Download CR9300 Series - CR Magnetics

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Stray voltage wikipedia , lookup

Stepper motor wikipedia , lookup

Mains electricity wikipedia , lookup

Thermal runaway wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Power inverter wikipedia , lookup

Ohm's law wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Switch wikipedia , lookup

P–n diode wikipedia , lookup

Voltage regulator wikipedia , lookup

Surge protector wikipedia , lookup

Rectifier wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Current source wikipedia , lookup

Protective relay wikipedia , lookup

Crossbar switch wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Transistor wikipedia , lookup

Alternating current wikipedia , lookup

Wilson current mirror wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Opto-isolator wikipedia , lookup

Buck converter wikipedia , lookup

Current mirror wikipedia , lookup

Transcript
Current Switch Normally Open
CR9300 Series
The CR9300 Series is a low cost, self powered, fixed set-point Current Switch
designed for applications that require an on-off indication of current flow.
Current levels above the guaranteed full-on level will turn the output to full on.
The Current Switch is recommended only for applications where the continuous
operating current is above the rated full on level of 350 mA. Operation below
this point will not drive the output device full-on and derate the output ratings.
The unit is available with a NPN or PNP output transistor for switching DC and a
SCR output for switching AC. Connections can be made directly to items such as
a PLC or electromechanical relay. Note that connections made directly to an in-
DC SWITCHING (-NPN or -PNP)
ductive device such as an electromechanical relay will require a customer supplied clamping diode for DC operation or a snubber network for AC operation.
Vce (full off): 30 VDC max.
Isink (full on): 120 mADC max.@ rated full-on
Vce (reverse polarity voltage): 1.2 VDC @
100 mADC
Vce (full on): 1.5 VDC @ 120 mADC Isink
Off state leakage current: 5ua @ 30 VDC
(typical)
Applications
Continuity
Proving Switch
Features
Low Cost
Low Fixed Trip Point
Fully Isolated
Reverse Output Polarity Protected
Self-Powered
AC SWITCHING (-ACA)
OUTLINE DRAWING
CR9321
CR9350
0.27
(6.86)
0.59 (15.0) DIA.
1.081
(27.46)
1.012
(25.70)
AWG # 22, 12 (304) LONG
30.30
1.19
1.775
(45)
Rated Full-on: 0.350 AAC RMS
Turn-on Time: 100 ms. max. @ rated full-on
Turn-off Time: 250 ms. max. to 80% of Vce
Maximum sense current: Continuous: 100 AAC
1 Second: 500 AAC
Frequency*: 50 to 400 Hz
Operating Temperature: -30° C to +60° C
Storage Temperature: -55° C to +85° C
Weight 0.08 LBS.
*All specifications for operation at 60 Hz only
0.875
(22.2)
0.834
(21.18)
in
(mm)
Regulatory Agencies
1.062
(27)
0.875
(22.2)
ELECTRICAL CONNECTIONS
E234389
PART NUMBER
CURRENT SWITCH
-
V+
RED +
CR
V+
I sink
VAC
ORANGE +
BLACK
Vce
BLACK
D
Specifications
BLACK -
Vce
BLACK -
.27 dia. Window
.61 dia. Window
I source
-NPN
-ACA
9321
9350
NPN Transistor Output
PNP Transistor Output
ACA AC Output
M MountingCase
(Optional)
-PNP
The Professional
Energy Monitoring
Company
M N TI
ISO 9001:2008 Quality Management System
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
69
E-mail: [email protected]
Relays, Switches, & Sensors
Off state voltage: 240 VAC RMS max.
Minimum holding current: 10 mA
On state current: 0.8 AAC RMS max. continuous
Off state leakage: 50 ua @ 240 VAC max.
Peak Non-Repetitive Surge Current:
8 AAC RMS (1 cycle, 60 Hz.)