Specification for Tender 840984200 General Specification for MV Motor Control Centers – Direct on Line 1. General 2. Product 3. Execution Last update : 2017-05-06 -1- Specification for Tender 840984200 Table of contents: 1. General ………………………………………………………………………………………………………….. 3 1.1 Section includes……………………………………………………………………………………. 3 1.2 References………………………………………………………………………………………….. 3 1.3 Medium voltage controllers................................................................................................................ 3 1.4 Submittals………………………………………………………………………………………….. 3-4 1.5 Quality Assurance………………………………………………………………………………….. 4 1.6 Qualifications………………………………………………………………………………............. 4 1.7 Delivery, Storage, and Handling……………………………………………………........................ 4 1.8 Operation and maintenance manuals…………………………………………….............................. 4 1.9 Extra products……………………………………………………………………………................. 5 2. Product…………………………………………………………………………………………….... 5 2.1 manufacturers …………………………………………………………………………………….... 5 2.2 Medium Voltage Motor Controller Assembly…………………………………………………........ 5 - 6 2.3 Ratings…………………………………………………………………………………………........ 6 - 7 2.4 Components………………………………………………………………………………….. ........ 7 - 8 2.5 Power and Earth Busbar (Motor Control Center Construction Only)………………….................... 8 2.6 Wiring / Terminations………………………………………………………………………............ 8 2.7 Motor Protection…………………………………………………………………………................. 8 2.8 Metering......……………………………………………………………………………………….... 8 2.9 Controllers.... ………………………………………………………………………………….......... 8 - 10 2.10 Mechanically Latched Contractor………........………….........………………………………........ 10 2.11 Incoming Line sections to MCC…………………………………………………………………... 10 2.12 Fabrication…………………………………………………………………………………............. 10 2.13 Factory finishing…………………………………………………………………………............... 11 2.14 Related Sections…………………………………………………………………………………..... 11 3. Execution……………………………………………………………………………………………. 11 3.1 Examination Specified Components………………………………………………………............... 11 3.2 Installation………………………………………………………………………………………….. 11 3.3 Field Quality Control……………………………………………………………………………….. 11 - 12 Last update : 2017-05-06 -2- Specification for Tender 840984200 1. General 1.1 Section includes 1.1.1 The Contractor shall furnish and install the medium voltage controllers as specified herein and as shown on the contract drawings. 1.1.2 Controller application describes Full Voltage Non Reversing starters for Induction Motors. 1.1.3 One-high construction. 1.1.4 Medium voltage motor control equipment shall be compatible with the medium voltage primary equipment. 1.2 References 1.3 Medium voltage controllers shall be designed, manufactured, assembled and tested in accordance with the following standards: 1.3.1 IEC 60694 Commons specifications for high-voltage switchgear and controlgear standards 1.3.2 IEC 62271-200 Ac metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV 1.3.3 IEC 60470 high voltage alternating current contactors and contactor based motor starter 1.3.4 IEC 60282-1 high voltage fuses: limiting fuses 1.3.5 IEC 62271-102 alternating current disconnectors and earthing switches 1.3.6 IEC 60255 measurement relay and protection unit (SEPAM) 1.3.7 IEC 60044-1 Instrument transformers - Part 1: current transformers 1.3.8 IEC 60044-2 Instrument transformers - Part 2: voltage transformers 1.3.9 IEC 60044-8 Instrument transformers - Part 8: low power current transducers 1.3.10 IEC 61958 High-voltage prefabricated switchgear and controlgear assemblies Voltage presence indicating systems 1.3.11 IBC 2000 Seismic Standards 1.3.12 The equipment shall also comply with the following standards: - NEMA ICS 3 Part 1 & 2 , 1993 (R2000), - UL 347, EEMAC E14-1. Arc Resistant, - ANSI C19.7, - ANSI C: 37.20.7, 200X, Arc Resistant. 1.4 Submittals 1.4.1 FOR REVIEW/APPROVAL 1.4.1.1 The following information shall be submitted to the Engineer: - Master drawing index. - Front view elevation. - Floor plan. - Top view. - Schematic diagram. - Nameplate schedule. - Component list. - Conduit entry/exit locations. - Assembly ratings including: - Short circuit rating. - Voltage. - Continuous current. - Basic impulse level. - Major component ratings including: - Voltage. Last update : 2017-05-06 -3- Specification for Tender 840984200 - Continuous current. - Interrupting ratings. - Cable terminal sizes. 1.4.1.2 Where applicable the following additional information shall be submitted to the Engineer: - Connection details between close-coupled assemblies. - Composite floor plan of close-coupled assemblies. - Key interlock scheme drawing and sequence of operations. - 4.1.3 Submit six (6) copies of the above information. 1.4.2 FOR INFORMATION 1.4.2.1 When requested by the Engineer the following product information shall be submitted: - Product brochures. - Product datasheets. 1.4.2.2 Test Certificates 1.4.3 FOR CLOSE-OUT 1.4.3.1 The following information shall be submitted for record purposes at time of shipment: 1.4.3.2 Final as-built drawings and information for items listed in Article 1.3.1. 1.4.3.3 Wiring diagrams. 1.4.3.4 Installation information. 1.4.3.5 Submit six (6) copies of the above information. 1.5 Quality Assurance 1.5.1 In accordance with (customer to specify section) 1.5.2 Manufacturer: Company specializing in medium voltage metal-enclosed motor controller with at least five years documented experience. The manufacturer of the motor controller must be the same as the manufacturer of the circuit breaker switchboard. 1.5.3 Type tests shall be carried out in accordance with IEC 62271-200 provided that additional requirements specified (e.g. busbar insulation) are taken into consideration. Certificates shall be available upon request. Certificates issued/supported by independent testing laboratories are preferred. Components installed within the assembly shall be type tested in accordance with the applicable IEC standards. Certificates obtained from the component Manufacturers shall be made available at the request of the Principal. 1.6 Qualifications 1.6.1 For the equipment specified herein, the manufacturer shall be ISO 9000. 1.6.2 The manufacturer of this equipment shall have produced similar electrical equipment for a minimum period of five (5) years. When requested by the Engineer, an acceptable list of installations with similar equipment shall be provided demonstrating compliance with this requirement. 1.7 Delivery, Storage, and Handling Equipment shall be handled and stored in accordance with manufacturer's instructions. One (1) copy of these instructions shall be included with the equipment at time of shipment. 1.8 Operation and maintenance manuals 1.8.1 Three (3) copies of the equipment operation and maintenance manuals shall be provided at time of shipment. 1.8.2 Operation and maintenance manuals shall include the following information: 1.8.2.1 Instruction books and/or leaflets. 1.8.2.2 Recommended spare parts list. 1.8.2.3 Drawings and information required by Article 1.3. Last update : 2017-05-06 -4- Specification for Tender 840984200 1.9 Extra products Manufacturer shall provide a recommended Spare Parts List, included as part of the Operation and Maintenance Manuals. 2. product 2.1 Manufacturers 2.1.1 The Medium Voltage Motor Controllers shall be Merlin Gerin type or approved equal. 2.1.2 Current limiting fuses shall of suitable manufacture to ensure the coordination and the integrity of the system. The blown fuse indicator shall be an "Extended Travel” type with a minimum of 25mm of travel. Fuses shall have a 50,000 Amperes interrupting rating. 2.1.3 Fuses shall be non-disconnect type with provisions for removal and replacement from the front of the motor controller ************************************************************************************** 2.1.4 Select the appropriate optional Fuselogic description and/or features ************************************************************************************** 2.1.5 {Option} The Medium Voltage Motor Controllers shall be equipped with an optional Fuselogic blown fuse protection system to automatically open the contactor, when a fuse interrupts. The system shall also prevent single phasing conditions by blocking the closing of the contactor when a fuse is blown or if a fuse is not installed. 2.2 Medium Voltage Motor Controller Assembly 2.2.1 Controllers to be supplied in modular one-high, one controller per structure construction. Stacked or tiered controllers are not acceptable. The equipment shall be factory-assembled (except for necessary shipping splits) and operationally checked. The width of a standard motor starter shall be 375 mm. The width of an enclosure with an integrated power factor correction capacitor shall be 750 mm. 2.2.2 The enclosure rating shall be IP3X. {Option:} [IP4X], [IP31], [IP41]. 2.2.3 The motor controller shall [consist of a single section] [be a multiple section line-up] [be close coupled to MetalClad Switchgear], and be of indoor construction 2.2.4 The medium voltage motor controller assembly shall be partitioned into the following distinct compartments: 2.2.4.1 Busbar compartment 2.2.4.2 Low Voltage compartment 2.2.4.3 Load compartment containing the fuses, contactor, instrument transformers, and customer cable terminations and cable-earthing switch. 2.2.5 Disconnector and contactor assemblies, including current limiting fuses, shall be of the componentto-component type. There shall be no bolted connections between the contactor finger assembly and the customer load terminals. 2.2.6 The equipment shall be designed for front accessibility only to allow installation against a wall. Standard rear access shall be provided. A viewing window shall be provided as standard to permit verification from the rear of the enclosure that an operator is accessing the proper cubicle by ensuring that the appropriate front door is open. 2.2.7 Cable entry or exit shall be [bottom] [top] [Bottom and top]. 2.2.8 {Option} [The enclosure shall be Internal Arc Class as defined in Annex A of 62271-200]. {Option} [A tunnel shall be provided to divert the hot gasses.] [The tunnel height shall be 440mm]. ****Required when ceiling height is 2 meters or less above the top of the equipment {top cable entry or exit is not available}. 2.2.9 In establishing the requirements for the enclosure design, consideration shall be given to such relevant factors as controlled access, tamper resistance, protection from ingress of rodents and insects. 2.2.10 Motor controller shall not require ventilation openings to aid in cooling of the associated components. Last update : 2017-05-06 -5- Specification for Tender 840984200 2.2.11 Flexible power conductors shall interconnect the main contactor with the motor load terminals. Flexible power conductor terminals shall be of the swage 360º radial cold-fused compression type connections. These connections shall be maintenance free, never requiring torque. 2.2.12 The motor controller shall be low maintenance designed to reduce the requirement for annual/ periodic maintenance of the equipment. Equipment with scheduled maintenance intervals of one or more years is preferred. 2.2.13 A low voltage compartment to accommodate control circuit terminal blocks, control components [and PowerLogic metering]. The low voltage compartment shall be located at the top of each vertical section. The interior of the Low Voltage compartment shall be painted white. 2.2.14 Shipping splits shall be a maximum of 5 sections (1875 mm) to minimize the number of overlapped main bus joints and on site labour. 2.2.15 Medium voltage motor control equipment shall be compatible with Merlin Gerin Distribution Equipment. 2.3 Ratings 2.3.1 System Voltage: [2.4] [[3.3] [4.16] [6.6] [7.2] [..] kV, three phase, [solidly earthed] [resistor earthed through a [..] ohm resistor] [unearthed], [three phase 3 wire] [three phase 4 wire]. Neutral Busbar not available. 2.3.2 Main Busbar Capacity: [630] [1250] [2500] [3150] amperes, continuous. 2.3.3 Medium Voltage Motor Controllers shall have the following ratings with HRC fuses Motor Controller Ratings Rated voltage (kV) 7.2 Rated insulation level power frequency withstand voltage 50 Hz - 1 20 min (rms kV) lightning impulse withstand voltage 1.2/50 µs 60 (kV peak) Frequency (Hz) 50/60 Nominal current and maximum short time withstand current (1) rated current In 200 Short time withstand current Ith max. (kA/3 s) 40 (kA/2 s) 50 Disconnector 0.25 second 50 Equipment (after fuses) 1 second 4.2 30 seconds 1.7 Earthing Switch Fault Close kA Symmetrical 5kA kA Peak 14kA Internal arc withstand (Optional) second 25kA 0.50 second 40kA 0.25 second 50kA Altitude Rating metres 1000 Contactor Rating rated current Electrical Endurance Mechanical Endurance Latched Last update : 2017-05-06 In Standard 200 250,000 2,500,000 250,000 7.2 20 60 50/60 400 (kA/3 s) 40 (kA/2 s) 50 50 7.8 3.0 5kA 14kA 25kA 40kA 50kA 1000 400 250,000 2,500,000 250,000 -6- Specification for Tender Short Circuit Interrupting Amps (RMS Sym.) Short Circuit Withstand at Rated Voltage (fused) kA Symmetrical kA Peak Short time withstand current Ith max. (1 second) (30 seconds) Chopping Current ( Avg. RMS Amps) Switching Frequency (Ops per hour) Maximum Closing Time (milliseconds) Maximum Opening Time (milliseconds) 840984200 6.3kA 6.3kA 50 130 50 130 4.0 2.4 0.5 6.0 2.4 0.5 1200/300 latched 100 or less 30ms or less 1200/300 latched 100 or less 30 or less 350 or more (delayed) 2.4 Components 2.4.1 The disconnector shall be a two position externally operated manual three-pole device, such that in the open position it earths and isolates the line side from the load compartment. The switch-operating handle shall be removable. The operating mechanism shall be rugged, simple and shall have provisions for three padlocks in the on or off position. [A changeover contact shall be provided for remote position indication of the disconnector.] [Provide key interlocks to coordinate with….] 2.4.1.1 Mechanical Interlocks: interlock shall be provided to prevent the opening of the high voltage access door with the no-load disconnector closed. To access the medium voltage compartment, the no-load disconnector must be opened to the earth position. The interlock must be directly attached to the operating mechanism and should not rely on long cables and linkages. 2.4.1.2 All interlocks shall not require adjustments over the life of the equipment. This shall be demonstrated by a test of 10 times the industry standard’s maximum. 2.4.1.3 A viewing port shall be installed in the disconnector enclosure to enable visible verification of the 2.4.2 {Option:} A cable earthing switch shall be provided. The earthing switch shall be used to earth the load cables. It is shall be mechanically interlocked with the disconnector and be operated using the same handle. The earthing switch shall have a spring operated quick make device capable of making 14kApk. The cable earthing switch shall be mounted in the load box at the motor lead terminals. The earthing switch shall be a maintenance free device. 2.4.3 Fuses shall be of the current limiting type. The blown fuse indicator shall be an "Extended Travel” type with a minimum of 25 mm of travel. Fuses shall have a 50,000 Amperes interrupting. The fuses shall incorporate special time/current characteristics for motor service allowing proper coordination with the contactor and overload relay for maximum protection. This coordination shall be such that under a low fault condition the interrupting rating and dropout time of the contactor shall be properly coordinated with all possible fuse sizes to eliminate contactor racing. The power fuses shall be vertically mounted permitting easy inspection and replacement without the need for removing the contactor. 2.4.3.1 {Option} Provide FuseLogic shunt trip, single phase protection system using DIN style fuses (or equal) to automatically open the vacuum contactor when a fuse blows or a fuse is not installed. This is intended for backup protection only to the motor overload relay. The system shall further prevent potential single phasing conditions by blocking the closing of the contactor when a fuse is blown or a fuse has nor been installed. (Provide optional changeover contact for trip indication}. 2.4.4 The vacuum contactor shall be with-drawable and magnetically held [mechanically latched] rated [200 A] [400 A] with single-break high-pressure type main contacts. The vacuum contactor contact wear shall be easily checked with the use of a “go/no-go” gauge, included with each controller. {Option} A built-in test circuit shall be included within each controller to permit checking the control and pilot circuits, Last update : 2017-05-06 -7- Specification for Tender 840984200 with the medium-voltage de-energized and isolated and the contactor in its normal. A viewing window shall be provided to view the contactor status. 2.4.5 The contactor shall withdraw on a rail system. When the contactor is lowered it will disconnect the contactor and when raised, it will connect the contactor and lock it in position. 2.4.6 A viewing port shall be provided to view the contactor status. 2.4.7 Accessories 2.4.7.1 The controller mounted control power transformer (CPT) shall be [300VA], [500VA], [750VA], 2kVA], and be 60kV BIL rated. Fuse holder with two primary current limiting fuses. 2.4.7.2 The controller mounted open delta voltage transformer shall be provided for metering and protection. 2.5 Power and Earth Busbar (Motor Control Center Construction Only) 2.5.1 When controllers are grouped together in a line-up, the horizontal main busbar shall be located in its own compartment. To allow for ease of maintenance or extension of line-ups, the main busbar shall be front, rear, top, and side accessible. 2.5.2 Main power busbar bars shall be tin-plated copper and braced for 50 kA 2-seconds (40 kA 3 seconds). All busbar shall be braced to withstand, without damage or deformation, maximum let-through current permitted by the current limiting fuses. 2.5.3 Copper earth busbar shall be continuous and extend from one end of the motor control centre to the other through each vertical section. Minimum size to be 6.35 mm by 50mm. 2.6 Wiring / Terminations 2.6.1 Standard control wire shall 1.5mm2. 2.6.2 Current transformer circuits shall utilize 2.5 mm2 wires. 2.6.3 Controllers shall be complete and control wires including terminations for external connections. 2.6.4 Phase sequencing shall have proper identification and all wires shall have suitable markings at all terminations. 2.7 Motor Protection Provide a microprocessor-based multi-function, motor protective relay that monitors three-phase ac current and makes separate trip and alarm decisions based on pre-programmed motor current and temperature conditions. [Sepam Series (20), (40) (80)] 2.8 Metering 2.8.1 Microprocessor-Based Metering Package 2.8.1.1 Where indicated on the drawings, provide a UL Listed solid-state microprocessor-based metering package with optional waveform capture. Metering package shall be a PowerLogic circuit monitor.[Each] PowerLogic Circuit Monitor, [with digital display][with waveform capture][stand-alone section[s] containing a controller shall include the following [as shown on the drawings]: - [CM 3000] [CM 4000] - [Wired for communications; to other [devices.] - PowerLogic digital meter. [PM620] [PM 650] [PM820] [PM 850] - Other: [..] 2.8.2 Auxiliary Devices 2.8.2.1 {Option} Provide fixed mounted potential transformer, fused type, 3 phase open delta as indicated on the contract drawings. These shall be used for the MPR [and meter]. 2.9 Controllers 2.9.1 The controllers shall be designed to accommodate motors of the size and type as shown on the drawings. 2.9.2 The controllers shall be provided by a single manufacturer with a complete product offering (refer to Article 1.1.2 of controllers to accommodate the following motor types and starting methods: 2.9.2.1 Induction Motor Full Voltage Start. Last update : 2017-05-06 -8- Specification for Tender 840984200 2.9.3 Provide the following equipment for type controller indicated in Article 2.07.A, and the contract drawings. 2.9.3.1 Each Induction Motor Full Voltage Non Reversing Controller shall include: - Medium Voltage Compartment: - One - three-pole non-load break isolating disconnector. - Current limiting power fuses. - One - Draw-out three-pole vacuum contactor assembly. - {Option} One - Control circuit transformer [300VA] [500VA] [750VA] [2kVA] - {Option} Two - Control circuit primary current limiting fuses. - Set - Electrical and Mechanical interlocks. - Three - Load terminals. An anti-rotational terminal pad shall have provision for two hole cable lugs. - Current Transformer Options: (Max 3) . Each section containing a contactor shall include the following [as shown on the drawings]: [one] three phase donut Type Low Power Current Transformer [use with SEPAM relay] Current transformer accuracy shall be equal to or higher than ANSI metering class. . [one] [two] three phase donut type current transformers [..]: 5A. or [..]: 1A . [one] Zero Sequence CT [2000:1] [50:5] - {Option} Provide two sets of thermal sensing optical probes for instant temperature detection placed at points with the most significant temperature rise. The probes shall be designed to withstand the constraints related to the medium voltage environments. The optical technology shall provide reliable measurements and give the system a long service life. The probes shall be factory-built assemblies comprised of 6 sensors, optical connections and a monitoring module. - Low-Voltage Compartment Door: - {Option} One - Motor protection relay (MPR) Sepam Series [20][40][80]where specified - {Option} One - Microprocessor metering package where specified. - Mounting space for any additional low voltage control, protection, or metering specified. - Components to be directly mounted on door - size of door cut-outs to match size of mounted component. - Low-Voltage Compartment: - Two - Control relays. - One - Control circuit secondary fuse. - Set of control circuit terminal blocks. - Customer terminal blocks with screw compression type connections. - Mounting space for any additional low voltage control, protection, or metering specified. - Operator panel - Disconnector operator mechanism. - Mechanical open-close indication. - Disconnector Viewing Window. - two – 22 mm pushbuttons. - two 22 mm indicating lights. - {Option}Elapsed time meter . - {Option} Key Interlocks: shall be provided for the disconnector operating mechanism as indicated on the drawings]. 2.9.4 {Option} Provide [compression lugs] for terminating cables onto the motor controller terminal pads. 2.9.5 {Option} Anti-condensation space heaters rated 220 VAC, 250W shall be supplied in each section. Control power shall be supplied [supplied by owner] [by internal controller mounted CPT] {and shall be supplied with} [thermostats] [humidistat.] 2.9.6 {Option} Cable earthing switch. To facilitate cable testing in the high voltage compartment, the earthing switch can be returned to the open position with the MV compartment door open. In this position Last update : 2017-05-06 -9- Specification for Tender 840984200 interlocks are to be provided to prevent replacement of the high voltage access panel and prevent closure of the load interrupter switch. 2.9.7 {Option} Voltage Presence Indication System shall be provided on the mechanism compartment and shall be an easily removable module containing three neon indicators powered from voltage dividers. 2.9.8 {Option:} Surge Arresters (metal-oxide type): [Distribution] [Intermediate] class, rated [3, 6, 9] kV, one per phase. 2.9.9 {Option} Main busbar live line indicators shall be provided as required and shall be mounted in the low voltage compartment.] 2.9.10 {Option} Power factor correction capacitor shall be provided. The capacitor shall be a 3 phase unit connected to the load side of the connector. The rating of the capacitor shall be [100], [150], [200], [250], [300], [350], [400] kVAR. 2.10 Mechanically Latched Contractor 2.10.1 Mechanically-latched contactors shall be provided when specified for transformer disconnect circuits, and other uses when it is required to have contactor remain closed, regardless of control voltage condition. 2.10.2 Mechanically-latched contactor shall be closed electrically from a local or remote ”close“ pushbutton, and an electrically operated solenoid shall be supplied to open the contactor from a remote location 2.10.3 A mechanical opening device shall be provided to mechanically open the contactor. 2.11 Incoming LIne sections to MCC 2.11.1 Each incoming line section shall be [500mm wide {bottom entry only}] [750mm wide {top or bottom entry and shall be connected to an adjacent controller. 2.11.2 Terminations shall accommodate up to quantity and size or ratings of cables as indicated on the drawings. 2.11.3 Incoming Line section shall have a rating of [630] [1250] [2500] [3150] amperes. 2.11.4 {Option} Provide a Voltage Presence Indication System connected by a capacitive circuit to the main bus. The system lights will indicate voltage when the equipment is energized. 2.11.5 {Option:} Surge Arresters (metal-oxide type): [Distribution] [Intermediate] class, rated [3, 6, 9] kV, one per phase. 2.11.6 {Option} The section shall contain a top mounted pull box [432 mm high] to ease in cable pulling and for additional shielded cable bending space. 2.11.7 SPECIFIED COMPONENTS 2.11.7.1 Standard push buttons shall be Harmony type 9001 ZB4, 600 V rated. 2.11.7.2 Standard pilot lights shall be Harmony type 9001 XB4, 600 V rated LED long life. 2.11.7.3 Standard control relays shall be type CA2DN. 2.12 Fabrication 2.12.1 Construction: Each cubicle shall be a separately constructed cubicle assembled to form a rigid freestanding unit. Adjacent cubicles shall be securely bolted together to form an integrated rigid structure. Each individual unit shall be braced to prevent distortion. 2.12.2 All busbar joints shall use Belleville washers. Torqued bolts that are used for busbar joints or for insulators and direct support of any current carrying parts shall be marked with a bead of highly visible bright orange "torque seal", that will readily show when a bolt has loosened. 2.12.3 Height: 2300mm, maximum including auxiliary support members on top and bottom. 2.12.4 Main busbar shall be copper, [non-insulated] [insulated] rated [630] [1250] [2500] [3150] amps, and shall be supported directly by the disconnector. 2.12.5 [For single cubicles, include an earth pad with lug.] [For multiple cubicle line-ups, include continuous earth busbar through the motor controller assembly, securely connected to the steel frame of each cubicle.] 2.12.6 Main busbar and earth busbar connections shall be designed for easy future extensions. Cut-out areas with removable bolted on covers shall allow for future extension of the main busbar. A knockout shall be removable for the extension of the earth busbar. Last update : 2017-05-06 - 10 - Specification for Tender 840984200 2.13 Factory finishing 2.13.1 All non-painted steel parts shall be zinc plated. 2.13.2 All painted steel parts shall be cleaned and a zinc-phosphate pre-treatment applied prior to paint application. 2.13.3 Paint Colour shall be RAL9002 White Frosted TGIC polyester powder, applied electrostatically through air. Following paint application, parts shall be baked to produce a hard durable finish. The average thickness of the paint film shall be 2.0 mils. Paint film shall be uniform in colour and free from blisters, sags, flaking and peeling. 2.13.4 Adequacy of paint finish to inhibit the build-up of rust on ferrous metal materials shall be tested and evaluated per paragraphs 5.2.8.1-7 of ANSI C37.20.3-1987. Salt spray withstand tests in accordance with paragraph 5.2.8.4 shall be performed on a periodic basis to provide conformance to this corrosion resistance standard of at least 600 hours minimum. 2.14 Related Sections 2.14.1 [Section 16290-3]-Power Monitoring And Control Systems 2.14.2 [Section 16290-6.1]-Medium Voltage Protective Relay 2.14.3 [Section 16290-7]-Web Enabled Power Distribution Equipment 3. Execution *********************************************************************************** The following paragraphs in this section represent work that is to be performed by the installing contractor. If this specification is written for the motor controller manufacturer only, eliminate these sections. *********************************************************************************** 3.1 Examination Specified Components 3.1.1 Visually inspect motor controller for evidence of damage and verify that surfaces are ready to receive work. 3.1.2 Visually inspect to confirm that all items and accessories are in accordance with specifications and drawings. 3.1.3 Verify field measurements are as [shown on Drawings] [shown on shop drawings] [instructed by manufacturer.] 3.1.4 Verify that required utilities (e.g., control voltage for heater circuits on outdoor motor controller) are available, in proper location, and ready for use. 3.1.5 Beginning of installation means installer accepts existing surface conditions. 3.2 Installation 3.2.1 Install in accordance with manufacturer's instructions and in accordance with recognized industry practices. 3.2.2 [Connect the primary surge arresters if not connected. If required, use jumper cables, as provided by the motor controller manufacturer.] 3.2.3 Bending of high-voltage cables should be avoided or minimized. All necessary bends should meet at least the minimum radii specified by the cable manufacturer. 3.3 Field Quality Control 3.3.1 Field inspection and testing will be performed by [the installing contractor] [a separate contractor furnished by the owner]. 3.3.2 Visually inspect for physical damage. 3.3.3 Perform mechanical operator tests in accordance with manufacturer's instructions. 3.3.4 Check torque of all bolted connections, including cable terminations, either by observing the bead of indicating compound to confirm that it is still intact, or with a torque wrench to confirm the joint is tightened to the manufacturer's specifications. 3.3.5 Touch-up paint all chips and scratches with manufacturer-supplied paint and leave remaining paint with Owner. Last update : 2017-05-06 - 11 - Specification for Tender 840984200 3.3.6 Verify key interlock operation if applicable. 3.3.7 Perform insulation resistance test on each phase to earth and each phase to each other phase. Record results. 3.3.8 Perform low frequency withstand tests according to applicable IEC standards. 3.3.9 Perform contact resistance test across each disconnector blade; report any contact resistance in excess of 50 micro-ohms. Last update : 2017-05-06 - 12 -