Transcript
Z
50 AC
06
WARNINGS
07
!
DISCONNECT AND UNPLUG TEST LEADS before opening case.
TEST NCV FUNCTION ON KNOWN LIVE WIRE before using.
DO NOT APPLY VOLTAGE greater than 30VAC or 60VDC to the
thermocouple or the jacks when the rotary dial is on °F°C. (Use
only Type K thermocouples)
DO NOT APPLY VOLTAGE TO THE JACKS when the rotary dial is on
microamps. Even low voltages can cause a current overload and
potentially harm the meter.
Temperature (°F/°C)
MFD
NCV
°F°C
COM
Plug any Type K thermocouple directly into the meter to measure
temperature. Cold junction is located inside the meter and allows for
extremely accurate measurements even in rapidly changing ambient
temperatures (going from rooftop to freezer). No adapter is required.
Range: -30°F to 932°F, (-35°C to 500°C) Resolution: 0.1°
Accuracy: ±(1°F)* 32°F to 120°F, ±(1°C) 0°C to 49°C
±(1%+2°F) 32°F to 572°F, ±(1%+1°C) 0°C to 300°C
±(2%+6°F) -30°F to 32°F, ±(2%+3°C) -35°C to 0°C
±(2%+6°F) 572°F to 932°F, ±(2%+3°C) 300°C to 500°C
Sensor type: Type K thermocouple *After field calibration
Overload protection: 30 VDC or 30VAC rms
30V
MAX
COM
10
V
30 X
MA
T III
CA600V
MP
OFF
TE
M
CO
TO
pie
Voltage AC (VAC) (50Hz-500Hz)
PE
TY
K-
AU
ld
Ho
MFD
NCV
°F°C
HZ
AAC
VAC
VDC
HZ%
µADC
ce
MFD
NCV
°F°C
HZ
AAC
VAC
VDC
HZ%
µADC
Use NCV to check 24VAC from a thermostat or live voltage up to
600VAC. Always test a known live source before using. A segment graph
and RED LED will display the presence of voltage. Audible beep increases
from intermittent to continuous as intensity of field (EF) increases.
AC Voltage Detection Range: 24VAC to 600VAC (50-60Hz)
09
30V
MAX
Unplug Leads and Slide
TEMP Switch to the Right
Non Contact Voltage (NCV)
Test power lines (120, 220, 480), test 24V going to controls, and
test for transformer failure.
Ranges: 500mV, 5V, 50V, 500V, 600V Resolution: 0.1mV
Accuracy: ±(1.2% + 8) 500mV range (50-60Hz)
±(1.2%+8), 5V, 50V, 500V; ±(1.5% + 8) 600V range
True RMS: model SC440 only Crest factor: ≤ 3
Audio/Visual Hi-V indicator: >30VAC/VDC
Input impedance: >100MΩ (500mV), 10MΩ (5V),
9.1MΩ (50V-600V)
AUTO OFF
TYPE K
0
COM
HZ
AAC
VAC
VDC
HZ%
µADC
S
RM
AUTO OFF
TYPE K
Please operate the instrument following all instructions
of the operator's manual to avoid impairing the safety
of the product.
08
30V
MAX
44
SC
NCV
AUTO OFF
TYPE K
ld
Backlight: 60 second duration with auto-off. Blue color. SC440 only.
Overrange: (OL) or (-OL) is displayed
Measurement rate: 3.3 times per second, nominal
Zero: Automatic
Operating environment: 32°F to 122°F (0°C to 50°C) at <70%
relative humidity
Storage temperature: -4°F to 140°F (-20°C to 60°C), 0 to 80% RH
(with battery removed)
Accuracy: Stated accuracy @ 73°F±9°F (23°C±5°C), <75%RH
Temperature coefficient: 0.1 x (specified accuracy) per °C [0°C to
19°C (32°F to 66°F), 28°C to 50° C(82°F to 122°F)]
APO (Auto Power Off): Approx. 30 minutes
Power: Single standard 9-volt battery, NEDA 1604, JIS 006P, IEC 6F22
Battery life: 200 hours typical alkaline (SC420); 100 hours typical
alkaline (SC440)
Low battery indication: Battery icon blinks and "LO.bt" is displayed
when the battery voltage drops below the operating level
Dimensions: 233mm(H) x 79mm(W) x 45mm(D)
Weight: Approx. 315g including battery
Altitude: Up to 6562 ft (2000m)
Overload protection: 600 VDC or 600VAC rms unless otherwise
stated
Test leads: Use UL listed test leads that comply to UL61010-031
rated CATIII 600V or above. Included test leads are gold-plated
and have removeable safety caps.
05
Fie
Never ground yourself when taking electrical
measurements. Do not touch exposed metal
pipes, outlets, fixtures, etc., which might be
at ground potential, while taking measurements. Keep your body isolated from ground
by using dry clothing, rubber shoes, rubber
mats, or any approved insulating material.
Disconnect the test leads before opening the
case. Inspect the test leads for damage to the
insulation or exposed wire. Replace if suspect.
Keep your fingers behind the finger guards
on the probes while taking measurements.
When disconnecting from a circuit, disconnect
the“RED”lead first, then the common“BLACK”
lead. Use one handed testing when possible.
Work with others.
Turn off power to the circuit under test before
cutting, unsoldering, or breaking the circuit.
Do not measure resistance (ohms) when circuit
is powered. Isolate load by disconnecting
from circuit.
Disconnect the meter from circuit before turning
any inductor off, including motors, transformers, and solenoids. High voltage transients
can damage the meter beyond repair.
Freeze the display.
Hold
30V
MAX
Functions
Specifications
Display: 5000 count dual display
Do not use during electrical storms.
Do not apply more than rated voltages between
input and ground.
Isolate capacitors from system and discharge
them safely before testing.
Temperature switch prevents leaving thermocouple plugged in while measuring voltage.
When measuring high frequency AC current, do
not exceed the rated 400AAC of the clamp.
Failure to adhere may cause the clamp to heat
up dangerously.
All voltage tests: All voltage ranges will
withstand up to 600V. Do not apply more than
600VDC or AC rms.
Symbols used:
Caution, risk of electric shock
! Caution, refer to manual.
Ground
Double insulation
600V
600V
UE
TR
TRUE RMS
TRUE RMS
SC640
e
ng
Ra
AUTO OFF
SC640
04
CAT
CATIIIIII
Manually select a range.
Hold
Select
COM
600V
30V
MAX
HZ
%
AAC
DC
VAC V HZµADC
Range
TYPE K
TEMP
TEMP
t AUTO OFF
TYPE K
FD
M
V
NC
°C
°F
µADC elec
30V
MAX
VDC
S %
K-TYPE
CAT III
MAX
30V
%
K-TYPE
MAX TEMP 600V
TRUE
TRUERMS
RMS AUTO
AUTOOFF
OFF
CAT III
Activate inrush current and scroll TEMP
600V
30V
30V
CAT III
K-TYPE
K-TYPE
MAX
MAX inrush ranges
through different
(SC440).
600VIII
CAT
HZ
°F
°C
DC
µADC
°F
°C
INRUSH
COM
Safety Information
HZ
Hold
SC640
Range
03
HZ
400 AAC
VACHold
VAC
TRUE RMS
Z
400 AC
AC
COM
02
Z
AC
AC
AUTO OFF
01
TRUE RMS 50
TYPE K
600V
CATIII 600V, class II and pollution degree 2
indoor use comply with CE, RoHS compliant.
CATIII is for measurements performed in the
building installation.
µADC
°F
°C
TRUE RMS
CAT III
WEEE
VDC
HZ
SC640
TEMP
30V
MAX
C-Tick (N22675)
µADC
Range
COM
AUTO OFF
MFD
°F
°C
Se
lec
t
TYPE K
NCV
%
HZ
50AAC
VAC HZ
400 AAC
VAC
µADC
SC440
VDC
HZ
°F
°C
TRUE RMS
Hold
MFD
VDC
Range
HZ
50AAC
VAC HZ
400 AAC
VAC
NCV
INRUSH
Se
lec
t
EN61010-1
EN61010-2-032
EN61010-2-033
EMC EN61326-1
Auto Power Off Enabled
INRUSH
INRUSH
High Voltage Warning (>30VAC/VDC)
Manual Range (RNG) Mode
SEL
Data
Hold Mode
SEL
SEL
Inrush Amps Mode (Model SC440)
Continuity Test
SEL
SEL
Diode
TestOFF
TRUE
RMS
AUTO
TRUE
RMS
AUTO
OFFOFF
TRUE
AUTO
30V RMS
Frequency
Test (hertz)
30VMAX
K-TYPE
SEL
SEL
30V
K-TYPE
MAX
K-TYPE
MAXOFF
Resistance
Test (ohms)
TEMP
TRUE RMS
AUTO
TRUE
RMSOFF
AUTO
TEMP
OFF
TEMP
Capacitance
Test (farads)
30V RMS
TRUE
RMS30VAUTO
AUTO
OFFK-TYPE
TRUE
OFF
K-TYPE
MAX
CAT
IIICycle Test (percentage)
MAX
Duty
CAT
III
30VTEMP
CAT III
TRUE
AUTO
OFF
30V
TRUE RMS
AUTORMS
OFF
600V
TEMP
600V
K-TYPE
K-TYPE
MAX
600V Unit (10−6, one millionth)
MAX
Rotate dial to%the function you want to
Micro
TEMP
30V
30Vuse. TEMP
K-TYPE
K-TYPE
OFF
MAX
CAT IIIMAX CAT III Milli Unit (10−3, one thousandth)
TEMP
TEMP
600V
600V
CAT
III
CAT
III
KiloOFF
Unit (103, one thousand)
C y c l e t h r o u g h p a r a m e t e r 600V
s600V
TRUE RMS AUTO
Se
lec
CAT III
III
Mega Unit (106, one million)
CAT
t within VAC/AAC/Hz and Ω/ / TRUE
RMS 30V
AUTO
600VOFF
600V
%
K-TYPE
HHold
MAX
OFF
Range
switch
positions.
A
30V RMS AUTO
TRUE
OFF
TEMP
H
V
K-TYPE
SC640
MAX
A
NCV
V
TRUE RMS
AUTO
TEMP OFF
30V
K-TYPE
MFD
V
TRUE
RMS
AUTO
OFF
MAX
CAT
III
OFF H
Illuminate backlight (SC440). 30V
A
TEMP 600V
INRUSH
UL 61010-1, Third Edition
HZ
AAC
VAC
VDC
HZ%
µADC
MFD
NCV
°F°C
HZ
HZ
AAC
VAC
VDC
HZ%
µADC
°C
°C
°F
°F
INRUSH
MFD
NCV
°F°C
%%
INRUSH
Models SC440 SC420
Certifications
Fieldpiece
Display
MFD
Controls MFD
Hz
Hz
The new SC400 series clamp meters are
designed for HVACR service. Hang clamp meter
to any metallic surface with the redesigned
heavy-duty magnet and keep your hands free
to do more (SC440 only). See both voltage and
amperage readings at the same time on the
dual LCD display, even in low light conditions
using the bright blue backlight (backlight SC440
only). Take measurements with one hand using
the single test lead holder for added safety. Test
leads come with removable gold plated tips to
connect with Fieldpiece accessory heads.
Take more accurate VAC and AAC readings
on VFDs with True RMS sensing technology
(SC440 only). Measure the starting amp draw of
a compressor with Inrush current feature (SC440
only). Find the wire you want to test with the
automatic clamp jaw light (SC440 only).
The SC400 series clamp meters are built toSelect
NCV
withstand the rigors of HVACR with high impactRange
MFD
plastic and a display you can read in hot or
cold environments. Move from a cold freezer
to a hot roof top and get accurate temperature
measurements that lesser thermometers canSe
lec
t
not measure properly.
MFD
Essential
Clamp
Meters
OPERATOR'S
MANUAL
Description
1.For electrical testing, connect test leads to
"COM" and "+" jacks.
2. Rotate the dial to your desired measurement.
3. Connect to test points and read measurement.
4. For temperature testing, remove test leads,
slide TEMP switch to the right and connect
Type K thermocouple.
HZ
50AAC
VAC HZ
400 AAC
VAC
Quick Start
OFF
Fieldpiece
O
F Hz
AAC
SEL
SEL
SEL
INRUSH
F VAC
AAC
VDC NCV
MFD
°F°C% Hz
HOLD
HOLD
%MFD°C F VAC V
DC
INRUSH
NCV
OO Hz
Hz % Hz °F
SEL
NCV
SEL
FF AAAC
°CHz
AC
INRUSH
°F
°C
AC
AC°F
FFVV
VV
DC
DC
SEL
SEL
INRUSH
Battery
Life
(replace 9V if blinking)
NCV
NCV
INRUSH
SEL
SEL
F AAC
F VAC VDC
MFD
SC56
%
NCV
Hz
°F°C Select VDC and measure DC voltages on circuit boards on more
INRUSH
advanced HVACR systems.
Ranges: 500mV, 5V, 50V, 500V, 600V Resolution: 0.1mV
Accuracy: ±(0.5% + 2)
HOLD
Input impedance:
O Hz >100MΩ (500mV), 10MΩ (5V),
F
A
AC
9.1MΩ (50V-600V)
F VAC VDC
MFD
%
NCV
Hz
°C
°F
Used for “ohming out” aSEL
compressor. 0.1Ω resolution is necessary
INRUSH
to test the resistance between the motor poles because
the values are
typically very low.
Ranges: 500Ω, 5kΩ, 50kΩ, 500kΩ, 5MΩ, 50MΩ
Resolution: 0.1Ω Overload Protection: 600VDC or 600VAC rms
Accuracy: ±(1.0% + 5) 500Ω to 500kΩ, ±(1.5% + 5) 5MΩ, ±(3.0%
+ 5) 50MΩ
Voltage DC (VDC)
Check incoming voltages to ensure they are cycling at 60Hz. For
frequency measurements on VFD equipment, use the amp clamp.
Ranges: 500Hz, 5kHz, 50kHz, 500kHz, 1MHz Resolution: 0.1Hz
Accuracy: ±(0.1% + 5) Sensitivity: 10Hz to 1MHz: >3.5Vrms
PW: >1µs Duty Cycle Limits: >30% and <70%
MFD
NCV
°F°C
HZ
AAC
VAC
VDC
HZ%
µADC
Capacitance (MFD)
MFD
NCV
°F°C
English
Metric
Ft/min
MPH
ºF
M/s
KM/hr
ºC
READ
Metric
Real
time
OFF
MFD
NCV
°F°C
HZ
AAC
VAC
VDC %
HZ
µADC
AUTOOFF
AAV3
Select
Hold
Range
TRUE RMS
SC440
AUTO OFF
TYPE K
30V
MAX
TEMP
COM
CAT III
600V
Visit www.fieldpiece.com to see all of the
different accessory heads that Fieldpiece offers.
16
17
HOLD
LO BATT
Air Velocity
& Temperature Average
English (16 sec)
Head
Fieldpiece
MFD
NCV
°F°C
HZ
AAC
VAC
VDC
HZ%
µADC
Auto power off or APO will automatcially turn
off your meter after 30 minutes of inactivty. By
default it is activated and APO will show on the
display. To disable, turn meter off. Hold
and
SC240
power on the meter by turning the selector
dial
to any range. Release
after the beep. APO will
no longer displaySC240
over the battery icon.
MFD
OFF
HZ
400 AAC
VAC
VAC
NCV
MFD
HZ
50AAC
M/m
HZ
%
µADC
OFF
Auto Hold
NCV
Se
lec
t
HZ
50AAC
VAC HZ
400 AAC
VAC
MFD
VDC
This meter is warranted against defects in
material or workmanship for one year from
date of purchase. Fieldpiece will replace or
repair the defective unit, at its option, subject
to verification of the defect.
This warranty does not apply to defects
resulting from abuse, neglect, accident,
unauthorized repair, alteration, or unreasonable
use of the instrument.
Any implied warranties arising from the sale of
a Fieldpiece product, including but not limited
to implied warranties of merchantability and
fitness for a particular purpose, are limited to
the above. Fieldpiece shall not be liable for loss
of use of the instrument or other incidental or
consequential damages, expenses, or economic
loss, or for any claim of such damage, expenses,
or economic loss.
State laws vary. The above limitations or
exclusions may not apply to you.
AUTO OFF
TYPE K
TEMP
30V
MAX
Press and hold
for two seconds. Meter
AUTO OFF
will beep andSC640
HOLD will blink on LCD. After
6 seconds the measurement on screen will
freeze automatically. Press
to exit this mode.
Range
A
HZ
Hold
TRUE RMS
°F
TYPE K
%
µADC
30V
°C
MAX
TEMP
COM
COM
CAT III
600V
Se
lec
t
Range
CAT
III
600V
TRUE RMS
Hold
SC640
Battery Replacement
AUTO OFF
DO NOT SWITCH
FROM J2
30V
MAX
When your meter’s battery is low, the battery
icon will appear empty and blink for 30 seconds.
AUTOmeter
OFF
“LO.bt” will display and
will power off.
Turn dial to OFF position, disconnect test
leads and remove the battery cover with magnet
strap (SC440 only) on the back of your meter.
Remove old battery and replace with a standard
9V battery only. Be sure to re-insert the magnet
strip before re-installing the battery cover.
TYPE K
COM
C
TYPE K
30V
MAX
COM
TEMP CAL
B
18
30V
MAX
Hold
AUTO
K
TYPE
RMS
VDC
µADC
SC640
TRUE
HZ %
OFF
Range
°F
°C
HZ
AC
HZ
50A
VAC 400AAC
VAC
COM
OFF
INRUSH
19
Inrush feature captures starting current of a compressor motor.
Starting current can assist in diagnosing a motor before it fails.
To activate Inrush feature
1. Turn selector switch to VAC/AAC/Hz
2. Press SELECT once to show AAC on upper display.
3. Press INRUSH once to select 50AAC range. Press INRUSH twice to
select 400AAC range.
4. Clamp meter around compressor start wire. Turn motor on. The
starting current will hold on the upper display.
5. Hold INRUSH for 2 seconds to exit Inrush feature or press and
release INRUSH to measure starting current again.
Inrush measurement period: 100-milliseconds
Minimum input: >2A on 50A range; >20A on 400A range
! Note: AAC through the clamp and voltage through the test
leads can be measured simultaneously. However, if only AAC,
Frequency (Hz), or Inrush is measured through the clamp, test
leads and thermcouple must be unplugged from the meter.
Call Fieldpiece Instruments for one-pricefix-all out-of-warranty service pricing. Send
check or money order for the amount quoted.
Send the meter freight prepaid to Fieldpiece
Instruments. Send proof of date and location
of purchase for in-warranty service. The meter
will be repaired or replaced, at the option
of Fieldpiece, and returned via least cost
transportation.
For international customers, warranty for
products purchased outside of the U.S. should
be handled through local distributors.
Limited Warranty
e
Rang
ge
M/mVDC Ran
Select
°F
°C
Select
HZ
AAC
VAC
VDC
HZ%
µADC
Obtaining Service
Clean the exterior with a dry cloth. Do not
use liquid.
AAC
VAC
VDC
NCV
°F°C
15
Maintenance
AAC
VAC
VDC
NCV
°F°C
INRUSH
LCD X
100
HOLD
ON
MFD
Fieldpiece
INRUSH
MFD
NCV
°F°C
HZ
AAC
VAC
VDC
HZ%
µADC
Fieldpiece
Auto Power Off
For accuracies of ±1°F, calibrate to a known
temperature. A glass of stabilized ice water
is very close to 32°F (0°C) and is usually very
convenient but any known temperature can
be used.
1. Select the °F °C range.
2. Plug thermocouple to be
calibrated into the Type K jack.
3. Unscrew A and B and remove
the battery cover.
4. Stabilize a large cup of ice
water. Stir the ice with the
water until temperature stays
at a stable value.
5. Immerse the thermocouple
probe and let it stabilize.
Keep stirring water to prevent
micro-environments.
6. Do not let the thermocouple
come in direct contact with
ice.
7. Use a small screwdriver to
adjust calibration pot C below
the battery as close to 32°F
(0°C) as you would like.
Note: J1-J2 switch is for autocalibration purposes only. Do
not switch from J2.
HZ
AAC
VAC
VDC
HZ%
µADC
14
K-TYPE
CAT III
600V
Temp. Calibration
Your new Swivel Clamp Meter is compatible
with all Fieldpiece Accessory Heads. With
Fieldpiece Accessory Heads, you can measure
any available parameter, and read the
measurement on your new meter's display in
real-time.
Just set the range to VDC and press the
RANGE button until mV is displayed. Remove
the probe tips of your test leads, and connect
your accessory head (model AAV3 shown).
TEMP
MFD
NCV
°F°C
K-TYPE
TEMP
Test diodes
forIIIproper forward and reversed-biased functions.
CAT
Test current:600V
0.8mA (Approx.) Accuracy: ±(1.5% + 5)
Open circuit volts: 3.2VDC typical Audible beep: <0.03V
Visual Indicator: Green LED
Overload
600VDC or 600VAC rms
TRUE
RMS Protection:
AUTO OFF
30V
13MAX
HZ
AAC
VAC
VDC
HZ%
µADC
MFD
NCV
°F°C
Diode Test ( )
Discharge Cap First!
12
Modular
Expandability
30V
MAX
HZ
AAC
VAC
VDC
HZ%
µADC
Measure Hz on variable frequency drive motors. Turn dial to VAC/
AAC/Hz and press SELECT twice. Hz will show in upper display.
Range: 10Hz to 400Hz Accuracy: ±(0.1% + 5)
Minimum current range: > 5AAC Overload Protection: 400AAC
Resolution: 0.1Hz
Inrush Current (SC440 only)
Use the continuity feature to test if a circuit is open or closed. Use
this feature to check fuses as well. A steady “beep” and green LED
indicate you have continuity. Press SELECT once.
Range: 500Ω Resolution: 0.1Ω Response time: 100ms
AudibleRMS
beep: <30Ω
Overload
TRUE
AUTO
OFF Protection: 600VDC or 600VAC rms
Duty cycle shows the % On Time of a 5V logic signal square wave.
Ranges: 5%-95% (40Hz to 10kHz), 10%-90% (10kHz to 20kHz)
Accuracy (5V logic): ±(2% + 10) Resolution: 0.1% PW: >10µs
Overload Protection: 600VDC or 600VAC rms
11
MFD
NCV
°F°C
Continuity SEL
( )
Duty Cycle (%)
Test any isolated power line. Press SELECT on VAC/AAC/Hz
position. Read AAC in upper display. True RMS on SC440 only.
Ranges: 50A, 400A Resolution: 0.01A Crest factor: ≤ 3
Accuracy: ±(2.0% + 10) 50-60Hz Jaw Opening: 1.2in (30 mm)
Frequency (Hz) Through Clamp
Resistance (Ω)
Frequency (Hz) Through Leads
Set to MFD to test motor start and run capacitors. Capacitors
are one of the most failure prone components in a HVACR system.
Disconnect from power and resistors between terminals. Discharge
capacitor before testing. If dIS.C is displayed, capacitor is not
discharged completely.
Ranges: 5µF, 50µF, 500µF, 5mF Resolution: 1nF
Accuracy: ±(3% + 15) 5µF, ±(3% + 5) 50µF to 500µF, ±(5% + 20) 5mF
Overload Protection: 600VDC or 600VAC rms
MFD
NCV
°F°C
Select
MFD
NCV
°F°C
HZ
AAC
VAC
VDC
HZ%
µADC
Amps AC (AAC) True RMS
HZ
AAC
VAC
VDC
HZ%
µADC
MFD
Microamps for flame rectifier diode test on a heater control.
Connect leads between flame sensor probe and control module and
turn heating unit on to read µA measurement. When the flame is on,
there should be a measurable µADC signal, typically under 10µADC.
Compare measurement to manufacturer’s specification to determine
if replacement is necessary.
Ranges: 500µA Resolution: 0.1µA
Accuracy: ±(1.0% + 2) Voltage burden: 1V
Overload Protection: 600VDC or 600VAC rms
NCV
MicroAmps DC (µADC)
www.fieldpiece.com
© Fieldpiece Instruments, Inc 2014; v21