
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram (housing)
Circuit diagram of the terminals
Wire ranges
stranded or solid
stranded with ferrules
Weight
Accessories
according to IEC 60664-1
3 outside, 2 inside
III
AC/DC 275 V
IP 40 / IP 20
Test severity 3
-25 – +60 °C
K 3-3
KS 250-4
2
1 x 0.2 – 6 or 2 x 0.2 to 2.5 mm
2
1 x 0.4 – 4 or 2 x 0.2 to 1.5 mm
0.14 kg
Remote potentiometer FP 10 k
Overview of devices / Part numbers
Type
NGZP 32
Page 80
Rated voltage
AC/DC 24-240 V 50-60 Hz
NGZP 32
ON-delay time
<0.1
...
1
0.15
...
3
0.5
...
10
1.5
...
30
5
... 100
15
... 300
50
... 1000
0.5
...
10
1.5
...
30
3
...
60
0.5
...
10
1.5
...
30
5
... 100
s
s
s
s
s
s
s
min
min
min
h
h
h
Part No.
R2.064.0619.0
R2.064.0669.0
R2.064.0609.0
R2.064.0659.0
R2.064.0579.0
R2.064.0629.0
R2.064.0559.0
R2.064.0599.0
R2.064.0649.0
R2.064.0679.0
R2.064.0589.0
R2.064.0639.0
R2.064.0569.0
Subject to change without further notice
SSP 56
SSP 56
SSP 33
SSP 72
SSP 34
Flip-flop relay
SSP 56, SSP 72
SSP 33, SSP 34
Wiring diagram
• Devices for Mono voltage
• Function: flip-flop relay
• contact assembly:
SSP 56 = 3 NO and 3 NC contacts
SSP 72 = 2 changers
SSP 33 = 3 changers
SSP 34 = 4 changers
Function
The flip-flop relay consists of two separate magnet systems which mutually
mechanically latch shut. Upon impulse or constant excitation of the magnet system equipped with contacts, the contacts toggle to the operating
position. At the same time, the catches on the relay anchors latch shut,
so that even in the event of a voltage failure and/or a voltage interruption, the operating position of the contacts is maintained. Upon excitation
of the non-equipped magnet system, the latch is released and the contacts return to the default position.
On the device types SSP 56 and SSP 72, a lever protruding from the front
plate prompts a manual shift in the magnet system and indicates the
position of the magnet and/or the contact. On the device types SSP 33
and SSP 34, two pushbuttons are available for this purpose.
The relay contacts have no preferred position. If both inductors are excited
simultaneously, the operating position of the contacts is maintained.
Function diagram
Dimensional drawings
Subject to change without further notice
SSP 56
Page 81
SSP 56
Technical Data
SSP 56
Function type according to DIN VDE 0435 Section 110:04.89
Function indicator
Function diagram
Supply circuit
Nominal voltage UN
Rated output Re 1 at 50 Hz and UN (AC) Power-on
SSP 72
Electro-mechanical flip-flop relay for Mono voltage
Item 2.4: bi-stable relay
Positioning lever Positioning lever Pushbuttons
FD 0022a
Rated output Re 2 at 50 Hz and UN (AC) Power-on
Rated output Re 2 at 50 Hz and UN (AC) Hold
Nominal frequency
Operating voltage range
see Device overview
approx. 13 VA / approx. 13 VA /
approx. 4.5 W
approx. 4.5 W
approx. 4 VA /
approx. 4 VA /
approx. 1.5 W
approx. 1.5 W
approx. 10.5 VA / approx. 3.5 W
approx. 3 VA / approx. 1 W
see Device overview
0.8 to 1.1 x UN
Timing circuit
Time setting/Numbers of time domains
Available time domains
Standby reactivation interval
Minimum power-on time
Fallback value
Parallel consumer loads permissible
Internal one-way rectification direction
–/–
–
–
–
≥ 15 % UN
yes
no
Rated output Re 1 at 50 Hz and UN (AC) Hold
Output circuit
contact assembly
Contact material
Switching nominal voltage Un
max. steady current In
Usage category according to EN 60947-5-1:1991
Permissible frequency of operation
Mechanical service life
Response time
Fallback time
General Data
Air and crawl sections between the electric circuits
Rated surge voltage
Over-voltage category
Degree of contamination
Rated voltage
Testing voltage Ueff 50 Hz according to DIN VDE 0110-1, Table
A.1
Safety class for casing/terminals according to DIN VDE 0470 Section
1:11.92
Interference emission
Interference resistance
Ambient temperature, work area
Dimensional drawing
Wiring diagram
Weight
Accessories
SSP 33
3 NO contacts
2 changers
and
3 NC contacts
Ag Cu
AC/DC 400 V
5A
AC-15: Ue 230 V AC, Ie 2 A
≤ 3600 switching cycles/h
6
10 x 10 switching cycles
≤ 20 ms
≤ 25 ms
SSP 34
Pushbuttons
approx. 18 VA /
approx. 6.5 W
approx. 5.2 VA /
approx. 1.8 W
approx. 18 VA /
approx. 6.5 W
approx. 5.2 VA /
approx. 1.8 W
3 changers
4 changers
DC-13: Ue 24 V DC, Ie 2 A
according to DIN VDE 0110-1:04.97
5 kV
III
3 exterior, 2 interior
400 V AC
2.7 kV
IP 30/IP 20
EN 50081-1:03.93. -2:03.94
EN 50082-2:1995
–10 to +55 °C
S 3-5
S 3-5
KS 5161/2
KS 5172/2
0.5 kg
0.5 kg
–
S 2-1
KS 5143/2
0.6 kg
S 2-1
KS 5137/2
0.6 kg
Device overview / Order numbers
Type
SSP 56
Rated voltage
AC 24 V 50 Hz
AC 42 V 50 Hz
AC 48 V 50 Hz
AC 110 V 50 Hz
AC 110 V 60 Hz
AC 120-131 V 60 Hz
AC 230 V 50 Hz
AC 24 V 50 Hz
AC 110-115 V 60 Hz
AC 230 V 50 Hz
AC 24 V 50 Hz
AC 230 V 50 Hz
AC 110 V 50 Hz
AC 230 V 50 Hz
SSP 72
SSP 33
SSP 34
Page 82
SSP 56
Order number
R2.153.0149.0
R2.153.0089.0
R2.153.0049.0
R2.153.0059.0
R2.153.0079.0
R2.153.0139.0
R2.153.0109.0
R2.153.0099.0
R2.153.0109.0
R2.153.0029.0
R2.152.0099.0
R2.152.0179.0
R2.152.0119.0
R2.152.0079.0
Subject to change without further notice
SSY 12
SSY 12
Interval ON and/or OFF fixed timer relay
•
•
•
•
Single voltage
1 function: Interval ON and/or OFF (EAW)
Fixed interval time 0.5 s
1 interval change-over contact and 1 interval NO
Circuit diagram
Time ranges
Fixed interval time 0.5 s
Function
The function (interval ON, interval OFF, interval ON/OFF) is selectable
with the jumpers on the terminals (see connection diagram).
Jumper Z1/Z2 =
Jumper Z2/Z3 =
No jumper =
interval ON
interval OFF
interval ON and OFF
Function diagrams
Dimension diagram
Subject to change without further notice
SSY 12
Page 83
SSY 12
Technical data
SSY 12
Function type according to IEC 60050 (445)
Electronic interval timer relay for single voltage; function selectable
– Interval ON relay
– Interval OFF relay
–
FD 0015
Function display
Function diagrams
Power supply circuit
Rated voltage UN
Rated consumption at 50 Hz and UN (AC)
Rated consumption DC
Starting current inrush stroke
Rated frequency
Operating voltage range
AC/DC
Time circuit
Time setting / number of time ranges
Available setting range
Recovery time 1
Minimum ON time(after application of the rated voltage)
Release value
Parallel loads permissible
Internal half-wave rectification
Mean value of the error
Dispersion
Influence of the energizing quantity, supply voltage
Influence of the ambient temperature
Output circuit
Contact assignment
Contact material
Rated operating voltage Un
Max. continuous current In
Application category according to EN 60947-5-1:1991
Permissible switching frequency
Mechanical life
Response time
Release time
General information
Creepage distances and clearances between the circuits
Rated impulse voltage
Overvoltage category
Degree of pollution
Rated voltage
Test voltage Ueff 50 Hz according to DIN VDE 0110-1, table A.1
Protection degree housing/terminal according to DIN VDE 0470 sec.
1:11.92
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram
Circuit diagram
Weight
Accessories
Approvals
24 V
0.6 VA / 0.5 W
0.3 W
0.3 A / 6 ms
50 to 60 Hz
0.8 to 1.1 x UN
110 – 127 V
2.0 VA / 1.7 W
1.1 W
0.1 A / 20 ms
230 V
2.0 VA / 1.8 W
1.3 W
0.1 A / 100 ms
fixed / 1
See table "Time ranges"
approx. 250 ms at continuous operation,
approx. 3 s after longer shutdown
approx. 3 s
–
Yes
no
≤ ± 20 %
≤ ± 1.5 % + ± 10 ms
≤ 1.2 % / % ∆ UN
≤ 0.5 % / K
1 passing change-over contact and 1 passing NO
Ag alloy, gold-plated
230/230 V AC/DC
5A
AC-15: Ue 230 V AC, Ie 2 A
DC-13: Ue 24 V DC, Ie 2 A
≤ 6000 switching cycles/h
6
30 x 10 switching cycles
approx. 20 ms
–
according to DIN VDE 0110-1:04.97
4 kV
III
3 outside, 2 inside
250 V AC
2.21 kV
IP 30 / IP 20
Test severity 3
–20 to +60 °C
S 3-2
KS 0115-1
0.17 kg
–
–
Overview of devices / Part numbers
Type
SSY 12
Page 84
Rated voltage
AC 110-127 V 50-60 Hz
AC/DC 24 V 50-60 Hz
AC/DC 230 V 50-60 Hz
SSY 12
ON-delay time
See table "Time ranges"
Part No.
R2.133.0019.3
R2.133.0029.3
R2.133.0039.3
Subject to change without further notice
UZD 51
UZD 51
Digital multi-function multi-range relay
•
•
•
•
•
•
Multi-voltage for AC 100 to 240 V, Mono-voltage for AC/DC 24 V
8 functions
2 color high-contrast LCD displays
Setting range digital 0.001 s to 999.9 h split into 8 time ranges
Zero-voltage secure
1 timed change-over contact
Circuit diagram
Function
The selection of the individual function and the time range is by a dual
in-line switch that is located on the right-hand side wall of the equipment. The time selection is carried out on the front. The set target value
is displayed digitally with a four-digit yellow LCD display and the individual actual value is displayed digitally with a four-digit red LCD display.
The set value settings are retained even if the power supply drops out
and is reinstated.
Setting the function, the time range and the time preselection
1. Setting the function and the time range
The new settings become active after switching off and on again of the
power supply.
Dual in-line switch
Time ranges
Setting range 0.001 s to 999.9 h split into:
0.001 s
… 999.9 s
10
0.01 s
… 99.99 s
0.1
0.1 s
… 999.9 s
1
1s
… 9999 s
0.1
s
min
min
h
…
…
…
…
99 min 59 s
999.9 min
99 h 59 min
999.9 h
Notes
• Set the function and time range before installing the unit.
• We recommend using the LOCK button to prevent inadvertent resetting of the set values.
• Adjusting the set value during the time sequence is not permitted.
• Gold-plated contacts should be used to ensure perfect switching.
• Switching by transistor is possible; see technical data.
Accessories
Plug mount
Plug mount
AT8-DF8S
AT8-RR
for DIN rail
for operating panel mount
1
2
3
4
5
6
7
8
Functions
See Table 1
Minimum on time
Setting time sequence
20 ms
additive
Time ranges
See Table 2
1 ms
subtractive
Table 1: Setting the function
Switch number
1
2
3
ON ON ON
OFF OFF OFF
ON OFF OFF
OFF ON OFF
ON ON OFF
OFF
ON
OFF
OFF
OFF
ON
ON
ON
ON
Functions
Mode
A: response delay (AV)
A2: response delay (AV)
B: response delay (AV) by excitation parameter
C: fallback delay (RV) with excitation parameter
D: switch-on wiper (EW) with excitation parameter
E: response delay (AV) (impulse switching)
F: clock generator starting with pause (TP)
G: response delay (AV) (time addition or subtraction)
Table 2: 2: Setting the time range
Switch number
6
7
8
ON ON ON
OFF OFF OFF
ON OFF OFF
OFF ON OFF
ON ON OFF
OFF OFF ON
ON OFF ON
OFF ON ON
Subject to change without further notice
Dual in-line switch
OFF
ON
Range
Time range
0.00 S
0.01 s
0.1
1
10 s
0.1 min
1 min
0.1 h
to
to
to
to
to
to
to
to
UZD 51
9.999 s
99.99 s
999.9 s
9999 s
99 min 59 s
999.9 min
99 h 59 min
999.9 h
Page 85
UZD 51
Function
Function diagrams
2. Setting the time preselection
Time preselection is carried out using the four buttons on the front.
Front view
1 - LCD display for the specific actual value
2 - LCD display for the set value
3 - LED display that flashes when time running
4 - Display, output excited
5 - Display, reset input switched
6 - Display, blocked input
7 - Display of set time range
8 - UP button, additive change of set value
9 - DOWN button, subtractive change of set value
10 - RESET button, deletes the actual value and resets the output
11 - LOCK button, blocks the RESET, the UP and the DOWN buttons
Dual in-line switch
Dimension diagram
Subject to change without further notice
UID 51
Page 86
UZD 51
Technical data
UZD 51
Function type according to IEC 60050 (445)
Multi-function relay with 8 functions for multi or mono voltage
- response delayed time relay
- fallback delayed time relay with power supply
- switch-on wiper
- clock generator
4 digit red LCD display for actual value, character height 7 mm,
4 digit yellow LCD display for set value, character height 5.5 mm,
Text fade-in
FD 0239-5/1 to 8
Function display
Function diagrams
Power supply circuit
Rated voltage UN
AC/DC
AC
AC
DC
Rated consumption at 50 Hz and UN
Rated output
Rated frequency
Operating voltage range
Residual ripple of the rated voltage UN
Time circuit
Electrical isolation from power supply circuit
Time setting / number of time ranges
Available setting range
Setting the time sequence (adjustable)
Clock start
Repeatability
Setting acuity
Influence of excitation or power supply
Minimum ON time(adjustable) Reset / excitation parameter
Recovery time
Transistor starting (open collector)of connections 3 or 4
Input voltage
Maximum input resistance (switched condition)
Minimum input resistance (open condition)
Maximum residual voltage (switched condition)
Output circuit
Contact assignment
Contact material
Switching voltage Un
Max. continuous current In
Application category according to EN 60947-5-1:1991
Permissible switching frequency
Mechanical life
Electrical life
General information
Creepage distances and clearances between the circuits
Rated impulse voltage
Overvoltage category
Degree of pollution
Rated voltage
Test voltage Ueff 50 Hz according to DIN VDE 0110-1, table A.1
Protection degree housing/terminal according to DIN VDE 0470 sec.
1:11.92
Noise immunity according to IEC 61000-4
Ambient temperature, operating range
Dimension diagram
Circuit diagram
Weight
Accessories
24 V
100 to 240 V
10 VA
3W
50 to 60 Hz
0.85 to 1.1 x UN
≤ 20 %
nein
4-digit digital / 8
See table "Time ranges"
additive, subtractive
Pause
± 0.005 % + 50 ms
± 0.005 % + 50 ms
± 0.005 % + 50 ms
20 ms / 1 ms (only with transistor starting)
≤ 100 ms
VCEO 20 V min., IC 20 mA, ICBO 6 µA max
12 to 40 V DC
≤ 1 kΩ
≥ 100 kΩ
≤2V
1 timed change-over contact
Ag alloy, gold-plated
230/30 V AC/DC
5A
AC-15: Ue 250 V AC, Ie 0.75 A
DC-13: Ue 30 V DC, Ie 2 A
≤ 3600 switching cycles/h
20 x 106 switching cycles
1 x 106 switching cycles
according to DIN VDE 0110-1:04.97
4 kV
III
3 outside, 2 inside
300 V AC
2.21 kV
IP 66 ((only with rubber seal) / IP 20
Test severity 3
–10 to +55 °C
U 3-1
KS 0362/1
0.11 Kg
Plug mounts AT8-DF8S, AT8-RR
Overview of devices / Part numbers
Type
UZD 51
ON-delay time
See table "Time ranges"
Subject to change without further notice
Rated voltage
AC/DC 24 V 50-60 Hz
AC 110-240 V 50-60 Hz
Part No.
R2.063.0019.0
R2.063.0029.0
UZD 51
Page 87
Pre-set pulse counter Electronic timer UID 51
UID 51
Digital multi function pre-set pulse counter
• Device for multi voltage AC 100 to 240 V
for single voltage AC/DC 24 V
• 5 input and 7 output modes; any combination possible
• 2-color high-contrast LCD displays
Protected against power failure
• 1 normally open contact
Circuit diagram
Pulse range
Available pulse ranges: –999 bis +9999
Function
The functions are set by means of a dual in-line switch located on the right
lateral side of the device. The setpoint value is set through four switches
and is digitally indicated on a 4-digit yellow LCD display and the actual
value is digitally indicated on a 4-digit red LCD display. The setpoint settings are protected against power failure and recovery.
1. Setting of the operating modes (input and output mode)
Dual-in-line-Schalter
Function
Notes
• Set the function prior to installing the device.
• Press the LOCK key to avoid unintentional modifications to the set
values.
• Modifications to the setpoint value during the counting operation are
permissible.
• Use gold-plated contacts to achieve proper control.
• Semiconductor input possible; see “Technical data”
Accessories
Pin holder
Pin holder
AT8-DF8S
AT8-RR
for DIN-rail
for panel mounting
1
2
3
4
5
6
7
8
Dual-in-line-switch
OFF
ON
Output mode
See table 1
Min. reset input signal width
Max. count rate
20 ms
30 kHz
Input mode
s See table 2
1 ms
5 kHz
Table 1: Output mode
DIP switch no.
Output mode
1
2
3
ON ON ON ON pulse, SHOT-A
OFF OFF OFF ON pulse, SHOT-B
ON OFF OFF ON pulse, SHOT-C
OFF ON OFF ON pulse, SHOT-D
ON ON OFF Holding function, HOLD-A
OFF OFF ON Holding function, HOLD-B
ON OFF ON Holding function, HOLD-C
OFF ON ON
– (DIP Err appears on the display)
T Table 2: Input mode
DIP switch no.
6
7
8
ON ON ON
OFF OFF OFF
ON OFF OFF
OFF ON OFF
ON ON OFF
OFF OFF ON
ON OFF ON
OFF ON ON
Subject to change without further notice
Input mode
Additive input
Subtractive input
Direction input
Independent inputs
Phase input
– (DIP Err appears on the display)
– (DIP Err appears on the display)
– (DIP Err appears on the display)
UID 51
Page 88
Pre-set pulse counter Electronic timer UID 51
Function
2. Setting of the setpoint
The setpoint is set using the four switches on the front.
Function diagrams
Input modes
Front view
1 – LCD display for the current actual value
2 – LCD display for the selected setpoint value
3 – Indicator for energized output
4 – Indicator for controlled reset input
5 – Lock indicator
6 – UP keys, additive modification to the selected setpoint value
7 – DOWN keys, subtractive modification to the selected setpoint value
8 – RESET switch, clears the actual value and resets the output
9 – LOCK switch, locks the RESET key, the UP and DOWN keys
Dual-in-line-switch
Dimension diagram
Subject to change without further notice
UID 51
Page 89
Pre-set pulse counter Electronic timer UID 51
Function diagrams
Output modes
Subject to change without further notice
Function diagrams
Output modes
UID 51
Page 90
Pre-set pulse counter Electronic timer UID 51
Technical data
Function type
UID 51
Multi-function pulse counter with 5 input and 7 output functions for multivoltage or single voltage
4-digit red LCD display for actual value, digit size 7 mm,
4-digit yellow LCD display for setpoint value, digit size 5.5 mm,
Text indications
See column "Function diagrams"
Function display
Function diagrams
Power supply circuit
Rated voltage UN AC/DC
AC
Rated consumption at 50 Hz und UN
AC
Bemessungsleistung DC
Rated frequency
Operating voltage range
Residual ripple of the rated voltage UN
Time circuit
Electrical isolation from power supply circuit
Setpoint setting / number of setpoint ranges
Available setting range
Setting of the counting modes
Counting rate
Min. counting pulse
Reset input
24 V
100 – 240 V
10 VA / 3 W
3W
50 – 60 Hz
0,85 – 1,1 x UN
≤ 20 %
Locking input
Input signal
Output circuit
Contact assignment
Contact material
Switching voltage Un
Max. continuous current In
Application category according to EN 60947-5-1:1991
Permissible switching frequency
Mechanical life
General information
Creepage distances and clearances between the circuits
Rated impulse voltage
Overvoltage category
Degree of pollution
Rated voltage
Test voltage Ueff 50 Hz according to DIN VDE 0110-1, table A.1
Protection degree housing/terminal according to
DIN VDE 0470 sec. 1:11.92
Ambient temperature, operating range
Dimension diagram
Circuit diagram
Weight
Accessories
Approvals
no
4-digit digital
See table "Pulse range"
additive, subtractive
30 Hz / 5 Hz (selectable with DIP switch)
16,7 ms at 30 Hz / 0,1 ms at 5 kHz, ON time : OFF time = 1 : 1
Signal reset / pressing a key,
Min. input time 1 ms / 20 ms (selectable with DIP switch)
Min. input signal width: 20 ms
Contact or open collector input / input impedance: max. 1 kΩ,
residual input voltage: max. 2 V,
Open impedance: min. 100 kΩ, max. voltage load: DC 40 V
1 normally open contacts
Ag-Legierung, hauchvergoldet
230/30 V AC/DC
5A
AC-15: Ue 250 V AC, Ie 0,75 A
DC-13: Ue 30 V DC, Ie 2 A
≤ 3600 switching cycles/h
20 x 106 switching cycles
according to DIN VDE 0110-1:04.97
4 kV
III
3 outside, 2 inside
250 V AC
2,21 kV
IP 66 (only with rubber gasket) / IP 20
-10 – +55 °C
U 3-2
–
0,11 Kg
Pin holders AT8-DF8S, AT8-RR
–
Overview of devices / Part numbers
Type
UID 51
Rated voltage
AC 24 V 50-60 Hz
AC 110-240 V 50-60 Hz
Subject to change without further notice
Impulsbereich
–999 bis +9999
Part No.
R2.213.0069.0
R2.213.0079.0
UID 51
Page 91