Download The drive may be seeing the motor acting as a generator

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Pulse-width modulation wikipedia , lookup

Power engineering wikipedia , lookup

Induction motor wikipedia , lookup

Transistor wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Power inverter wikipedia , lookup

History of electric power transmission wikipedia , lookup

Rectifier wikipedia , lookup

Ohm's law wikipedia , lookup

Three-phase electric power wikipedia , lookup

Resistor wikipedia , lookup

Electrical substation wikipedia , lookup

Islanding wikipedia , lookup

Power electronics wikipedia , lookup

Schmitt trigger wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Electrical ballast wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Opto-isolator wikipedia , lookup

Voltage regulator wikipedia , lookup

Stepper motor wikipedia , lookup

Current source wikipedia , lookup

Stray voltage wikipedia , lookup

Surge protector wikipedia , lookup

Alternating current wikipedia , lookup

Buck converter wikipedia , lookup

Distribution management system wikipedia , lookup

Fault tolerance wikipedia , lookup

Mains electricity wikipedia , lookup

Voltage optimisation wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Transcript
The drive may be seeing the motor acting as a generator and feeding a voltage back into the drive and
increasing the DC Bus voltage. Depending on the application, this regeneration may be a avoided by
increasing the decel time on ramp to stop on the inverter. Otherwise, Dynamic Braking may be needed.
Useful Definitions:
Regeneration: The characteristic of a motor when the rotor's synchronous frequency is greater than the
applied frequency.
Dynamic Braking: A system of electric braking in which the motor, when used as a generator, converts
the kinetic energy of the load into electric energy dissipated in resistors, in doing so, exerts a retarding
force on the load. Dynamic braking uses an internal transistor to switch the DC bus voltage across an
externally mounted resistor. Resistors are usually placed across the DC bus to dissipate the power
returned.

OV trip levels for all drives that apply to this FAQ?
Example:
 OV fault occurs at 800 VDC or 565 VAC on 460V models.
 OV fault occurs at 400 VDC or 283 VAC on 230V models.
 OV fault occurs at 1000VDC or 707VAC on 575V models.
To measure bus voltage, meter across DC bus terminals + bus to - bus






Possible causes with braking circuit installed
Open resistor
Defective braking transistor
Braking torque requirement exceeds drives braking circuit capacity. (decel too fast for load etc.)
If the turn-on level is improper, overvoltage may be experienced.
Verify the DC Bus indication from the drive(U1-07) is within 20 volts of that as measured with a
multimeter (obviously, the closer the indication the better, but 20 volts should be OK).

Verify the braking module is turning on at the proper level (oscilloscope is preferred):
Jumper setting
Turn-on Level
230
380V +/- 3V
220
365V +/- 3V
208
345V +/- 3V
200
330V +/- 3V
460
440
415
400
380
760V +/- 6V
730V +/- 6V
690V +/- 6V
660V +/- 6V
630V +/- 6V
Verify the braking resistor capacity can dissipate the necessary energy absorbed from the load. This must
be done with an oscilloscope. Place the O-scope across the resistor. When decelerating, voltage will
appear across the resistor (this indicates the CDBR module has turned on). When voltage appears
across the resistor, it should immediately start to decrease (voltage should decrease). If the voltage
continues to rise and/or hold steady while DB is on, the DB capacity may be insufficient to achieve the
desired deceleration rate. An additional resistor and CDBR module may be necessary.



Is the "DB On" LED illuminating at the time of a trip?
Are dual CDBR braking modules setup and wired properly (one as master and one as a slave) per
the braking manual.
Is stall prevention during decel disabled? It should only be disabled when braking circuit is not
installed

Possible causes when braking circuit is NOT installed:
 Parameter Stall Prevention during decel disabled w/o braking circuit installed.
 High line condition: Explain what AC line condition causes an OV trip on 230V ,575V models

Overall possible causes
 Poor motor parameter tuning
 Noisy encoder feedback in closed loop control causing unstable output waveform.