Download Type LG Braking Modules

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Mercury-arc valve wikipedia , lookup

Utility frequency wikipedia , lookup

Ground (electricity) wikipedia , lookup

Induction motor wikipedia , lookup

Ohm's law wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Electrification wikipedia , lookup

Electric power system wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Electrical substation wikipedia , lookup

Audio power wikipedia , lookup

Electrical ballast wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Rectifier wikipedia , lookup

Three-phase electric power wikipedia , lookup

Current source wikipedia , lookup

Stray voltage wikipedia , lookup

History of electric power transmission wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Islanding wikipedia , lookup

Power engineering wikipedia , lookup

Surge protector wikipedia , lookup

Power inverter wikipedia , lookup

Fault tolerance wikipedia , lookup

Stepper motor wikipedia , lookup

Voltage optimisation wikipedia , lookup

Opto-isolator wikipedia , lookup

Distribution management system wikipedia , lookup

Buck converter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Mains electricity wikipedia , lookup

Alternating current wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Transcript
TYPE LG BRAKING MODULES
> RATINGS AND FEATURES
AC variable frequency drives are commonly used with general purpose AC
induction motors to form reliable variable speed drive systems. Problems
with these drive systems can occur when an application requires a
deceleration rate faster than what can be managed by the drive alone, or
when motor speeds exceed the synchronous speed set by the output
frequency of the drive (which is called an overhauling load condition).
Both of these conditions create regenerated power which flows from the
motor back into the drive, causing its DC Bus to rise. To manage the
regenerated power and avoid shutting the drive down due to an overvoltage trip, this power must be dissipated by an external braking
resistor. Braking Modules are used in conjunction with an AC drive to
monitor the DC bus of the drive and activate external braking resistor as
needed.
A.C. Drive
Braking Module
W
Braking Resistor
Slave
Powerohm TypeBM
Braking Module
L1
Master
DANGER: HIGH VOLTAGE
Braking module containslethal voltageswhen
connected to the inverter. Power to the inverter must
be removed before servici ng the braking module.
Allow adequate time(approximately10 minutes) after
removing power before touching any components.
The POWERON LED must be completelyout before
servicing theunit.
L2
L3
EXTERNAL
THERMAL SWITCH
TO DRIVE LOGIC
Master - Slave
Jumper
Slave
INTERNAL
Master
Voltage Level Jumper
Brake Enable
Jumper
CLASS JP1 JP2 JP3 JP4 JP5
200
400
600
Master - Slave
Jumper
380 400 415 440 460
POWER ON (GREEN)
Fault Contact
Jumper
TURN ON LEVEL (ADJ.)
NC NO
BRAKING(GREEN)
Ext ernal
Brake Enable/
Fan Power
120VAC
FAULT (RED)
Slave
Input
+
1
2
T1
AC
MOTOR
T2
Fault
Output
3
N[DC-] P[DC+]
4
Master
Output
+
5 6
G
G
7
8
PO[1]
9
10
B[2]
T3
DC+ DC-
A typical AC Drive, Braking Module and Braking Resistor configuration.
PRODUCT OVERVIEW
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Nominal Voltage Ratings of 240, 480 and 600 volts.
Continuous Current Ratings up to 115 amps.
Peak Current Ratings as high as 300 amps.
Optional Enable Control Voltages of 120VAC or 24VDC.
Compact Frame with High Current Capacity.
Heat sink Over-temperature Protection.
Under Voltage Detection for Logic Supply.
Master/ Slave Configuration.
External or Internal Brake Enable Capability.
ELECTRICAL SPECIFICATIONS AND PART DIMENSIONS
Powerohm Nominal AC
RMS
Turn ON
Part
Line
Continuous Voltage
Number
Voltage
Current
BM2-50
240
50
390
BM2-115
240
115
390
BM2-150
240
150
390
Max Peak
Current
200
200
300
BM4-50
480
50
775
200
BM4-115
BM4-150
BM6-50
BM6-115
BM6-150
480
480
600
600
600
115
150
50
115
150
775
775
970
970
970
200
300
200
200
300
Note: Peak currents up to the maximum are allowed at
intermittent duty cycles, as long as:
· The Module RMS Load Current rating is not exceeded.
· RMS Load Current = Peak Current X the square root of duty cycle.
* The cooling fan option is necessary to achieve the 115 amp rating and requires 120VAC, or optional 24VDC Control
Power for fan.
ENVIRONMENTAL RATINGS
WEIGHTS
Ambient Temperature:
-10ºC to 40ºC
BM50 Amp Series without fan: 8 lbs.
Maximum Altitude:
3300 feet (1000m)
BM115 Amp Series with fan: 10 lbs.
Maximum Vibration:
10 to 20Hz, 32ft/sec/sec; 20 to
50Hz, 6.5 ft/sec/sec
For detailed specifications and mounting instructions, download the Type LG Installation Manual on the web at
www.powerohm.com.