* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download smart voltage reduction
Spark-gap transmitter wikipedia , lookup
Stepper motor wikipedia , lookup
Immunity-aware programming wikipedia , lookup
Power engineering wikipedia , lookup
Pulse-width modulation wikipedia , lookup
Power inverter wikipedia , lookup
Electrical ballast wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Three-phase electric power wikipedia , lookup
Current source wikipedia , lookup
Resistive opto-isolator wikipedia , lookup
History of electric power transmission wikipedia , lookup
Electrical substation wikipedia , lookup
Schmitt trigger wikipedia , lookup
Power MOSFET wikipedia , lookup
Opto-isolator wikipedia , lookup
Power electronics wikipedia , lookup
Buck converter wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Surge protector wikipedia , lookup
Voltage regulator wikipedia , lookup
Alternating current wikipedia , lookup
Stray voltage wikipedia , lookup
TechAdvantage 2015 SMART VOLTAGE REDUCTION David Aldrich, P.E. Beckwith Electric BECKWITH ELECTRIC CO.INC. 727.544.2326 [email protected] Discussion LTC Control Basics Smart Voltage Reduction What, Why? How- Historical and “Smart” Methods Interaction with Capacitors Improving CVR Factor (CVRf) LTC Control Basics To accomplish voltage regulation, these minimum parameters must be defined Bandcenter (V) Bandwith Time Delay LTC Control Basics Additional Functions of Modern LTC Controls Line Drop Compensation Blocking Reverse Power Voltage Reduction Tap Position Monitoring Transformer Paralleling Advanced Smart Grid Communications Data Logging, SOE, Power Quality Condition Based and Automated Maintenance Conservation Voltage Reduction Conservation Voltage Reduction (CVR) Part of Voltage/VAr Optimization (VVO) Intentional lowering of distribution circuit voltage within lower band of allowed ANSI C84.1 (2006) Standard for Electric Power Systems and Equipment – Voltage Ratings • • Range A is the optimal voltage range Range B is acceptable, but not optimal VVO and CVR - Why Lowering distribution voltage levels during peak periods to achieve peak demand reductions Reducing voltage levels for longer periods to achieve electricity conservation Reducing energy losses in the electric distribution system Expected benefits include deferral of capital expenditures, energy savings, and greater operational flexibility and efficiency Voltage and Reactive Power Management – Initial Results: US DOE, 12/12 Conservation Voltage Reduction - What Goal of voltage reduction is to reduce load V= I * R for resistive load The lower the V the lower the I The lower the I, the lower the I2R = W (constant Z load) Ex., incandescent lights, strip heaters Not true if load is not constant power type (constant PQ load): Ex., motors, power supplies Can be deployed at: All times For load reduction periods During system emergencies when the voltage is collapsing due to more load than available generation or supply % VR pf 1.0 Load Reduction pf 0.9 Load Reduction 2% 1.5 % 0.5% 4% 3.0 % 2.0% EPRI “Distribution Green Circuits” Report - 2010 Load Models and CVR Factor Load models Constant Power (PQ) Constant Impedance (Z) Constant Current (I) CVRf = ∆P/∆V 0.8 to 1 is typical Greater than 1 is really good Load current changes inversely to the change in voltage Load current changes linearly with the change in delivered voltage, and the demand varies as a squared function of the voltage change Power delivered to the load varies linearly with the change in voltage delivered to the load Evaluating Conservation Voltage Reduction with WindMil® - Milsoft Substation Traditional VVO & CVR Cap #2 Cap #1 With both caps on VVO With cap #1 on only CVR – Conservation Voltage Reduction Voltage Profile Capacitors affect voltage level, losses, capacity, etc. Loads only General Rules for Coordination Series Regulators Regulator closest to source taps first (shortest time delay) Multiple Cap Banks (Voltage Controlled) Cap banks furthest from source close first, open last Caps switch before regulators Decreases LTC/regulator operations Save asset Saves maintenance $$$ Historical Voltage Reduction Load Reduction called with Load Management Software Load Reduction Software » SCADA » Output Relay » LTC/Regulator Input Output relays connected to auxiliary summing transformer with multiple taps Auxiliary summing transformer has taps connected/disconnected by control relays to create a higher sensing voltage the LTC or Regulator Control This higher voltage, sensed by the LTC/Regulator Control, would now cause the control to issue tap-down commands to lower voltage The control would not know that it is in voltage reduction mode, and would simply react to the sensed voltage change LINE VT SUMMING TRANSFORMER SCADA CONTACTS FOR VOLTAGE REDUCTION LTC CONTROL Historical Voltage Reduction - Disadvantages The time delay to tap is still in play The percentage of reduction is fixed due to the taps on the summing transformer Each percentage reduction point required an auxiliary relay If the communications failed while in reduction, the LTC or Regulator would remain in voltage reduction Voltage Reduction in Modern Controls Controls typically support three reduction levels Reduction level range set from 1 -10 % Typical for static or digital controls: Contact sensing inputs The contacts would be from a SCADA RTU and/or local switches For digital controls, additionally: Using the integrated HMI on the control (buttons) Using PC software locally Using SCADA interface (ex., DNP from RTU) Using Ethernet by radio (ex., DNP TCP/IP) Using Cellular or other medium Example for Local Interface on Control Typical Digital Voltage Regulator Control HMI and Buttons Voltage Reduction LED Contacts Used for Voltage Reduction Typical Digital Voltage Regulator Control Voltage Reduction in Modern Controls Voltage Reduction changes the bandcenter to induce controls to lower voltage instead of increasing sensed voltage Signal to control can be: o SCADA to contacts, contacts to control o Direct SCADA DNP write to control Time delay skipped on initial voltage reduction command Because bandcenter is being altered, entering reduction does not always reduce voltage, or reduce near amount of requested reduction Voltage Reduction Bandcenter set to 122V, Bandwidth of 3V Apply a 2% reduction 122 – 122* 0.98 = 119.56 or 119.6 Upper rail = 119.6 + (3/2) = 121.1 Lower rail = 119.6 – (3/2) = 118.1 123.5 3 120.7 122.0 121.1 120.5 120.7 Before Reduction 119.6 3 118.1 After Reduction Assume 0.75V/tap (10V/16 taps = 0.75V/tap) 120.7V before reduction, after reduction that value is still in-band Results in no voltage reduction, 0% Voltage Reduction Bandcenter set to 122V, Bandwidth of 3V Apply a 3% reduction of 122 – 122* 0.97 = 118.34 or 118.3 Upper rail = 118.34 + (3/2) = 119.8 Lower rail = 118.34 – (3/2) = 116.8 123.5 3 119.95 122.0 120.5 119.8 120.7 Before Reduction 119.2 118.3 3 116.8 After Reduction Assume 0.75V/tap (120*10%=12V; 12V/16 taps = 0.75V/tap) 120.7V before reduction, 2 Taps Down Taken Tap 1 = 119.95, Tap 2 = 119.2 % = ( | V1 - V2 | / ((V1 + V2)/2) ) * 100 = ( | 120.7 - 119.2 | / ((120.7 + 119.2)/2) ) * 100 = 1.25% reduction Voltage Reduction Bandcenter set to 122V, Bandwidth of 3V Apply a 4% reduction of 122 – 122* 0.96 = 117.12 or 117.1 Upper rail = 117.1 + (3/2) = 118.6 Lower rail = 117.1 – (3/2) = 115.6 123.5 3 119.95 119.2 122.0 118.45 120.5 120.7 118.6 117.1 Before Reduction After Reduction 3 115.6 Assume 0.75V/tap (120*10%=12V; 12V/16 taps = 0.75V/tap) 120.7V before reduction, 3 Taps Down Taken Tap 1 = 119.95, Tap 2 = 119.2, tap 3 = 118.45 % = ( | V1 - V2 | / ((V1 + V2)/2) ) * 100 = ( | 120.7 - 118.45 | / ((120.7 + 118.45)/2) ) * 100 = 1.88% reduction Voltage Reduction A “Block Lower” setting of 118 will stop control from performing voltage reduction if low limit setpoint is violated Be sure “Block Lower” setting does not interfere with voltage reduction 123.5 3 119.95 119.2 122.0 Block Lower 118.45 120.5 120.7 118.6 117.1 115.6 Before Reduction After Reduction 3 Voltage Reduction Turnoff Timer Used to turn off Voltage Reduction (VR) if entered via SCADA or pulsed contacts Intent is to remove voltage reduction mode if SCADA is lost and communications goes down Control will automatically remove VR once the timer expires, even if SCADA is still communicating o New signal during timing interval would keep VR going Voltage Reduction - Summary o The control will never reduce the actual voltage by the percentage requested o The larger the bandwidth, the less actual reduction o The “Block Lower” setting: Blocks tap lowers if measure voltage is less than setpoint o No time delay when entering or exiting voltage reduction Voltage Reduction – Present Method If the goal of voltage reduction is to reduce voltage, we want to finish reduction on lower end of band, not higher end Previous example: 3% request, 1.25% delivered 123.5 3 119.95 122.0 120.5 119.2 119.8 120.7 Before Reduction 118.3 116.8 After Reduction 3 Smart Voltage Reduction Apply a 3% reduction of 122 – 122* 0.97 = 118.34 or 118.3 Upper rail = 118.34 + (3/2) = 119.8 Lower rail = 118.34 – (3/2) = 116.8 Temporarily: • Disable Upper Band Limit • Use Bandcenter as Upper Band Limit 123.5 3 119.95 119.2 118.4 122.0 120.5 120.7 Before Reduction 117.7 119.8 118.3 3 116.8 After Reduction Assume 0.75V/tap (120*10%=12V; 12V/16 taps = 0.75V/tap) 120.7V before reduction, 4 Taps Down Taken Tap 1 = 119.95, Tap 2 = 119.2, Tap 3 = 118.4, Tap 4 = 117.7 % = ( | V1 - V2 | / ((V1 + V2)/2) ) * 100 = ( | 120.7 - 117.7 | / ((120.7 + 117.7)/2) ) * 100 = 2.52% reduction Leaving Voltage Reduction – Present Method Unintended Results: Cap Banks May Stay On Too Long REDUCTION kV NORMAL kV TEST MVAr NORMAL MVAr Typically when entering reduction, all switched capacitors will close as the voltage is reduced (assumed voltage control) This may cause circuits to be leading when in reduction When leaving reduction, some of the capacitors need to be switched off to get back to unity power factor Leaving Voltage Reduction - Present Method 119.2 123.5 119.95 122.0 120.5 119.8 3 3 120.7 118.3 116.8 During Reduction Normal Operation This may not be a high enough voltage to cause voltage controlled capacitors to switch off Leaving Voltage Reduction: Smart Voltage Reduction Method 119.2 119.95 122.2 121.5 123.5 122.0 3 120.5 119.8 3 The extra voltage will now allow the capacitors to start timing to an open 120.7 118.3 116.8 During Reduction Normal Operation Lower band is temporarily disabled to force voltage to finish between bandcenter and high band edge Once voltage crosses bandcenter, lower band edge becomes active again Cap Banks Opening After Leaving Reduction Smart Method Employed REDUCTION kV NORMAL kV TEST MVAr NORMAL MVAr Smart Voltage Reduction About Those Capacitors... Proper coordination with switched capacitor banks will maximize the amount of reduction possible The majority of the load on any feeder is at the feeder. The load drops more the further we get from the substation o (EPRI: 50% Load, 1st 25% of Feeder) To get maximum benefit out of reduction, the lowest voltage needs to be were the highest current is (Zone 1) 115 KV 12 KV 12 KV XFMR 12 KV Substation 400 amps 600 kVar 1.1 V 300 amps 115 KV 115 KV 600 kVar 0.8 V Zone 1 600 kVar 1.9 V 600 kVar 2.1 V 100 amps 50 amps Zone 2 Positive Reactive Compensation Using a positive X to bias bandcenter during reduction would allow control to further lower voltage close to regulator as VArs go leading Push voltage lower as control detects leading VArs Lowest voltage will be at regulator – voltage will be higher down feeder as VArs go leading Positive Reactive Compensation Setting added so control treats VArs differently in voltage reduction Allows control to reduce voltage further as down line as capacitors close If capacitors are out-of-service, control will dynamically know not to lower voltage as much while in reduction No communications required Smart Voltage Reduction About Those Capacitors... Secondary Voltage Down stream capacitors, when closed will provide voltage support at end of circuit Regulator detecting a leading power is an indication that downstream voltage is higher than source voltage due to voltage rise of cap banks This allows regulator to reduce voltage even lower 126 Vac 126 “Flipped Circuit” 120 Traditional VVO 114 Vac 114 0 1 2 3 4 Distance 5 6 7 8 Present Method: V1 Pre Smart Method: V1 Post Applied on LTC CVRf of 1.2 to 1.4 obtained "Can a Grid be Smart without Communications? A look at an Integrated Volt VAR Control (IVVC) Implementation," Barry Stephens, Georgia Power; Bob McFetridge, Beckwith Electric, April 25, 2012 Summary A new method exists for voltage reduction that delivers closer to called percentage Coordination of capacitors with LTCs and regulators provides VVO Using positive reactance compensation when in voltage reduction, along with proper amount of capacitance, allows “circuit flipping” of voltage profile for even greater CVR factor TechAdvantage 2015 QUESTIONS? SMART VOLTAGE REDUCTION David Aldrich, P.E. Beckwith Electric BECKWITH ELECTRIC CO.INC. 727.544.2326 [email protected] References ANSI C84.1, “Standard for Electric Power Systems and Equipment – Voltage Ratings” “Distribution Green Circuits Interim Report – 2010,” EPRI “Evaluating Conservation Voltage Reduction with WindMil®,” Milsoft “Voltage and Reactive Power Management – Initial Result,” US DOE, 12/12 "Can a Grid be Smart without Communications? A look at an Integrated Volt VAR Control (IVVC) Implementation," Barry Stephens, Georgia Power; Bob McFetridge, Beckwith Electric, April 25, 2012 Annex: Percent Calculations