Download BEWARE OF PHASE CONTROL INTO RESISTIVE LOADS

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Rectifier wikipedia , lookup

Standby power wikipedia , lookup

Resilient control systems wikipedia , lookup

Electrical ballast wikipedia , lookup

Wireless power transfer wikipedia , lookup

Power over Ethernet wikipedia , lookup

Decibel wikipedia , lookup

Audio power wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Electrical substation wikipedia , lookup

Buck converter wikipedia , lookup

Power factor wikipedia , lookup

Electric power system wikipedia , lookup

Stray voltage wikipedia , lookup

Control system wikipedia , lookup

Islanding wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Power inverter wikipedia , lookup

Electrification wikipedia , lookup

Metadyne wikipedia , lookup

History of electric power transmission wikipedia , lookup

Power engineering wikipedia , lookup

Power electronics wikipedia , lookup

Switched-mode power supply wikipedia , lookup

AC adapter wikipedia , lookup

Three-phase electric power wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
BEWARE OF PHASE CONTROL
INTO RESISTIVE LOADS
Nichrome type heaters should be controlled with a zero cross type of power control to reduce the
electrical noise generated, and to insure that the power factor is high.
Tungsten and other heaters with a high resistance change, (cold to hot), need to be controlled by
phase angle control so that they can be powered slowly (soft start) to allow a gradual resistance
change.
Phase control into resistive loads can cause several problems.
•
•
•
Electrical noise. The fast turn on of phase control produces harmonics that can cause
problems with sensitive equipment, and reduce heater life.
Power Factor Concerns. The delayed turn on causes the current to be behind the voltage,
which results in a reduced power factor. This can cause reduced voltage levels in the plant,
and causes increased electricity cost.
DI/DT. The rapid turn, on inside the sine wave, causes very high DV/DT (delta
voltage/delta time) ratios. Without any circuit inductance wired after the power control, the
amperes per microsecond rating of the SCRs could be exceeded, causing premature failure.
This can also put voltage notches in the sine wave that can confuse the zero cross detector.
The normal failure mode is nuisance power shut downs. The control will soft start to
approximately 30% power, detect an extra zero cross pulse, shut down, then restart.
Scope picture
Watlow Winona
1241 Bundy Blvd
Winona, MN 55987
Telephone (507) 494-5656
© 2005 Watlow Electric Manufacturing Company
1
LCr 04/01/05
BEWARE OF PHASE CONTROL
INTO RESISTIVE LOADS
These problems are usually worse in a small plant where the heating load is a large percentage of
the power available to the building. Operating from a generator may also be a problem.
There are several ways to correct or eliminate this problem.
•
•
•
•
Add inductors between the power control and the heater. This will reduce the DI/DT, and
reduce the voltage notches in the sine wave. Adding inductors also increases heater life.
Use “Power Factor correction capacitors” ahead of the power control to stiffen the line, fill
the voltage notches in the sine wave and improve the power factor.
Reconnect the system to a stiffer (lower impedance) power source.
Make sure that all connections are tight and the wire size is adequate.