Download 48-Pulse Based SSSC (Static Synchronous Series

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Immunity-aware programming wikipedia , lookup

Capacitor wikipedia , lookup

Ground (electricity) wikipedia , lookup

Transformer wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Wireless power transfer wikipedia , lookup

Decibel wikipedia , lookup

Electrification wikipedia , lookup

Power factor wikipedia , lookup

Electrical ballast wikipedia , lookup

Power over Ethernet wikipedia , lookup

Audio power wikipedia , lookup

Ohm's law wikipedia , lookup

Current source wikipedia , lookup

Electric power system wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Schmitt trigger wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Transformer types wikipedia , lookup

Triode wikipedia , lookup

Power MOSFET wikipedia , lookup

Electrical substation wikipedia , lookup

Rectifier wikipedia , lookup

Three-phase electric power wikipedia , lookup

Metadyne wikipedia , lookup

Power engineering wikipedia , lookup

Voltage regulator wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Surge protector wikipedia , lookup

Distribution management system wikipedia , lookup

Stray voltage wikipedia , lookup

Opto-isolator wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Islanding wikipedia , lookup

Buck converter wikipedia , lookup

History of electric power transmission wikipedia , lookup

Voltage optimisation wikipedia , lookup

Power inverter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Alternating current wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
48-Pulse Based SSSC (Static Synchronous Series Compensator),
an Evaluation of its Performance
R. L. V. ARNEZ, L. C. ZANETTA
Department of Electrical Engineering
University of São Paulo
Av. Prof. Luciano Gualberto, Trav.3, n° 380, S.P.
BRAZIL
ricleon, [email protected]
Abstract: This paper presents a performance comparison between a 24-pulse and a 48-pulse phase-shift VSI
based SSSC. Initially a brief but useful description of the SSSC basic operation, is presented. Simulations of the
two configurations have been carried out using the EMTP program. It has been found that the 48-pulse based
SSSC, may well avoid the presence of harmonic filters, because it presents a nearly sinusoidal set of threephase voltage waveforms which clearly agree with power quality standards. It is also shown the SSSC ability in
modifying instantaneously both active and reactive power. Within the current electric market, a continuous
assessment of the technical performance of this device and the other FACTS members, is needed.
Keywords: SSSC, FACTS, Series Compensation, THD, Transmitted Power, EMTP.
1 Introduction
V1
Solid state electronics is developing very fast and
research is needed to determine the feasibility of
the use of this new devices within the FACTS
(Flexible AC Transmission Systems) technology.
The use of FACTS devices in the present
deregulated electric market, is bringing the users of
high voltage transmission systems fresh
opportunities as well as new challenges. So far,
they appear to be one of the most important
alternatives to overcome both the inflexible
condition of most of the power systems and the
continuously growing demand of power in them.
Recent developments in power research have lead
to FACTS devices to modify the power flow
locally within a power grid. As a third generation
member of the FACTS devices, the SSSC (Static
Synchronous Series Compensator) has the ability to
perform some functions which no other
conventional equipment with similar tasks (e.g.
synchronous condenser, phase shifter transformer,
etc) could perform.
At present, little attention has been paid to this
device probably because it has been obfuscated by
its akin the UPFC (Unified Power Flow
Controller). It is to be pointed out that the SSSC
forms part of the UPFC; yet, it performs one of the
most important functions within the UPFC [2].
The objective of this paper is to focus and evaluate
the performance of the SSSC (Fig. 1) when
operates under a 24-pulse and a 48-pulse phaseshifted inverter configurations.
R1  jX1
Vq
R2  jX 2
V2
IL
Vdc
Fig.1 Two machine system with a SSSC
2 SSSC Analysis
Basically, the SSSC is a voltage source inverter
(VSI) based device which injects an alternating
nearly sinusoidal series voltage that is in quadrature
(90°) with the line current. The voltage coming
out from the set of GTO (Gate Turn-Off Thyristors)
based inverters, is controlled both in amplitude and
phase angle.
When the SSSC injected voltage is set to lead the
line current, it behaves like an inductive reactance
in series with the transmission line causing the line
current, therefore the power flow, to decrease.
Conversely, when this voltage is set to lag the line
current, it behaves like a capacitive reactance in
series with the transmission line causing the line
current, therefore the power flow, to increase [4],
[6]. The former is said to be operating in the
inductive mode, whereas the latter in the capacitive
mode. Both the magnitude and the direction of the
quadrature injected voltage, can be controlled. The
above description can be better comprehended with
the help of Figs. 2 and 3, in which a simple power
transmission system and its vector diagrams, are
represented.
 jVq
VX
IL
V1
V2
Fig.2 Simplified power transmission system with a
SSSC
Vq
VX
VX
VX
Vq
VX '
V1
IL
V2
V1
IL
V2
VX '
V1
V2
IL



(a)
(b)
(c)
Fig.3 Vector diagrams in presence of a SSSC:
(a) no compensation, Vq=0
(b) inductive compensation
(c) capacitive compensation
Using the above vector diagrams, the transmitted
power equation in presence of the SSSC can be
obtained [3], [6] with no difficulty, as shown:
*
S 2  V2 I L  P2  jQ2
(1)
V1  V1e
j
V2  V2 e
Vq  Vq e

2
j
j
(2)

2

2
 V1  Vq  V2 

I L  
X


(3)
(4)
Using (1), (2), (3) and (4), as well as regarding the
system as symmetrical, yields,
VVq
V2

Sin 
Cos
X
X
2
VVq
V2

Q2  ImS 2  
( 1  Cos ) 
Sin
X
X
2
P2  eS 2  
(5)
(6)
Note in (5), how despite the phase angle difference
between the sending and the receiving end voltage
() would be equal to zero, it is possible to transmit
real power through the line. Also, if the series
voltage ,Vq, impressed across the line would have a
reversed polarity (i.e. with the same line voltage
drop polarity), the transmitted power can be
decreased. This being a situation as if the inductive
line reactance was increased. Yet, if that reversed
polarity from the compensating voltage is set to be
larger than the uncompensated voltage existing
across the line, then, power flow can be reversed
[1], [4], [6].
Fig. 4, depicts the configuration used to simulate
the 48-pulse inverter waveforms. The 24-pulse
inverter configuration will be constituted by only
half the number of the 6-pulse inverters shown in
Fig. 4. The shifting output transformer technique to
obtain multilevel voltage operations is well known
from long time. It consists in summing the output
of different inverters by means of suitable phase
shifting transformers, in this way an intrinsic
harmonic reduction and a certain voltage level, can
be obtained.
It should be noted that the 24 and 48-pulse
inverters analysed use Y-Y and -Y transformer
connections as a magnetic interface with the ac
system. Both multilevel inverter configurations
utilise the so called QHN (Quasi Harmonic
Neutralised) technique for harmonic cancellation
[6].
It can be seen (Fig. 4a) that only one dc capacitor is
used for the eight voltage-sourced inverters. Each
inverter used, is assumed to be lossless, that is, no
losses are present as a result of the switching
condition. Likewise, the vector diagram of the
output voltages from the 8-inverter arrangement
along with their respective phase-shifted angles, is
shown in Fig. 4(b). The left circle containing the
output vectors of the first four inverters, whereas
the right circle corresponding to the rest (i.e. output
vectors from inverters 5, 6, 7 and 8).
The control system used in this SSSC model,
utilises measurements of voltages and currents at
the SSSC point of connection with the ac system.
Details of the control system are considered to be
beyond the scope of the present analysis.
with the converter regarded as lossless, at all
instant the power relationship, Pdc=Pq, will have to
be complied by the SSSC. The term, Pq, being the
power injected to the ac system.
Pq  vqa i2 a  vqb i2b  v qc i2c
(9)
Transmission Line
0o
Magnetic Circuit
Vdc
 7.5o
 15o
Υ
0o

30o
Υ
0o

30o
Υ
0o

30o
Υ
0o
Pdc
idc
Vdc
i2 a
i2b
i2 c
 22.5o
 30 o
 37.5o
Pq
Vqa
Vqb
Vqc
Fig.5 SSSC converter (VSI)
 45o
 52.5o

Υ
30o
(a)
C8 (-240-52.5°)
C7 (-240-45°)
C6 (-240-37.5°)
C5 (-240-30°)
C4 (-240-22.5°)
C3 (-240-15°)
C2 (-240-7.5°)
C1 (-240°)
A1 (0°)
A2 (-7.5°)
A3 (-15°)
A4 (-22.5°)
B8 (-120-52.5°)
B7 (-120-45°)
B6 (-120-37.5°)
B5 (-120-30°)
B4 (-120-22.5°)
B3 (-120-15°)
B2 (-120-7.5°)
B1 (-120°)
A5 (-30°)
A6 (-37.5°)
A7 (-45°)
A8 (-52.5°)
Equations (7) and (8) rule the dynamics of the
SSSC. During the periods in which the dc capacitor
voltage is equal to its nominal value the
instantaneous real power at the SSSC terminals is
practically zero. The SSSC can be continuously
controlled to inject the quasi sinusoidal ac voltage
for leading or lagging the line current by /2 rad. A
permanent track of the line current along with the
ancillary controls of the series compensator will
permit to set the proper PI controller values for
having a fast or a moderated response. Generally, a
sluggish PI response may not provide enough
response time to the SSSC for coping with the
system transients. Conversely, a fast PI response
causes some oscillations over the compensation
characteristic.
(b)
Fig.4 SSSC with a 48-pulse arrangement:
(a) Phase-shift transformer configuration
(b) Output voltage vector diagram of the
8-converter set
4 Results
3 SSSC Dynamics
The power balance between the converter input and
output power is chiefly required to maintain the dc
capacitor appropriately charged, thus keeping the
dc voltage, Vdc, around its nominal value.
If harmonics are neglected, the dc current, idc, and
the capacitor voltage have the following relation,
(Fig. 5):
idc  C
dvdc
dt
(7)
also,
idc 
Pdc
vdc
(8)
The EMTP program constituted as the main tool to
validate the analysis presented in this paper. The
curves shown below are based upon the phase
control based technique which involves 4 and 8
multi-connected phase shift 6-pulse inverters,
respectively.
Figs. 6(a) and (b) show that both configurations, in
general, have a good performance under balanced
conditions, and they are capable to have quick
transient responses (about ¼ cycle). This will
mainly depend upon the PI controller adjustment in
the program control system.
To realise an evaluation in the waveform
improvement,
the
voltage
waveforms
corresponding to phase A of Figs. 6(a) and (b),
were plotted separately and are shown next.
0.35
0.25
0.15
0.05
-0.05
-0.15
-0.25
-0.35
0.350
0.372
0.394
(file SSSC24.PL4; x-var t) t: E2APU t: E2BPU
0.416
t: E2CPU
0.438
0.460
0.416
t: E2CPU
0.438
0.460
(a)
0.35
0.25
0.15
0.05
-0.05
-0.15
-0.25
-0.35
0.350
0.372
0.394
(file SSSC48.PL4; x-var t) t: E2APU t: E2BPU
(b)
Fig. 6 SSSC voltage injection from a:
(a) 24-pulse inverter
(b) 48-pulse inverter
0.35
Vq-24
0.25
0.15
0.05
-0.05
-0.15
Ideally, the phase-shifted 24 and 48-pulse inverter
configuration should only present harmonics of
order ( 24n  1 ) and ( 48n  1 ) , respectively. The ac
output voltage having harmonic magnitudes of:
Vh_24=1/23rd, 1/25th, 1/47th, 1/49th, ...
Vh_48=1/47th, 1/49th, 1/95th, 1/97th, ...
However, in the QHN technique using Y-Y, -Y
transformer connections, cancellation of the low
order harmonics in relation to the total pulse
number (i.e. 24, 48-pulse) is not realised
thoroughly. That is, the 24-pulse configuration
presents harmonics of order: 11th, 13th, 23rd, ... etc.
Similarly, the 48-pulse configuration presents
harmonics of order: 11th, 13th, 23rd, 25th, 35th, 37th,
47th ,... etc.
The above, thus, agreeing with the term quasi
harmonic neutralised configuration designated to
this technique of transformer arrangement. An
alternative to cancel out the low order harmonics
pertaining to the 24 and 48-pulse configurations
may well be with the use of delta-zig-zag or wyezig-zag transformers as magnetic interface between
the inverter and the ac system [5].
When a 24-pulse configuration is used, there is
typically a need to install passive filters on the
output terminals of the inverter, to reduce the
harmonic content of the output voltage waveforms.
High levels of harmonics will affect industrial
power system equipment in a number of ways,
prominently overheating and misoperation.
According to IEEE 519-1992 standard, the total
harmonic distortion (THDv) voltage shall not
exceed 5.0% of the fundamental 60 Hz frequency,
for voltages below 69 kV. In a simple way the
THDv in voltage can be expressed as (10),
-0.25

-0.35
0.440
0.455
0.470
(file SSSC24.PL4; x-var t) t: E2APU
0.485
0.500
0.515
0.530
THD v 
(a)
Vq-48
V1
* 100%
(10)
V 1: rms value of the fundamental voltage component.
Vh : hth harmonic voltage component (rms).
0.15
0.05
-0.05
-0.15
-0.25
-0.35
0.440
0.455
0.470
(file SSSC48.PL4; x-var t) t: E2APU
h2
2
h
where,
0.35
0.25
V
0.485
0.500
0.515
(b)
Fig. 7 Series injected voltage, phase A
(a) 24-pulse arrangement
(b) 48-pulse arrangement
0.530
The THDv evaluation for both inverter waveforms
shown in Fig. 7, was realised. The corresponding
results are summarised in Table 1. Note in Table 1,
the less percentage of THDv present in the 48-pulse
configuration compared to the 24-pulse case, as the
former have a nearer sinusoidal waveform than the
latter.
Table 1. THDv of the configurations analysed
Harmonic
component
1°
11°
13°
23°
25°
35°
37°
47°
49°
24-Pulse
(p.u. value)
1.00000000
0.02490476
0.01914285
0.04876486
0.03980952
0.00675924
0.00728571
0.02185714
0.02647952
48-Pulse
(p.u. value)
1.00000000
0.02286387
0.01796721
0.00513264
0.00437291
0.00498503
0.00673892
0.02454539
0.01973964
THDv
7.89%
4.42%
Another big improvement occurs in the voltage of
the dc capacitor (Fig. 8). The dc capacitor is used
as a temporary energy storage device, making
possible a continuous exchange of the energy
between the ac system and the SSSC.
0.30
frequent update of the charge in the dc capacitor,
compared to the 24-pulse case. Thus, reducing
notably the ripple existing in the dc voltage.
An ideal VSI, would provide a sinusoidal output
voltage and would have zero input current from the
dc capacitor [1]. In this way, the dc capacitor
would assist the VSI only during transient periods
of the SSSC operation.
The SSSC ability to control and modify
instantaneously the transmittable power, is shown
in Fig. 9. Observe the form in which it can reduce
or increase power almost instantaneously. The
referred response corresponds to the condition
when power is flowing from point 1 to 2 in the
simplified system shown in Fig.1.
The ideal condition of the converters as well as the
assumptions considered in this paper may lead to
an excessively optimistic performance of the SSSC.
Therefore, for an actual SSSC it should be realised
a deep analysis on the assumptions regarded,
namely: losses in the converters, unbalanced
condition of the ac system and some constraints
related to the SSSC operation.
1.5
0.26
P2
1.0
0.22
0.5
0.18
0.0
Q2
0.14
-0.5
0.10
0.20
0.24
0.28
(file SSSC24.PL4; x-var t) t: VDCPU
0.32
0.36
0.40
(a)
-1.0
-1.5
0.0
0.1
(file SSSC.PL4; x-var t)
0.2
0.30
0.3
0.4
0.5
0.6
Time (s)
Fig.9 Receiving end active and reactive power
0.26
0.22
4 Conclusions
0.18
0.14
0.10
0.20
0.24
0.28
(file SSSC48.PL4; x-var t) t: VDCPU
0.32
0.36
0.40
(b)
Fig.8 Dc voltage behaviour in the SSSC
(a) 24-Pulse inverter
(b) 48-Pulse inverter
The virtually higher switching frequency of the 48pulse arrangement can be regarded as a more
In this paper, an evaluation in the performance of a
24 and a 48-pulse phase-shifted VSI-based SSSC,
was realised. Both configurations have shown a
good performance under balanced conditions.
However, the 48-pulse configuration presents a
nearly sinusoidal series voltage waveform, thus,
this configuration may avoid the presence of
harmonic filters between the inverter and the ac
system without trespassing the voltage harmonic
content limit of the power quality standards. In
general, the SSSC has showed a quick transient
response (about ¼ cycle or more) depending on the
PI controller adjustment. It has also been observed
the SSSC ability in increasing and modifying the
transmittable power of a line, where it has been
implemented.
References:
[1] N.G. Hingorani, L. Gyugyi, UNDERSTANDING FACTS: Concepts and Technology of
Flexible AC Transmission Systems, IEEE
Press, N.Y., 2000.
[2] R.L.V. Arnez, L.C. Zanetta, Steady-State
Analysis of the Unified Power Flow
Controller (UPFC) and its Capability in
Modifying the Transmittable Power,
IEEE/PES, Latin America Transmission &
Distribution Conference, São Paulo, March
18-22, 2002.
[3] L. Gyugyi, C. Schauder, K.K. Sen, Static
Synchronous Series Compensator: A SolidState Approach to the Series Compensation
of Transmission Lines, IEEE Power
Engineering Review, 120-6, WM, January
1996, pp. 1-8.
[4] R. Mihalic, I. Papic, Mathematical Models
and Simulation of a Static Synchronous
Series
Compensator,
International
Conference on Electric Power Engineering,
PowerTech, Budapest, 1999.
[5] M. Carpita, S.M. Tenconi, M. Fracchia, A
novel multilevel structure for Voltage Source
Inverter, European Electronics and Drives
Association (EPE) 91, Florence, Italy,
September 3-6 1991, pp. 90-94.
[6] K.K. Sen, SSSC-Static Synchronous Series
Compensator: Theory, Modelling and
Applications, IEEE Transactions on Power
Delivery, Vol 13, No 1, January 98, pp. 24146.