Download discharge of high voltage lines and capacitors banks

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Pulse-width modulation wikipedia , lookup

Ground (electricity) wikipedia , lookup

Electromagnetic compatibility wikipedia , lookup

Coilgun wikipedia , lookup

Power engineering wikipedia , lookup

Power inverter wikipedia , lookup

Stepper motor wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Islanding wikipedia , lookup

Electrical ballast wikipedia , lookup

Ohm's law wikipedia , lookup

Current source wikipedia , lookup

Capacitor wikipedia , lookup

Power electronics wikipedia , lookup

Three-phase electric power wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power MOSFET wikipedia , lookup

Schmitt trigger wikipedia , lookup

Triode wikipedia , lookup

Capacitor discharge ignition wikipedia , lookup

Electrical substation wikipedia , lookup

Metadyne wikipedia , lookup

Distribution management system wikipedia , lookup

Transformer wikipedia , lookup

Rectifier wikipedia , lookup

Resonant inductive coupling wikipedia , lookup

History of electric power transmission wikipedia , lookup

Buck converter wikipedia , lookup

Surge protector wikipedia , lookup

Opto-isolator wikipedia , lookup

Voltage regulator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Stray voltage wikipedia , lookup

Alternating current wikipedia , lookup

Voltage optimisation wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
DISCHARGE OF HIGH
VOLTAGE LINES AND
CAPACITORS BANKS
THROUGH INDUCTIVE
VOLTAGE TRANSFORMERS
In addition to the accurate measurement
of the voltage on HV electricity networks,
inductive voltage transformers canal so be
used to discharge high voltage trapped
charges.
When opening the circuit breakers of an
energized HV line and isolating it from earth,
the voltage of this line is trapped in the high
voltage conductors. This is a DC voltage.
This trapped DC voltage can cause over
voltages during the reconnection of the line.
It can also cause insulation problems due to
the polarization of insulating materials (for
example the SF6).
One of the most practical ways to eliminate
these trapped charges in the line is to place
an inductive voltage transformer. These
inductive voltage transformers must be
sized properly to withstand the mechanical
stresses caused by the discharge current of
the line through the primary winding of the
transformer. We must also take into account
the increase in the temperature of the primary
coil when the discharge of the line occurs,
because all the energy trapped in the line will
be dissipated by the primary winding of the
transformer, causing a substantial increase in
the temperature of the winding.
Another interesting application is the
discharge of capacitor banks. In the same
way as with the lines, when a capacitor
bank is disconnected,electric charges are
trapped in the capacitor bank, causing a
big accumulation of energy. This trapped
DC voltage in the capacitor bank can cause
overvoltage problems on high voltage
equipment when reconnecting the capacitor
bank. This can be easily avoided by using an
inductive voltage transformer to discharge
the capacitor bank.
When discharging capacitors banks it is often
an important requirement that the discharge
is done quickly with the voltage reduced
down to a few volts.
Another usual and important requirement
in the case of capacitors banks is to enable
a reconnection of the discharged capacitor
bank within a short period of time. Normally
the number of possible reconnections is
limited to 2.
This number of reconnections is important
because the heating of the primary winding of
the transformer occurs very fast, and the time
between two consecutive discharges is not long
enough to allow the primary winding to dissipate
all the energy. These successive discharges
increase the heating of the primary winding of
the inductive voltage transformer in a linear way,
being the final temperature increase the addition
of the temperature increases of both discharges.
The graphic shows a discharge of a HV line
through an inductive voltage transformer.
The blue line shows how the voltage (in kV) is
reduced following an oscillating pattern. We can
notice two different behaviours: one during the
period of time when the core is saturated and
another when the core is not saturated. In green
we can see the current (in Amps) that appears
during the discharge.
197.7 kV
100 kV
15 A
10 A
5A
0A
-5 A
-10 A
-15 A
-20 A
-25 A
-30 A
-35 A
0 kV
-100 kV
-200 kV
>>
-329.6 kV
0s
1
0.400 s
0.800 s
V (U6:P1)
2
I (R1)
1.200 s
1.600 s
2.000 s
2.400 s
Time
Inductive voltage transformers are built
specifically to comply with these requirements.
Therefore, they can dissipate the energy stored
in HV lines and capacitor banks, thus protecting
the insulation of HV equipment against
overvoltages caused by the reconnection of
these lines or capacitor banks with trapped
charges. Simultaneously, inductive voltage
transformers can provide a reliable and accurate
voltage output that can be used both for
measurement and protection.
Inductive voltage transformers can be used
to discharge lines or capacitors banks at any
voltage level, being the only limitation the
amount of energy to discharge.