Download soft start

Document related concepts

Control theory wikipedia , lookup

Distributed control system wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Ohm's law wikipedia , lookup

Electrical ballast wikipedia , lookup

Current source wikipedia , lookup

Brushless DC electric motor wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Resilient control systems wikipedia , lookup

Electrical substation wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Electric motor wikipedia , lookup

Buck converter wikipedia , lookup

Power electronics wikipedia , lookup

Opto-isolator wikipedia , lookup

Surge protector wikipedia , lookup

Earthing system wikipedia , lookup

Protective relay wikipedia , lookup

Stray voltage wikipedia , lookup

Time-to-digital converter wikipedia , lookup

AC motor wikipedia , lookup

Three-phase electric power wikipedia , lookup

Mains electricity wikipedia , lookup

Distribution management system wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

Induction motor wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Two-port network wikipedia , lookup

Stepper motor wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Transcript
RVS-DN Technical Presentation
Yuval Paz – Technical Support Manager
March 2008
1
2
Presentation Content
1. Presentation
2. Power Wiring
3. Control wiring
4. Programming
4. Protection
3
Main Features
• Heavy Duty Design: 400% In, 30 sec. at 50°C,
4 starts an hour
• Comprehensive Range: 8-3000A, 220-1000V
• Third Generation Digital Field proven
experience
• Fully featured: Control, Comprehensive motor
Protection & Supervision
• User Friendly: Default settings, LCD display,
Selectable languages
4
RVS-DN Approvals
USA
UL Approved : 8-820A,
1100A and above are designed to meet UL requirements
Canada
cUL Approved : 8-820A
1100A and above are designed to meet cUL requirements
European
CE Approved (EMC & Safety) : 8-1400A
1800A and above are designed to meet CE requirements
Marine &
Offshore
Lloyd’s Approved (ENV 1 & ENV 2) : 8-1400A
1800A and above are designed to meet Lloyd’s
specifications for ENV1 & 2 requirements
Marine &
Offshore
Germaniche Lloyd’s Approved: 8-1400A
1800A and above are designed to meet Germaniche
Lloyd’s specifications
5
RVS-DN Approvals
China
China Compulsory Certificate
Russia
GOST certificate of conformity
Marine &
Offshore
Marine &
Offshore
Det Norske Veritas
Registro Italiano Navalo
6
Selector Guide – Frame A
• Model
RVS-DN 8
RVS-DN 17
RVS-DN 31
RVS-DN 44
RVS-DN 58
RVS-DN 72
Line
To by-pass
(option)
LCD
(selectable
languages)
LEDs
(status display)
Control terminals
(Plug-in)
IP 20
To Motor
Finger protected
7
for safe operation
Selector Guide – Frame B
(Bus bar cover
• Model
removed)
RVS-DN 85
RVS-DN 105
RVS-DN 145 Power
Section
RVS-DN 170
To Motor
To Bypass contactor
(not shown in the picture)
Line
Control Module
(Identical for sizes
B-G)
Preparation for bypass
contactor is standard in
8
this model
Selector Guide – Frame C
• Model
RVS-DN 210
RVS-DN 310
RVS-DN 390
To Bypass
contactor
Line
C/Ts
Power
Section
Control
Module
To Motor
9
Selector Guide – Frame D
To Bypass
• Model contactor
RVS-DN 460
RVS-DN 580
C/Ts
RVS-DN 820
Line
Power
Section
Control
Module
To Motor
10
Selector Guide – Frames C,D UL/Marine
Load
• Model
RVS-DN 210
RVS-DN 310
RVS-DN 390 C/Ts
RVS-DN 460
RVS-DN 580
RVS-DN 820
RVS-DN 950
In RVS-DN 950A
C/Ts are mounted
outside the soft starter
Line
(Bus-bar cover
removed)
Power
section
Control
module
RVS-DN 950A and up must be
11
operated with an external bypass
Selector Guide – Frame E
Line
• Model
RVS-DN 1100
RVS-DN 1400 C/Ts
RVS-DN 1800 Normally mounted
Power
Section
Outside the Soft starter
Control
Module
To Motor
This model must be operated
with an external bypass 12
Selector Guide – Frame F
• Model
Line
RVS-DN 2150
Power
Section
C/T
Control
Module
To Motor
This model must be operated
with an external bypass 13
Selector Guide – Frame G
• Model
RVS-DN 2400
RVS-DN 2700
RVS-DN 3000
Line
Power
Section
External C/T
are available
To Motor
Control
Module
This model must be operated
with an external bypass 14
Selector Guide – 1000V Models
• Model
RVS-DN 105A
RVS-DN 170A
RVS-DN 210A
RVS-DN 310A
RVS-DN 390A
RVS-DN 460A
1000V models must be operated
15
with an external bypass
Selector Guide – 1000V Models
• Model
RVS-DN 105A
RVS-DN 170A
RVS-DN 210A
RVS-DN 310A
RVS-DN 390A
RVS-DN 460A
16
Selector Guide – How to Select?
• System voltage
– Motor current and connection
– Starting conditions
– Options and control voltage
17
Selector Guide – How to Select?
• System voltage
– 400 230 - 400 VAC, 50/60Hz, +10% -15%
– 480 480 VAC, 50/60Hz, +10% -15%
– 600 600 VAC, 50/60Hz, +10% -15%
– 690 690 VAC, 50/60Hz, +10% -15%
– 1000 1000 VAC, 50/60Hz, +10% -15%
Models: 105A, 170A, 210A, 310A, 390A, 460A.
18
Selector Guide – How to Select?
• Motor current and connection
– Starter current ≥ motor FLA
!!!
19
Selector Guide – How to Select?
• Motor current and connection
– In line/Inside delta
• When soft starter is connected “inside delta” lower
current is running through the soft starter.
20
Selector Guide – How to Select?
• Motor current and connection
– In line/Inside delta
• Advantages:
– Smaller dimensions
– Less expensive Soft Starter
• Disadvantages:
–
–
–
–
–
–
–
Six wire to the motor – more complicated wiring.
No pulse start
No curve selection (Curve 0! Only)
No energy save
No slow speed
No phase sequence “off” mode.
Although current inside delta is reduced by 1.73 (√3), Soft starter
current is reduced by 1.5.
For example: for a 870A motor, you can choose a 580A soft starter
when connected “inside delta”
21
Selector Guide – How to Select?
• Starting conditions
– The RVS-DN is able to start at 4xIn, 30 seconds at
50°C
22
Selector Guide – How to Select?
• Options:
•
•
•
•
•
•
•
•
•
•
•
•
Communication - RS-485 (Modbus)
Communication – Profibus
Insulation tester
Analog card – Thermistor in and Analog out
Harsh environment treatment.
Preparation for Bypass contactor
Line and load bus bars at bottom
Remote panel mounting replacing the original panel.
Russian characters LCD display
Marine approval
UL & cUL approval
Tachometer card for special drive systems
23
Bypass Contactor
• Models 8-820A can operate continuously
without a bypass contactor
• All models from RVS-DN 950A and up and
RVS-DN 1000V must be implemented with
a bypass contactor
• Bypass preparation is standard in models
RVS-DN 85-170A.
24
Bypass Contactor
• Current flow during start
25
Bypass Contactor
• Current flow with bypass contactor
Soft starter must be ordered with preparation for bypass contactor
26
Bypass Contactor
• Bypass contactor connection
Line
C/T
Bypass
Contactor
To motor
M
27
Bypass Contactor
• How to control the bypass contactor?
End of Acceleration
Relay
RVS-DN
M
1 2 3
L
4...9
13 14 15 16 17 18 19 20 21
N
28
Control Module (B-G models)
Optional boards:
•Insulation Test board
•Analogue board
•Tacho encoder board
(only one option can be
installed)
Control
Plug
Control
Transformer
Dip Switches
Power
Supply
Board
Microprocessor &
EPROM
Fan control
jumper
Optional comm. boards:
Control
Supply
I / O terminals
•RS 485 (MODBUS)
•Profibus
•Others upon request29
Control Module (B-G models)
Auxiliary Relays : C/O, 8A/250VAC
* Immediate - with On and Off delays
* Fault - prog. Fault / Fail- safe
* End of Acceleration - with On delay
8 dip switches
30
Dip Switches in Control Module
No.
1
2
3
4
5+6
7
8
Function
Display
Tacho feedback
Mains / Generator
Always OFF
Language selector
Extended range
Software lock
OFF (default)
Minimum
Disabled
Mains
ON
Maximum
Enabled
Generator
English, French, German, Spanish, Russian*
Disabled
Enabled
Open
Locked
1
2
3 4
5 6
7 8
OFF
* Russian display must be specified when ordering.
31
Dip Switches in Control Module
• Dip switch #7 functions
Parameter
Range Switch #7 - Off
Range switch #7 - On
INITIAL VOLTAGE
10-50%
5-80%
CURRENT LIMIT
100-400%
100-500%
ACCELERATION TIME
1-30 seconds
1-90 seconds
MAX. START TIME
1-30 seconds
1-250 seconds
PHASE LOSS Y/N
Yes
Yes/No
MAX SLOW SP TIME
1-30 seconds
1-250 seconds
O/C or WRONG CON
protection in Inside
Delta mode.
Protection active in normal
set
Protection active in high set
32
Presentation Content
1. Presentation
2. Power Wiring
3. Control wiring
4. Programming
4. Protection
33
Mains Wiring
• In line wiring
L1 L2 L3
Fuses or
Circuit breaker
Line Contactor
(when required)
Soft Starter
M
34
Mains Wiring
• In line wiring with bypass contactor
L1
L2
L3
By-pass
Contactor
“Preparation for By-pass”
eliminates the need for
additional O / L
M
35
Mains Wiring
• In line wiring with pf capacitors
L1
L2
L3
Fuses or
circuit breaker
Soft starter
Capacitor (when used)
must be at Line side. A
capacitor contactor is
not mandatory.
M
Motor
36
Presentation Content
1. Presentation
2. Power Wiring
3. Control wiring
4. Programming
4. Protection
37
Control Wiring
• Control wiring = Wiring
terminals in the bottom of
the control module (B-G
models)
38
1 2 3
4 5 6 7 8 9 10 11 12
Neutral
Tacho feedback
External Fault
Aux Contact
“End of Acc.”
Aux Contact
“Fault”
Aux Contact
“Immediate”
D. Adjust / Rev. / Reset
Common
Stop
Soft Stop
Start
E.Save / Slow Sp / Reset
Control Wiring
13 14 15 16 17 18 19 20 21
!
39
Control Wiring
• Terminal 21
3P+N+GR - Connect terminal 21 to neutral
3P+N - Connect terminal 21 to neutral
3P+GR - Connect terminal 21 to ground
3P - Leave terminal 21 unconnected
3P - Leave terminal 21 unconnected
3P+GR - Leave terminal 21 unconnected
40
Neutral
Control Wiring - Terminal 21
1 2 3
N
4 5 6 7 8 9 10 11 12
N
13 14 15 16 17 18 19 20 21
(1) For Mains system with Ground and / or
Neutral - connect Terminal 21 to N or Gr.
N or Gr.
(1)
(2) For Mains system without Ground and
Neutral - leave Terminal 21 open
41
1 2 3
L
N
4 5 6 7 8 9 10 11 12
Neutral
Common
D. Adjust / Reverse / Reset
Stop
Soft Stop
Start
E.Save / Slow / Reset
Control Wiring
13 14 15 16 17 18 19 20 21
Same voltage for Control Supply (1-3) and Control Commands (4-9)
42
1 2 3
L N
Neutral
Common
D. Adjust / Reverse / Reset
Stop
Soft Stop
Start
E.Save / Slow / Reset
Control Wiring
4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21
Different voltages for Control Commands (4-9)
can be AC or DC (must be specified)
Control Command
voltage
43
Soft Stop
Start
E.Save / Slow / Reset
D. Adjust / Rev. / Reset
Common
1 2 3
Stop
Control Wiring - Start / Stop
4
5
6
7
8
9
C
L
N
Motor will soft start when C closes and
stop immediately when C opens
44
Soft Stop
Start
E.Save / Slow / Reset
D. Adjust / Rev. / Reset
Common
1 2 3
Stop
Control Wiring - Start / Stop
4
5
6
7
8
9
C
L
N
Motor will soft start when C closes
and soft stop when C opens
45
Soft Stop
Start
E.Save / Slow / Reset
D. Adjust / Rev. / Reset
Common
1 2 3
Stop
Control Wiring - Start / Stop
4
5
6
7
8
9
C2
L
N
C1
C
Push-button operation - Motor will soft start when C closes,
soft stop when C1 opens and stop immediately when C2
opens
46
L
Soft Stop
Start
E.Save / Slow / Reset
D. Adjust / Rev. / Reset
Common
1 2 3
Stop
Control Wiring - Start / Stop
4
5
6
7
8
9
C
N
47
Soft Stop
Start
E.Save / Slow / Reset
D. Adjust / Rev. / Reset
Common
1 2 3
Stop
Control Wiring - Energy Save
4
5
6
7
8
9
C
L
N
Energy Save will operate when Terminal 7 is designated
as Energy Save and C closes. For automatic operation
use a jumper.
48
Soft Stop
Start
E.Save / Slow / Reset
D. Adjust / Rev. / Reset
Common
1 2 3
Stop
Control Wiring - Slow Speed
4
5
6
7
8
9
C
L
N
Slow Speed will operate when Terminal 7 is designated as
Slow Speed and C closes before motor starting.
49
Soft Stop
Start
E.Save / Slow / Reset
D. Adjust / Rev. / Reset
Common
1 2 3
Stop
Control Wiring - Remote Reset
4
5
6
7
8
9
C1
L
N
C2
* Remote (hardwire) Resetting will operate when Terminal 7
or 8 are designated as Reset and C1 or C2 close
50
Soft Stop
Start
E.Save / Slow / Reset
D. adjust / Reverse / Re.
Common
1 2 3
Stop
Control Wiring - Dual Adjustment
4
5
6
7
8
9
C
L
N
Dual Adjustment (secondary parameter setting) will operate
when Terminal 8 is designated as Dual Adjust and C1 closes.
51
Soft Stop
Start
E.Save / Slow / Reset
D. Adjust / Reverse / Re.
Common
1 2 3
Stop
Control wiring - D.G. Programming
4
5
6
7
8
9
C
L
N
D.G. Program will operate when Dip Switch 3 “Generator” is set
to On, Dip Switch 1 “Display format” is set to On, Terminal 8
is designated as Dual Adjust and C closes.
52
Soft Stop
Start
E.Save / Slow / Reset
D. Adjust / Reverse / Res.
Common
1 2 3
Stop
Control Wiring - Slow Speed Reverse
4
5
6
7
8
9
C1
L
N
C2
Slow Speed Reverse will operate when Terminal 7 is designated as
Slow Speed, Terminal 8 is designated as Reverse and when closing
C1 (before starting) and C2 (before or during motor running)
53
“Immediate Relay”
Immediate / ShearLpin
Relay
1 2 3
4 5 6 7 8 9 10 11 12
Selection by designating the Immediate Relay as:
* Immediate - with On and Off delays
* Shear pin - When relay is designated as Shear-pin
54
“Immediate Relay” - Immediate
Immediate
L
Relay
1 2 3
Applications
* Operating a valve
* Opening / closing a brake
4 5 6 7 8 9 10 11 12
On delay
after Start
Off Delay
after Stop
55
“Immediate Relay” - Immediate
D. Adjust
Immediate
Relay
1 2 3
4 5 6 7 8 9 10 11 12
Creating special Starting
Curves:
1. Designate “Imm Relay” as
Immediate and set On Delay
time
2. Designate Terminal 8 as “Dual
Adjust” and set parameters
Voltage
Ramp-up
On delay
56
Bypass Contactor
End of Acceleration
Relay
RVS-DN
M
1 2 3
L
N
4...9
13 14 15 16 17 18 19 20 21
57
Fault Relay
Fault Relay
1 2 3
4...9
13 14 15 16 17 18 19 20 21
Fault Relay programmable :
• Fault - upon fault 13-15 change position, returns upon fault reset
• Fault Fail Safe - Upon Control Supply connection 13-15 change
position, upon fault 13-15 returns, returns upon fault reset.
58
External Fault
Control Wiring - External Fault
1 2 3
4...9
13 14 15 16 17 18 19 20 21
External Fault input - connected between 19 and 21 (Neutral),
use short wires, can be used only when 21 is connected to Ground
or Neutral
59
Control Wiring - Optional Cards
Analogue I/O Board
Motor Insulation Alarm
Communication Board
28
Thermistor
25
22 N.C.
29
Thermistor
26
23 (-) RS485
30
Ground
27
24 (+) RS485
31 (-) Analogue
32 (+) Analogue
Digital Tacho Board
25 (+)
Encoder
(-)
26
27
Ground
60
Control Wiring – Fan Control
Jumper
A
B
C
K
1
L1
2
3
N
Internal Jumper
• When connected to A - fan (s) will operate as
long as Control Supply is connected to Terminals
1-3
• When connected to B - fan (s) will operate when
Control Supply is connected to Terminal 2 (for
example through a N.C. contact of the by-pass
contactor)
•
When connected to C - Fan (s) will operate
when relay K closes (Automatically upon start
signal, stops 5 min. after stop signal or when bypass contactor closes.
Notes :
• It is recommended to leave at factory default (A).
• For size A, 44-72A, modification should be done
by a field technician.
61
Presentation Content
1. Presentation
2. Power Wiring
3. Control wiring
4. Programming
4. Protection
62
RVS-DN Programming
63
RVS-DN Programming
• LED indications
Green
On
Lights when the control supply voltage is connected to the RVS-DN.
Yellow
Start
Lights during soft start, indicating that motor supply voltage is
ramping up.
Green
Run
Lights after completion of the starting process, indicating that motor
is receiving full voltage. This LED flashes during slow speed
operation.
Yellow
S.Stop
Red
Stop
Yellow
E.Save/Slow
Green
D.Adj./Rev
Red
Fault
Lights during soft stop, indicating that the motor supply voltage is
ramping down.
Lights when the motor is stopped.
Lights when ENERGY SAVE is in operation.
Flashes when the motor is running in SLOW SPEED.
Lights when DUAL ADJUSTMENT is in operation.
Flashes when motor is running in SLOW SPEED REVERSE.
Lights upon operation of any of the built-in protections.
Flashes when the INSULATION ALARM optional relay is activated.
64
Presentation Content
4. Programming
MONITORING PAGE
MAIN PARAMETERS
START PARAMETERS
STOP PARAMETERS
Shows only when
dipswitch #1 is ON
DUAL ADJUSTMENT PARAMETERS
EN. SAVE & SL. SPD PARAMETERS
FAULT PARAMETERS
I/O PROGRAMMING PARAMETERS
COMM. PARAMETERS
STATISTICAL DATA
65
Monitoring Page
% OF MOTOR FLA
55%
AMP.
0
VOLT
0
MOTOR INSULATION
52.8Mohm
THERMISTOR RES.
3.1 Kohm
OPTION CARD
NOT INSTALLED
66
Presentation Content
4. Programming
MONITORING PAGE
MAIN PARAMETERS
START PARAMETERS
STOP PARAMETERS
DUAL ADJUSTMENT PARAMETERS
EN. SAVE & SL. SPD PARAMETERS
FAULT PARAMETERS
I/O PROGRAMMING PARAMETERS
COMM. PARAMETERS
STATISTICAL DATA
67
Main Parameters
STARTER FLC
58 AMP.
As indicated on soft starter’s label
MOTOR FLA
58 AMP.
As indicated on soft motor’s label.
If motor is connected inside delta set
MOTOR FLA= (motor rated FLA/√3)
Can be set as low as 50% of FLC
CONNECTION TYPE
LINE
Set To INSIDE DELTA if soft starter is
connected inside delta.
68
Main Parameters
UNDER CURRENT - Trips the RVS-DN
when the motor current drops below
the level that was set for a time period
longer than UNDER CURRENT
DELAY.
• Adjustments:
– Trip Current: Off, 20-90% I FLA
– Trip Delay 1-40 sec.
• Applications
– Dry running pumps
– Broken belt / gear
– Closed air inlet (fan)
UNDERCURR. TRIP
0% OF FLA
UNDERCURR. DELAY
10 SEC.
I FLA
90%
80%
20%
Start
2
20
40 sec.
69
Main Parameters
O/C – SHEAR PIN - Operational when RVS-DN
is energized and has three trip functions:
• At all time - If I > 850% of FLC it trips the
RVS-DN within 1 cycle (overrides the value
of the O/C – SHEAR PIN setting).
• At starting process - If I > 850% of FLA it
trips the RVS-DN after O/C DELAY (see
here after)
• At run time - If I > O/C – SHEAR PIN setting
of FLA it trips the RVS-DN after O/C DELAY
Note:
850%
• The O/C SHEAR PIN is not intended to
IFLA
replace the fast acting fuses, required to
protect the thyristors.
• Adjustments:
– Trip Current: 100-850% of FLA
– Trip Delay 0-5 sec.
O/C SHEAR PIN
850% OF FLA
O/C DELAY
0.5 SEC.
Trip
70
Main Parameters
OVERLOAD TRIP
115% OF FLA
OVERLOAD TRIP - is operational
when running (the RUN LED is lit).
• Incorporates a thermal memory
register that calculates heating
minus dissipation of the motor.
Trips when the register fills up.
t
• The thermal register resets itself
15 minutes after the motor stops. .
• Adjustments:
OVERLOAD DELAY
4 SEC-AT 5 FLA
– Trip Current: 75-150% of FLA
– Trip Delay 1-10 sec.
10 sec
1 sec
75%
115%
O/L setting
150%
trip time at
500% FLA
I
500%
71
Main Parameters
UNDERVOLT. TRIP
300 VOLT
UNDER VOLTAGE - Trips the RVSDN when the motor voltage drops
below the level that was set for a
time period longer than UNDER
VOLTAGE DELAY.
• Adjustments:
Voltage
– Trip Voltage: 120-600V *
– Trip Delay 1-10 sec.
600V
* 600-900V (RVS-DN 1000V)
UNDERVOLT. DELAY
5 SEC.
120V
Start
1
10 sec.
72
Main Parameters
OVERVOLT. TRIP
480 VOLT
OVER VOLTAGE - Trips the RVS-DN
when the motor voltage is above
level that was set for a time period
longer than OVER VOLTAGE DELAY.
• Adjustments:
Voltage
– Trip Voltage: 150-750V *
750V
– Trip Delay 1-10 sec.
* 1100-1300V (RVS-DN 1000V)
OVERVOLT. DELAY
2 SEC.
150V
Start
1
10 sec.
73
Presentation content
4. Programming
MONITORING PAGE
MAIN PARAMETERS
START PARAMETERS
STOP PARAMETERS
DUAL ADJUSTMENT PARAMETERS
EN. SAVE & SL. SPD PARAMETERS
FAULT PARAMETERS
I/O PROGRAMMING PARAMETERS
COMM. PARAMETERS
STATISTICAL DATA
74
Start Parameters
SOFT START CURVE
SOFT START CURVE
0 (STANDARD)
1 !!SOFT START CURVE
2 !!SOFT START CURVE
3 !!SOFT START CURVE
4 (TORQUE)
• START CURVE 0 – Standard curve (Default). This curve is the most
suitable curve for preventing prolonged starting and motor overheating.
Note:
When RVS-DN is connected Inside Delta, the RVS-DN will always use
CURVE 0 regardless of the curve defined.
• START CURVES 1-3 - Pump Control - Induction motors produce peak
torque of up to 3 times the rated torque towards the end of starting
process. In some pump applications, this peak may cause pressure surge
in the pipes.
• Start Curves 1, 2, 3 – During acceleration, before reaching peak torque,
the Pump Control Program automatically controls the voltage ramp-up,
thus, reducing peak torque.
75
Start Parameters
When starting with a standard soft starter Starting Torque is reduced drastically,
however Peak Torque still remains high,
causing high Acceleration Torque towards the
end of the starting process.
Peak & Acceleration Torque must be reduced
to extend the Acceleration time.
Torque
Voltage
SOFT START CURVE
SOFT START CURVE
0 (STANDARD)
1 !!SOFT START CURVE
2 !!SOFT START CURVE
3 !!SOFT START CURVE
4 (TORQUE)
Speed
D.O.L
With soft
starter
M start
soft
starter
Time
Accel.
Torque
Load
Speed
Time
76
Start Parameters
SOFT START CURVE
SOFT START CURVE
0 (STANDARD)
1 !!SOFT START CURVE
2 !!SOFT START CURVE
3 !!SOFT START CURVE
4 (TORQUE)
D.O.L
0
With soft starter
0
1 2 3
4
Speed
Torque
Voltage
DOL
1
Area of
Pump Control
Start Curves
Time
2
3
Speed
Time
77
Start Parameters
Start Curve 4 (Torque) – Torque Controlled
acceleration, provides a smooth time
controlled torque ramp for the motor and the
load (pump).
SOFT START CURVE
SOFT START CURVE
0 (STANDARD)
1 !!SOFT START CURVE
2 !!SOFT START CURVE
3 !!SOFT START CURVE
4 (TORQUE)
Note - Always start with Start Curve 0. If towards
end of acceleration, peak torque is too high
(pressure is too high), proceed to Curve 1, 2, 3
or 4 if necessary.
Torque
Tn
Linear Torque
increase
Peak over speed (Torque)
acceleration
Slight time increase
smoothes the Peak
Ideal
Conditions
IV
Time = t1
Time < t1
Time
Time > t1
78
Start Parameters
PULSE TIME
0 sec.
PULSE TIME - Intended to start high friction loads that
require high starting torque for a short time.
• A pulse of 80% Un without CURRENT LIMIT is
initiated to break the load free.
• Pulse duration is adjustable, 0.1–1sec. After this
pulse the voltage is ramped down to INITIAL
VOLTAGE setting before ramping up again to full Un
voltage according to the START PARAMETERS
settings.
Note:There is no PULSE START function when RVSDN is connected Inside Delta.
time
0.1 - 1 sec.
79
Start Parameters
INITIAL VOLTAGE - determines the Initial
Torque (the Torque is reduced in the
square proportion of the voltage
reduction).
Note: When INITIAL VOLTAGE is set its
maximum value, this displays changes to
INITIAL CURRENT.
• Adjustments:
– 10-50% (80%) Un, should be set so
that motor starts turning immediately
after Start signal initiated
– 100-400% FLA when INITIAL
CURRENT is reached
Initial
Voltage
INITIAL VOLTAGE
30%
INITIAL CURRENT
100%
Un
50
%
10
%
80
Start Parameters
INITIAL CURRENT - determines initial Ramp-Up
starting Current. When needed, increase Initial
Voltage to Max. (over the 50% or 80%
respectively). The LCD displays INITIAL
CURRENT and the starter will linearly Ramp Up
the current following the desired acceleration
time.
INITIAL CURRENT
100%
Current
Imax (400%)
I init.(100%)
Linear Current
increase
Ideal
Conditions
Time
Start time
81
Start Parameters
CURRENT LIMIT - determines the maximum
current during acceleration process and the
acceleration time to full speed.
• Adjustments:
CURRENT LIMIT
400% OF FLA
– 100-400% (500%) of FLA
Set to the highest acceptable current.
I start
Un
U C. L
400%
U1
U start
Current
Limit
100%
t soft start
82
RPM
Start Parameters
CURRENT LIMIT
400% OF FLA
• CURRENT LIMIT/starting time ratio
Lower CURRENT LIMIT => Longer start time
4 x In
3 x In
In
5
10
15
20
25
30
Time
83
Start Parameters
ACCELERATION TIME - Determines the Voltage
Ramp-up Time, from Initial to Full Voltage.
• Adjustable :1-30 (90) sec.
Set to the shortest acceptable time.
ACC. TIME
10 SEC.
Un
U start
30 (90) sec
1
Voltage Ramp-up Time
Time
84
Start Parameters
MAX. START TIME
30 SEC.
MAX. START TIME - Preventing Stall condition, trips
the starter if current is not reduced below Motor
FLA within the adjusted time.
• Adjustments:
– 1-30 (250) sec.
Starting
Current
10
20
Max. Starting Time
30
85
Start Parameters
• Limits the NUMBER OF STARTS during
the period of time defined by STARTS
PERIOD.
• If you try to start even one more time
within that period the START INHIBIT
period will take effect. During the START
INHIBIT period the WAIT BEFORE RST
XX MIN message will be displayed.
• Adjustments:
NUMBER OF STARTS
10
STARTS PERIOD
30 MIN.
START INHIBIT
15 MIN.
– NUMBER OF STARTS – 1-10, OFF
– STARTS PERIOD, START INHIBIT - 1-60min.
86
Start Parameters
RUN CONTACT DELAY - Sets time delay for
END OF ACCELERATION relay to close.
• Adjustments:
RUN CONTACT DEL.
5 SEC.
– 0-120 sec.
End of Acceleration
Relay
RVS-DN
M
1 2 3
L
N
4...9
13 14 15 16 17 18 19 20 21
87
Presentation Content
4. Programming
MONITORING PAGE
MAIN PARAMETERS
START PARAMETERS
STOP PARAMETERS
DUAL ADJUSTMENT PARAMETERS
EN. SAVE & SL. SPD PARAMETERS
FAULT PARAMETERS
I/O PROGRAMMING PARAMETERS
COMM. PARAMETERS
STATISTICAL DATA
88
Stop Parameters
SOFT STOP CURVE
SOFT STOP CURVE
0 (STANDARD)
1 !!SOFT STOP CURVE
2 !!SOFT STOP CURVE
3 !!SOFT STOP CURVE
4 (TORQUE)
•
STOP CURVE 0 – Standard Curve (Default) – voltage is linearly reduced from nominal to zero.
The most stable and suitable curve for preventing prolonged stopping and motor overheating.
• STOP CURVES 1, 2, 3 Pump Control – In some pump applications, when pumping to higher
elevation a considerable part of the torque is constant and does not decrease with speed.
It may happen that during the deceleration process when voltage decreases the motor torque
abruptly falls below load torque (instead of smoothly decreasing speed to zero), thus closing the
valve and causing water hammer.
Curves 1, 2 and 3 eliminate the water hammer phenomenon. In pump applications the load
torque decreases in square relation to the speed, thus correcting control of voltage to reduce
torque adequately and to smooth deceleration to a stop.
Note:
• It is recommended that STOP CURVE 0 be used for all standard applications (not pumps).
• To reduce water hammer, select STOP CURVE 1, then 2, then 3 in that order.
89
Stop Parameters
When stopping with a D.O.L starter speed is quickly reduced and flow
abruptly stopped. This may cause a
Water Hammer (mechanical shock
and audible noise) with severe
damage to pipes, joints, fittings,
valves, etc.
SOFT STOP CURVE
SOFT STOP CURVE
0 (STANDARD)
1 !!SOFT STOP CURVE
2 !!SOFT STOP CURVE
3 !!SOFT STOP CURVE
4 (TORQUE)
Un
DOL opens
Speed
90
Stop Parameters
SOFT STOP CURVE
Stopping with a standard soft starter SOFT STOP CURVE
0 (STANDARD)
when pumping to a higher elevation,
1 !!SOFT STOP CURVE
2 !!SOFT STOP CURVE
motor torque may quickly fall below
3 !!SOFT STOP CURVE
load torque (as torque decreases at the
4 (TORQUE)
square of voltage reduction). This may
cause abrupt stalling instead of
smoothly decreasing speed to zero,
creating the Water Hammer
Stalling point
phenomenon
U
n
“Soft stop”
Speed
91
Stop Parameters
D.O.L
0
Speed
Torque
Voltage
SOFT STOP CURVE
SOFT STOP CURVE
0 (STANDARD)
1 !!SOFT STOP CURVE
2 !!SOFT STOP CURVE
3 !!SOFT STOP CURVE
4 (TORQUE)
1
Area of
Pump Control
Stop Curves
Time
2
3
Speed
0
1 2 3 4
DOL With soft starter
Time
92
Stop Parameters
DECELERATION TIME - Used for controlled
deceleration of high friction loads.
Determines the motor’s voltage ramp down
time.
• Adjustments:
DEC. TIME
10 SEC.
– 1-30 sec. (90)
Un
2
Speed
30 / 90 sec
Deceleration Time
93
Stop Parameters
Area of
Pump Control
Final Torque
FINAL TORQUE
0 (MIN.)
Speed
Voltage
FINAL TORQUE - Determines torque towards the
end of a soft stop. If the current still flows after
speed is softly reduced to zero, you should
increase the FINAL TORQUE setting.
• Adjustments:
– 0(MIN)-10(MAX)
Check Valve
closes and
motor stops
Time
Time
DOL
94
Presentation Content
4. Programming
MONITORING PAGE
MAIN PARAMETERS
START PARAMETERS
STOP PARAMETERS
DUAL ADJUSTMENT PARAMETERS
EN. SAVE & SL. SPD PARAMETERS
FAULT PARAMETERS
I/O PROGRAMMING PARAMETERS
COMM. PARAMETERS
STATISTICAL DATA
95
Dual Adjustment
Two sets of parameters - for Variable
Loads, Two Speed Motors and
D.ADJ.:GENERATOR PARAMETERS
DA: INIT. VOLT.
30%
DA: INIT. CURRENT
100%
DA: CUR. LIMIT
400% OF FLA
DA: ACC. TIME
10 SEC.
DA: DEC. TIME
10 SEC.
DA: MOTOR FLA
31 AMP.
96
Dual Adjustment
• Using two starting characteristics, the starter will accelerate to
DA-IV reaching 100% current limit. After Tx (Imm. Relay delay)
voltage to terminal 8 is switched off, using the standard
characteristic to complete acceleration. Useful to prevent initial
high acceleration. (Applications: Submersible pumps, Drum
fans with resonating frequency, etc).
U%
100
25
10
t1
Tx
t2
t
97
Dual Adjustment
Control wring for Dual Adjustment implementing two starting characteristics:
98
D.ADJ.:GENERATOR PARAMETERS
Usage of D.ADJ.:GENERATOR PARAMETERS mode:
• The D.ADJ.:GENERATOR PARAMETERS must not
always be used when a diesel generator is supplying
the RVS-DN. Only use D.ADJ.:GENERATOR
PARAMETERS when the normal starting process fails,
i.e. SHORTED SCR or WRONG CONNECTION faults
occur, and only after you have tested and are sure
that the SCRs, motor and motor connections are not
faulty.
99
D.ADJ.:GENERATOR PARAMETERS
To operate D.ADJ.:GENERATOR PARAMETERS mode:
• Set dip switch # 3 and dip switch #1 to on
• Insert a contact (or jumper) between Control Supply and
input terminal 8 (DUAL ADJUST) and close contact to
operate the D.ADJ.:GENERATOR PARAMETERS. Dual
Adjust LED will light.
• Set the DUAL ADJUST parameters to the values
necessary for the application (e.g., shorter
ACCELERATION TIME, lower CURRENT LIMIT, etc.).
100
D.ADJ.:GENERATOR PARAMETERS
Control wring for D.ADJ.:GENERATOR PARAMETERS:
101
Presentation Content
4. Programming
MONITORING PAGE
MAIN PARAMETERS
START PARAMETERS
STOP PARAMETERS
DUAL ADJUSTMENT PARAMETERS
EN. SAVE & SL. SPD PARAMETERS
FAULT PARAMETERS
I/O PROGRAMMING PARAMETERS
COMM. PARAMETERS
STATISTICAL DATA
102
EN. Save & SL. SPD Parameters
SAVING ADJUST.
0 (MIN.)
SAVING ADJUST - potential saving and P.F.
improvement on lightly loaded motors .
• Adjustable:
– 0-10 (Min-Max) .
Note – may not meet CE requirements
Un
In
I motor
time
103
EN. Save & SL. SPD Parameters
SLOW SPEED TORQUE - Motor operates at 1/6
speed, Forward or Reverse (no contactors
required)
• Adjustable:
– 1(MIN)-10(MAX).
– 1-30 SEC (250)
• Applications:
Speed
SLOW SPEED TORQ.
8
MAX SLOW SP TIME
30 SEC.
– Positioning
– Sewage pumps Nn
1/6 Forward
1/6 Reverse
Max. Slow Speed Time 30 Sec.
104
Presentation Content
4. Programming
MONITORING PAGE
MAIN PARAMETERS
START PARAMETERS
STOP PARAMETERS
DUAL ADJUSTMENT PARAMETERS
EN. SAVE & SL. SPD PARAMETERS
FAULT PARAMETERS
I/O PROGRAMMING PARAMETERS
COMM. PARAMETERS
STATISTICAL DATA
105
Fault Parameters
PHASE LOSS - protection trips the RVS-DN when 1
or 2 phases are missing for more than 1 sec.
Notes:
The range of the PHASE LOSS can be extended to
YES or NO by using the EXPANDED SETTING
Do not set PHASE LOSS to NO unless it is found to
be necessary in the field!
PHASE LOSS Y/N
YES
106
Fault Parameters
PHASE SEQ - protection trips the RVS-DN when
phase sequence is wrong.
Notes:
When RVS-DN is connected Inside Delta, you can not
set PHASE SEQUENCE protection to NO.
Set to NO when reversing contactors in the input.
PHASE SEQ. Y/N
NO
107
Fault Parameters
Motor Insulation (optional) - tests motor insulation level
when motor is not running (requires a Line
Contactor or disconnecting a Line C/B etc. ).
• Adjustments:
– Alarm Level: 0.2 - 5 Mohm
– Trip Level: Off, 0.2 - 5 Mohm
• Applications
INSULATION ALARM
OFF
INSULATION TRIP
OFF
– Submersible pumps
– Harsh environments
– Motors not running for a long period of time.
S
108
Fault Parameters
The RVS-DN can be automatically reset for
UNDER VOLTAGE and PHASE LOSS
faults.
To start the motor after UNDER VOLTAGE
and PHASE LOSS faults have been
cleared, remove the START signal and
recommence the signal.
Note: AUTO RESET function has a nonprogrammable time delay of 60 seconds.
AUTO RESET
NO
109
Fault Parameters
Motor Thermistor Input - Over Temp Protection (option,
in place of Insulation Card)
• Adjustments:
– THERMISTOR TYPE: PTC or NTC
– Trip Level: Off, 0.1 - 10Kohm
• Note - the Analog card contains also Analog Output,
related to motor’s current (0-10VDC, 4-20mA, 020mA)
THERMISTOR TYPE
PTC
THERMISTOR TRIP
OFF
110
Fault Parameters
• If the UNDER CUR. RESET setting is OFF then
RVS-DN will not automatically reset after an
UNDER CURRENT TRIP fault occurs.
If you set the UNDER CUR. RESET setting to a
time value then RVS-DN will automatically reset
with a delay (the time defined for UNDER CUR.
RESET), but only after the start signal is removed.
To restart the motor recommence the start
command.
• Adjustment:
– 10-120min., off
UNDER CUR. RESET
OFF
111
Presentation Content
4. Programming
MONITORING PAGE
MAIN PARAMETERS
START PARAMETERS
STOP PARAMETERS
DUAL ADJUSTMENT PARAMETERS
EN. SAVE & SL. SPD PARAMETERS
FAULT PARAMETERS
I/O PROGRAMMING PARAMETERS
COMM. PARAMETERS
STATISTICAL DATA
112
I/O Programming Parameters
PROG. INPUT #7
RESET
RESET, SLOW SPEED, ENERGY SAVER
PROG. INPUT #8
DUAL ADJUSTMENT
DUAL ADJUSTMENT, SLOW SPD REVERSE, RESET
FAULT RELAY TYPE
FAULT
FAULT, FAULT-FAIL SAFE
IMM/ S.PIN RELAY
IMMEDIATE
IMMEDIATE, SHEAR PIN
RELAY ON DELAY
0 SEC.
0-3600 SEC.(IMMEDIATE), 0.0-5SEC (SHEAR PIN)
RELAY OFF DELAY
0 SEC.
0-3600 SEC.(IMMEDIATE), 0.0-5SEC (SHEAR PIN)
AN. OUT PARAMETER
I, 0...200% OF FLA
I, 0...200% OF FLA; I, 0...200% OF FLC or inverted(1000V)
113
Presentation Content
4. Programming
MONITORING PAGE
MAIN PARAMETERS
START PARAMETERS
STOP PARAMETERS
DUAL ADJUSTMENT PARAMETERS
EN. SAVE & SL. SPD PARAMETERS
FAULT PARAMETERS
I/O PROGRAMMING PARAMETERS
COMM. PARAMETERS
STATISTICAL DATA
114
Comm. Parameters
Modbus menu
PROTOCOL
MODBUS
COMM. PROTOCOL
PROFIBUS
BAUD RATE
9600 (MODBUS)
BAUD RATE
AUTO (PROFIBUS)
PARITY CHECK
EVEN
PROFI.NETWORK ID
126
SERIAL LINK NO.
OFF
S. LINK PAR. SAVE
DISABLE
S. LINK PAR. SAVE
DISABLE
SER. LINK CONTROL
DISABLE
SER. LINK CONTROL
DISABLE
FRONT COM ADDRES
OFF
FRONT COM ADDRES
OFF
STORE ENABLE
COMM. PARAMETERS
Profibus menu
115
Presentation Content
4. Programming
MONITORING PAGE
MAIN PARAMETERS
START PARAMETERS
STOP PARAMETERS
DUAL ADJUSTMENT PARAMETERS
EN. SAVE & SL. SPD PARAMETERS
FAULT PARAMETERS
I/O PROGRAMMING PARAMETERS
COMM. PARAMETERS
STATISTICAL DATA
116
Statistical Data
LAST STRT PERIOD
NO DATA
LAST STRT MAX I
NO DATA
TOTAL RUN TIME
0 HOURS
TOTAL # OF START
0
PREVIOUS TRIP -2
NO DATA
.
.
.
LAST TRIP
NO DATA
TRIP CURRENT
0 % OF FLA
TOTAL # OF TRIPS
0
PREVIOUS TRIP -9
NO DATA
117
Presentation Content
1. Presentation
2. Power Wiring
3. Control wiring
4. Programming
4. Protection
118
Protection
Under/Over Frequency
Operational when the RVS-DN is energized and protects the motor when the
frequency is less than 45 or greater than 65Hz.
Phase Loss
Operational when the RVS-DN is energized, provided this protection has not been deactivated. Phase loss protection trips the RVS-DN when 1 or 2 phases are missing for
more than 1 sec.
Phase Sequence
Operational when the RVS-DN is energized, provided this protection has not been deactivated. Phase sequence protection trips the RVS-DN when phase sequence is
wrong.
119
Protection
Wrong Connection
Operational after start signal. Trips if motor is not properly connected to the RVS-DN’s
load terminals, when internal disconnection is detected in the motor winding. This
protection is not active when D. ADJ.: GENERATOR PARAMETERS is selected.
R
C
400V
120
Protection
Shorted SCR
Trips the RVS-DN if one or more of the SCRs have been shorted. This protection is not
active when D. ADJ.: GENERATOR PARAMETERS is selected.
Heat-Sink Over Temperature
Thermal sensors are mounted on the heat-sink and trip the RVS-DN when the
temperature rises above 85ºC
External Fault
External Fault becomes operational when RVS-DN is energized.
The RVS-DN will trip if contact closes for more than 2 sec.
121
Protection
Active During
Timing And Occurrence
Too many starts with START INHIBIT period
Start
Run
Stop
Soft Stop
√
√
Electronic overload with curve selection
O/C shear pin (jam)
RVS-DN protection – trip immediately at I≥850% FLC
√
√
√
Motor protection – trip function
During start – factory set at 850% FLA after O/C DELAY.
√
√
During run – adjustable 200 – 850% FLA after O/C DELAY.
√
Under current adjustable time delay
√
Phase loss
√
Phase sequence
√
√
√
122
Protection
Active During
Timing And Occurrence
Start
Run
Under voltage with adjustable time delay. Time delay is
override in case of PHASE LOSS.
√
√
√
Over voltage with adjustable time delay
√
√
√
Long start time (stall protection)
√
Shorted SCR
√
Wrong connection (load loss)
√
External fault – input from a N.O. contact
√
√
√
√
SCR protection by Metal Oxide Varistors (MOV)
√
√
√
√
RVS-DN over-temperature
√
√
√
√
RVS-DN internal test, when the On LED is lit.
√
√
√
√
Soft Stop
√
Motor insulation test (optional) – Two levels for alarm & trip.
When installed, operates when mains voltage is removed.
Motor thermistor (optional) – programmable PTC/NTC, with
adjustable trip level.
Stop
√
√
√
√
√
123
RVS-DX Technical Presentation
Yuval Paz – Technical Support Manager
124
RVS-DX
125
Presentation content
1. Presentation
2. Power & control Wiring
3. RVS-DX vs. RVS-DN
126
Main features
•
•
•
•
•
•
•
•
•
•
•
•
Digital Soft Starters with internal bypass and motor protection
8-1100A; 230-600V
For enhanced Applications and Price Driven Market
Includes most of the RVS-DN winning features.
Standard Duty Design include bypass: 350% In, 15 sec. at 40°C
Range: 8-1100A, 220-600V
Third Generation Digital circuitry Field proven experience
Incorporating : Soft Start, Current Limit, Soft Stop, Comprehensive
Motor Protection, built-in internal bypass
Simple Installation and operation
Narrow footprint (book type)
Power and cos phi measurements
UL, cUL to 170A
127
Starter
Frame
Motor KW
Type
Size
400V
RVS-DX 8
4
RVS-DX 17
7.5
RVS-DX 31
D1
15
RVS-DX 44
22
RVS-DX 58
D2
30
RVS-DX 72
37
RVS-DX 85
D3
45
RVS-DX 105
55
RVS-DX 145
D4
75
RVS-DX 170
90
RVS-DX 210
110
RVS-DX 310
D5
160
RVS-DX 390
200
RVS-DX 460
D6
250
RVS-DX 580
315
RVS-DX 650
400
RVS-DX 820
450
RVS-DX 950
D7
550
RVS-DX 1100
650
Starter should be selected according to motor’s Full Load Amp and starting conditions128
RVS-DX Front Panel
Sizes : D1 8-44A
D2 58-72A
D3 85-105A
D4 145-210A
D5 310-390A
D6 460-820A
D7 950-1100A
LED’s for status
display
Lin
e
Simple 6
pushbutton
operation
IP 20 8-44A
Finger protected
for safe operation
Control terminals
(Plug-in)
LCD for
programming
Data & statistics
display
Load
End of Acceleration
and fault relays
(Plug-in)
129
RVS-DX Internal Components
SMT
components
End of Acceleration &
Trip (prog.) Relays –
1 N.O. each
Compact size
Aluminum case
Built-in Bypass for
minimum heat
dissipation
130
AX, DX Internal view
Line
C/T
Bypass Relay
Latched, 12VDC
>145A two in parallel
Thyristor
Semitop up to 44A
Standard above it
Motor
131
Presentation content
1. Presentation
2. Power & control Wiring
3. RVS-DX vs. RVS-DN
132
Power & control wiring
133
Presentation content
1. Presentation
2. Power & control Wiring
3. RVS-DX vs. RVS-DN
134
RVS-DN vs. RVS-DX
Construction
RVS-DN
RVS-DX
Starting ratings
400% In, 30
Sec. @ 50°C
350% In, 15
Sec. @40°C
Built-in Bypass
-
■
Enclosed, rugged
construction
■
■
Preparation for by-pass
contactor
■
Internal Bypass
Starter voltage range
220-1,000V
220-600V
Starter current range
8 – 3,000A
8 – 1,100A
0 – 50°C
0 – 40°C
Operating temperature range
135
RVS-DN vs. RVS-DX
Start / Stop Features
RVS-DN
RVS-DX
Digital Micro Processor base
■
■
Soft Start
■
■
Soft Stop
■
■
Current Limit
■
■
Torque Control – optimizing starting &
stopping process
■
■
Current Control
■
■
Pulse Start (Kick Start)
■
■
Dual Adjustment - 2 start/stop
characteristics and overload, designed
for varying load applications and 2
speed motors
■
■
Pump Control - six start / stop curves
■
■
136
RVS-DN vs. RVS-DX
Start / Stop Features (Continued)
RVS-DN
RVS-DX
Slow Speed - 1/ 6 nominal speed for
positioning
■
■
Electronic Reversing at Slow Speed
■
■
Linear Acceleration - tacho. feedback
0-10V
■
-
Special Starting Process - for weak
diesel generator supplies
■
■
Energy saver
■
-
137
RVS-DN vs. RVS-DX
Motor & Starter Protection
RVS-DN
RVS-DX
Too Many Starts with Start Inhibit
period
■
■
Electronic Overload with Curve
Selection
■
■
Electronic Fuse with two settings for
Start & Run
■
■
Under Current, adjustable Time Delay
■
■
Phase Loss
■
■
Phase Sequence
■
■
Under Voltage with adjustable Time
Delay
■
■
Over Voltage with adjustable Time
Delay
■
■
Long Start Time (Stall Protection)
■
■
138
RVS-DN vs. RVS-DX
Motor & Starter Protection
(Continued)
RVS-DN
RVS-DX
Shorted SCR
■
■
Wrong Connection (Load Loss)
■
■
External Fault - input from a N.O
contact
■
■
SCR Protection by Metal Oxide
Varistors
■
■
Starter Over Temperature
■
■
Optional
No
Motor Insulation test, two levels for
Alarm & Trip
139
RVS-DN vs. RVS-DX
Displays
LCD - two lines 16 characters,
language selection between
English, French, German, Spanish,
displaying:
Parameter settings, Motor current,
Insulation level (when option is
included),
Statistical Data : Last start current
& time, Total Run time, Total
number of Starts & Trips, Last Trip
Language selection by
Illuminated LCD
Indicating lights for complete status
display
RVS-DN
RVS-DX
■
■
Internal dipswitch
Software
■
■
8 LEDs
4 LEDs
140
RVS-DN vs. RVS-DX
Control
RVS-DN
RVS-DX
Digital, Microprocessor Control
■
■
Opto-isolated control inputs
■
■
Auxiliary relays (total No. of relays)
3 C/O
8A/250V,
1800VA
2 N/O
58A/250V
“Immediate” contact” with adjustable
On & Off time delays.
■
■
“End of acceleration” contact with
adjustable time delay
■
■
“Fault” contact
■
■
Immediate contact can be set as
Shear Pin Alarm
■
-
Local and Remote Reset (hard
wired or by communication)
■
■
141
RVS-DN vs. RVS-DX
Control (Continued)
RVS-DN
RVS-DX
Communication RS485 with
MODBUS protocol for full control
(parameter modification, start, stop,
reset etc + supervision)
Option
Option
Communication Profibus protocol for
full control (parameter modification,
start, stop, reset etc + supervision)
Option for
75A and up
(consult
factory for
smaller
sizes)
Option for
210 and up
(consult
factory for
smaller
sizes)
Analog Card includes: Analog
output, related to motor’s current,
selectable 0-10VDC or 4-20mA or o20mA and Thermistor input
selectable as PTC or NTC.
Option
Option
142
Analog soft starters
Technical Presentation
Yuval Paz – Technical Support Manager
143
RVS-AX
Analog Soft Starter with internal bypass* and motor protection
8-170 A; 230-600V
For Simple Application and the Price Driven Market
* Internal bypass in 31-170A models
144
RVS-AX Advantages
• Standard Duty Design include bypass: 300% In for 30 sec,
350% In for 20 sec 400% In for 5 sec. at 40°C, 4 starts per hour.
• Range: 8-170A, 220-600V
• Third Generation Analog Field proven experience
• Incorporating : Soft Start, Current Limit, Soft Stop, Motor
Protection, internal bypass (31-170A models)
• Narrow footprint (book type)
• Simple Installation and operation
UL
cUL
145
RVS-AX Selector Guide
Starter
Type
RVS-AX 8
RVS-AX 17
Frame Internal Motor KW
Size
ByPass 400V
4
7.5
RVS-AX 31
A1
RVS-AX 44
RVS-AX 58
A2
RVS-AX 72
RVS-AX 85
A3
RVS-AX 105
RVS-AX 145
RVS-AX 170
A4
■
15
■
22
■
30
■
37
■
45
■
55
■
75
■
90
Starter should be selected according to motor’s Full Load Amp and starting
conditions
146
RVS-AX
Sizes : A1 8-44A
A2 58-72A
A3 85-105A
A4 145-170A
Line
Potentiometers
for simple
adjustments
LEDs for
status
display
IP 20 8-44A
Finger protected
for safe operation
(8-44A models )
Control terminals
(Plug-in)
Load
147
Neutral
1
2
3
4
5
Fault
Stop
No Connection
End of
Acc.
Start
RVS-AX - Control wiring
6
7
8
* Control voltage to the electronic circuitry is derived from three phase supply
* Connect Neutral to terminal 3 to enable Phase Loss Protection (when
Neutral
is not available or not connected to Terminal 3 starter may not detect
Phase Loss
of lightly loaded motors.
* Use “dry contact” between terminals 1&2 to start/stop the soft starter.
* Do no apply start/stop signal to terminals 1&2 simultaneously with voltage
148
to terminals L1, L2, L3.
RVS-AX - Easy Adjustments
•
•
•
•
Motor FLC
Initial Voltage
Current Limit
Ramp-up Time
• Ramp-down Time
• Overload Trip
50-100% Starter FLA setting *
10-50% Un
100-400% Motor FLA setting
2-30 sec.
0.2-30 sec.
115% Motor FLA setting, factory set.
* e.g. for motor 100A and Starter 105A, set 100 x 100 =
95%
105
149
RVS-AX - Motor Protection
•
•
•
•
Electronic overload
Phase Loss
Heatsink Over Temperature
Built in bypass (31-170A
models)
150
RVS-AX - Applications
–
–
–
–
–
–
Pumps
Fans and blowers
Compressors
Transport systems
Conveyors
Weak mains and generator networks
151
Solstart Plus
Analog Soft Starters with internal bypass and motor protection
31-170A; 230-600V
For Simple Application and the Price Driven Market
Unique – 2 phase control, motor protection and bypass
152
Solstart Plus - Sizes and features
FLC
[A]
Start/stop
Dimensions
by
WxHxD
Voltage
[mm]
free
contact
Solstart +
31
31
65x190x114
Solstart +
44
44
65x190x114
Solstart +
58
58
120x265x12
1
O



-
Solstart +
72
72
120x265x12
-1
O



-
Solstart +
85
85
120x265x12
1
O



-
Solstart +
105
105
120x265x12
1
O



-
Solstart +
145
145
129x275x18
2
O



-
129x275x18
2
O



153
Solstart+
type
Solstart +
170
170
EOA
Relay
Fault
Relay
Aluminum
case
Din Rail
mounted
O
-


O
O
-


O
1
2
3
4
5
Fault
End of
Acc. *
{ Start/Stop
{ Control Voltage
Solstart Plus - Control wiring
6
7
8
~
* End of Acceleration output relay from 58A and up.
154
Solstart Plus - Easy Adjustments
•
•
•
•
Motor FLC
Initial Voltage
Current Limit
Ramp-up Time
50-100% Starter FLA setting *
10-50% Un
100-400% Motor FLA setting
2-10 sec.
• Ramp-down Time
0.2-10 sec.
• Overload Trip
115% Motor FLA setting,
factory set.
* e.g. for motor 100A and Starter 105A, set 100 x 100 =
95%
105
155
Solstart Plus - Motor Protection
•
•
•
•
Electronic overload
Under Voltage
Phase Loss
Heatsink Over
Temperature
• Built in bypass
156
Solstart Plus - Applications
–
–
–
–
–
–
Pumps
Fans and blowers
Compressors
Transport systems
Conveyors
Weak mains and generator networks
157
Solstart
Analog Soft Starters with internal bypass
31-170A; 230-600V
For Simple Application and the Price Driven Market
Unique – 2 phase control and bypass
158
Solstart - Technical Advantages







Current Range:
Initial Voltage:
Ramp-up Time:
Ramp-down Time:
Starts per hour
loads)
Protection
Mounting
8 - 170A
10 - 80%
0.5 - 5 Sec.
0.5 - 5 Sec.
4. (10 starts per hour for light
IP 20
DIN Rail (8-31A)
159
Solstart - Marketing Advantages

Motors 8-170A , 220-600V (8A @ 690V is available) (4-37KW, 540HP)

Standard Duty Design include bypass: 350% In for 5 sec, 4
starts per hour. (Up to 10 starts per hour at light loads)








Includes a bypass
Second Generation
Easy settings & operation
Compact
Small foot print
Cost Effective
Simple replacement for Star/Delta Systems
Starts single phase motors as well as three phase motors
160
Solstart - Two-phase Control
Start
L1
L2
L3
a. Voltage is control no two phases only
b. Internal by-pass relays
c. One phase Motor start (only in 230V version)
U
V
W
End Of Acceleration (31-170A)
161
Solstart 8-170A – Din rail and EOA relay
Start
Start
L1
L2
L3
L1
L2
L3
U
V
W
EOA
U
V
W
8-22A
Din Rail Standard
EOA relay - NA
31-170A
Din Rail – Optional (31-58A)
EOA relay - Standard
162
Solstart - Easy Adjustments
- 8-170A, 230-600V
- Soft Start
- Soft Stop
- Compact
- Easy to use
163
Solstart - Technical details











Max. Current:
Initial Voltage:
Ramp-up Time:
Ramp-down Time:
Starts per hour:
applications)
Protection:
Adjustment:
Mounting:
Dual Phase Bypass:
End Of Acceleration:
Enclosure:
8-170A
0 - 85%
1 - 5 Sec.
1 - 5 Sec.
4 (Max. 10 starts per hour for light
IP 20 (31-58A)
Three potentiometers
DIN Rail up to 22A, Option 31-58A
One phase (L2-V) direct connection
Standard Relay output 31-170A, N.A. 8-22A
ABS No Smoke Plastic 8-22A,
Molded Aluminum 31-170A
164
Solstart - Applications
– Small Pump Motors
– Fans and blowers
– Compressors
– Transport systems
– Conveyors
165
Analog soft starters comparison
RVS-AX
Solstart
Solstart Plus
Starting capacity
300% 30 sec. 4 starts per hour
350% 5 sec. 4 starts per hour
300% 15 sec. 4 starts per hour
Range
8-170
8-170
31-170
Controlled phases
3
2
2
Control voltage
No control voltage
No control voltage
110-230V AC/DC
Control input
Dry contact
Dry contact
110-230V AC/DC
Protection



Electronic overload
Phase loss
Heat sink over
temperature
No Protection




Electronic overload
Phase loss
Under voltage
Heat sink over temperature
LEDs






ON
RampUp/Down
Run
Overload
Phase loss
Over temperature








ON
RampUp/Down
Run
Overload
Fault
Settings



IV-10-50%
Ramp Up-2-30sec
Ramp Down-0.2-30sec

IV-10-80%

Ramp Up-0.5-5sec
Ramp Down-0.5-5sec



IV-10-80%
Ramp Up-0.5-10sec
Ramp Down-0.5-10sec
Output contacts


End of acceleration
Fault


End of acceleration (58A and
up)
166
Fault
ON
Ramp
Run
End of acceleration (31A
and up)

The End