Download Large-panel digital display

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Control system wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Rectifier wikipedia , lookup

Stray voltage wikipedia , lookup

Alternating current wikipedia , lookup

Voltage optimisation wikipedia , lookup

Buck converter wikipedia , lookup

Oscilloscope types wikipedia , lookup

Multimeter wikipedia , lookup

Schmitt trigger wikipedia , lookup

Oscilloscope history wikipedia , lookup

Phone connector (audio) wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Oscilloscope wikipedia , lookup

Opto-isolator wikipedia , lookup

Mains electricity wikipedia , lookup

Electronic paper wikipedia , lookup

Transcript
Standard Devices
Large-panel
digital display
ANZ GR01
Helmut Mauell GmbH • Am Rosenhügel 1–7 • D-42553 Velbert • Telefon (0 20 53) 1 30 • Fax (0 20 53) 1 34 03
Description of function
The ANZ GR 01 large-panel digital display consists of a control unit
and a display unit. The large-panel digital display with 4-digit, 7segment display (plus sign) allows both variable matching of the
signal area to a digitally precise display (e.g. 0 mA to 20 mA = 0°C
to 1800°C) and zero displacement (e.g. 0 mA to 24 mA = -100°C to
1800°C).
The display unit is intended for flush integration into the M24
Mosaik System. The height of the displayed digits is 56 mm. The
brightness of each individual 7-segment display can, to a large
extent, be adjusted to the relevant local conditions using potentiometers, accessible after removing the front panel component.
There is also a separate potentiometer for setting the brightness of
the decimal point. The decimal point can be activated via a jumper
which is also accessible after removing the front panel component.
A further jumper can be used to set the suppression of the leading
zeros. The 24 V DC supply and the LED test input are fed via a 4pin plug to the display unit.
The control unit is supplied with two cables, each with a 4-pin plug.
The control unit supply must be 24 V AC or DC. A built-in transformer ensures that the measuring circuit is isolated from the current
supply. In order to retain the isolation, a supply voltage which is
similarly isolated from the measuring circuit must be activated in the
display unit.
The display are can be adjusted in steps or using precision adjustment. The device has external inputs for a display memory which
allows the display value to be "frozen". The display unit is connected to the control unit by means of two cables with plugs.
Technical data
Input parameters
Connector pin assignment
Control unit
Direct voltage
0 V to 1 V
±1 V
0 V to 2 V
±2 V
0 V to 5 V
±5 V
0 V to 10 V
±10 V
Supply voltage
Supply voltage
plug 1
24 V AC or DC
Indication input
Ue+/ IeUe- / Ie-
plug 1
positive indication
negative indication
Memory input
plug 2
RUN / HOLD +
RUN / HOLD -
memory input separated by
optocouplers, at 24 V DC on
RUN/HOLD+ and 0 V on
RUN/HOLD-, current display
value is saved and displayed
Input impedance
> 1 MΩ
> 1 MΩ
> 1 MΩ
> 1 MΩ
> 1 MΩ
> 1 MΩ
> 1 MΩ
> 1 MΩ
Direct current
Voltage drop
0 mA to 1 mA
approx. 1 V
±1 mA
approx. 1 V
0 mA to 2 mA
approx. 1 V
±2 mA
approx. 1 V
0 mA to 20 mA
approx. 1 V
±20 mA
approx. 1 V
4 mA to 20 mA
approx. 1 V
Intermediate intervals for matching signal area to digitally precise
display possible.
Error limits
Display unit
Test input
LT+
LT-
plug 5
input separated by optocouplers
positive LED test input, 24 V DC
negative LED test input, 0 V
Supply voltage
24 V DC
0V
plug 5
positive supply voltage
zero volt potential
Measured data
Measuring principle
Overall error at + 23 °C
±(0,01 % + 1 digit)
(in relation to display)
with zero displacement additional ±0,01 % of indication value
Temperature coefficient
< 50 ppm / K of display
Zero drift
2 µV / K
Rejection ratio
common mode (CMRR)
series mode (SMRR)
> 80 dB at 50 Hz
> 60 dB at 50 Hz
Display unit
dual slope with automatic
balance
Type
7-segment-LED-display
Colour
red
Averaging time
approx. 80 ms
Digit height
approx. 56 mm
Measuerments per second
3 (typical value)
Digit range
- 9.9.9.9
Sign
automatic "-" display with
negative values
Decimal point
can be set via jumper
Overload
display 0000
Measurement input
Overload
for voltage measurement
for current measurement
2
bipolar, non-earthed
10-fold, max. 250 V
2-fold
The difference between the lowest and highest display values must
be ≥ 500 digits at e.g. 0 mA to 20 mA.
Large-panel digital display ANZ GR01
Supply voltage
Order details
Control unit
24 V AC ±10 %
24 V DC ±20 %
Display unit
24 V DC ±20 %
Power input
control unit
large-panel display
1 W (typical value)
14 W (typical value)
Order number
70 - 91 - 4 _ _
Application
Measurement
parameters
Integration into M 24
Mosaik Systems
direct current
8
Integration into M 24
Mosaik Systems
direct current
9
Standard specifications
Design
as per DIN VDE 0411, part 1
Class
I as per DIN VDE 0411, part 1
Insulation group
B external, A internal as per
VDE 0110 b / 2.79
Degree of protection
Special design
Test voltages
casing IP40 as per DIN 40050
connections IP 00 as per
DIN 40050
casing front IP 54 as per DIN
40050
indication input - current supply
1 kV
Range
0 V to 1 V
or
0 mA to 20 mA
0
±1 V
or
±20 mA
1
0 V to 2 V
or
4 mA to 20 mA
2
±2 V
or
0 mA to 1 mA
3
0 V to 5 V
or
±1 mA
4
±5 V
or
0 mA to 2 mA
5
±2 mA
6
0 V to 10 V or
±10 V
7
Example of an order
Digital large-panel display
Range direct voltage 0 V to 10 V
Order number 70 - 91 - 496
Rear view of Display unit ANZ GR01
Large-panel digital display ANZ GR01
3
Control unit
Plug 1
24 V
A
0V
B
Display unit
DC
AC or DC
Plug 4
Ue+ / Ie+
C
D
Ue- / Ie-
4.2
4.3
D
4 x 0.14 mm2,
finely stranded
4.4
4.5
Plug 2
unassigned
unassigned
RUN / HOLD+
A
B
C
RUN / HOLD-
D
4.6
Plug 3
0.14 mm2,
4x
finely stranded
A
A
LT-
B
24 V DC
C
0V
D
0V
3.1
B1
3.2
B2
3.3
B4
3.4
B8
4 x 0.14 mm2,
finely stranded
Plug 5
LT+
6 x 0.14 mm2, finely stranded
4.1
D2
D4
POL
D1
D3
1a
1c
1b
1d
4 x 0.14 mm2,
finely stranded
Survey diagram
10
perspex, red, matt
20
96 (4 x 24)
66
56
front panel component
1
2
3
1
4
1
4
1
4
1
4.1
approx. 234
288 (12 x 24)
24
1 = brightness setting for 7-segment display
D
C
B
Plug 3
Plug 4
D
B
Plug 1
ca. 107
A
C
Control unit
(ANZ VAR)
D
B
Plug2
A
Dimensioned drawing of mounted unit
5.0014.04 E 97 IIIII
3 = jumper for suppression of leading zeros
right = with leading zeros
left = without leading zeros
4 = jumper B1 to B4 for activating decimal point,
4.1 = no decimal point activated
A
C
2 = brightness setting for decimal point
Plug 5
93