Download Generator Set Motor Starting

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Mains electricity wikipedia , lookup

Power engineering wikipedia , lookup

Opto-isolator wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Buck converter wikipedia , lookup

Electric machine wikipedia , lookup

Commutator (electric) wikipedia , lookup

Voltage optimisation wikipedia , lookup

Electrification wikipedia , lookup

Three-phase electric power wikipedia , lookup

Alternating current wikipedia , lookup

Rectiverter wikipedia , lookup

Brushless DC electric motor wikipedia , lookup

Electric motor wikipedia , lookup

AC motor wikipedia , lookup

Induction motor wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Stepper motor wikipedia , lookup

Transcript
GENERATOR SET
MOTOR STARTING
MOTOR STARTING
The following must be taken into account when motors are started while the load
is on the generator set:
•
Type of motor
•
Method of starting
•
Starting current requirement
•
Voltage dip limitations
•
Sequence in which the motors are started
FORMULA
The generator set power is calculated as follows:
kW gen
Where:
∩ motor
Created by J. M. J. Lloyd
=
0.746 x motor h.p. (output)
∩ motor
=
motor kW (output)
∩ motor
=
motor efficiency
Uncontrolled once printed
DIRECT ON LINE (D.O.L.) STARTING
In D.O.L. starting the motor is started with the windings connected in DELTA so
full voltage is applied directly to the motor terminals on start-up and during
running.
MOTOR STARTING CURRENT
A delta connected motors’ starting current is 6 times its full load current.
ALTERNATOR OVERLOAD CAPACITY
The generator set alternators’ overload capacity is 2.5 times its rated output.
FORMULA
The ratio of generator set kW to motor kW is calculated as follows:
Created by J. M. J. Lloyd
kW gen x 2.5
=
6 x motor kWm
∩m
kW gen
=
6 x motor kWm
2.5 x 0.9
kW gen
=
2.67 times motor KWm
Uncontrolled once printed
STAR DELTA STARTING
In Star Delta starting the motor is started with the windings connected in Star
so the starting voltage is reduced by √3.
MOTOR STARTING CURRENT AND TORQUE
The starting current is reduced to 2 times its full load current
The starting torque is reduced to 1/3 of the D.O.L. value
FORMULA
The ratio of generator set kW to motor kW is calculated as follows:
Created by J. M. J. Lloyd
kW gen
=
2 x motor kWm
2.5 x 0.9
kW gen
=
0.9 times motor kWm