Download Definition Crest Factor - AMETEK Programmable Power

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Mercury-arc valve wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power over Ethernet wikipedia , lookup

Stray voltage wikipedia , lookup

Electrical substation wikipedia , lookup

Islanding wikipedia , lookup

Opto-isolator wikipedia , lookup

Rectifier wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Electrical ballast wikipedia , lookup

Electric power system wikipedia , lookup

Voltage optimisation wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Power inverter wikipedia , lookup

Power MOSFET wikipedia , lookup

Current source wikipedia , lookup

History of electric power transmission wikipedia , lookup

Three-phase electric power wikipedia , lookup

Decibel wikipedia , lookup

Power engineering wikipedia , lookup

Buck converter wikipedia , lookup

Electrification wikipedia , lookup

Mains electricity wikipedia , lookup

Audio power wikipedia , lookup

Metadyne wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Power factor wikipedia , lookup

Alternating current wikipedia , lookup

Transcript
Definition
Crest Factor
PURPOSE
DISCUSSION OF EXAMPLE
To serve as a guideline in power source selection.
The blue trace is a 5A rms sinusoid with a peak current
of 7.07A:
CREST FACTOR DEFINED
The crest factor and the peak currents of a load are
important considerations in power source selection.
Crest factor is defined as the ratio of peak value to rms
value of a current waveform:
The red trace is a non-sinusoidal waveform that is also
5A rms, but has a peak at 21.21A. The crest factor for
this example is 4.24:1. A 5A rms current would have a
peak of 7.07A for a true sine, therefore:
The crest factor for a sinusoidal current waveform, such
as that which a pure resistive load would draw, is 1.414
since the peak of a true sinusoid is 1.414 times the rms
value. However, the crest factor for a non-sinusoidal
current waveform can differ dramatically for loads that
are not power factor corrected, such as a switching
power supply or lamp ballast, which give a current
waveform that is short in duration but high in amplitude.
Since the same rms current level is drawn in both
examples, the true power provided would be the same
for both (if the voltage were held at a constant level for
both examples). This means that a power source
selected to feed the loads at 120VAC would need to
provide the 600VA that both loads require. However,
the power source rated for 600VA may not be able to
provide the required peak currents that the load
demands.
CREST FACTOR EXAMPLE
POWER SOURCE SELECTION
The following graph shows two current waveforms, one
sinusoidal and one non-sinusoidal:
The power source feeding the high crest factor load
would need to be able to support the crest factor or
have an output current that would provide this peak
level. In order to determine the ability to provide the
high crest factor peak currents you need to look for
”peak repetitive current” or “crest factor” in the data
sheet or spec sheet of a power source.
Crest Factor Example
25
C
u
r
r
e
n
t
20
As a final note, peak currents are also important in
calculating the voltage drop across conductors to
minimize voltage drops.
15
10
5
0
-5
-10
-15
-20
-25
0
90
180
270
360
Angle
AMETEK Programmable Power
9250 Brown Deer Road
San Diego, CA USA 92121-2267
Web : www.programmablepower.com
Phone : 858.458.0223
Email : [email protected]
Email : [email protected]