Download M1 M1 Start Stop M1 motor To 3-phase power source F1 F2 OL OL

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power inverter wikipedia , lookup

Buck converter wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Voltage optimisation wikipedia , lookup

Electric power system wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Commutator (electric) wikipedia , lookup

Control system wikipedia , lookup

Electrical substation wikipedia , lookup

Fault tolerance wikipedia , lookup

Three-phase electric power wikipedia , lookup

Earthing system wikipedia , lookup

Electrification wikipedia , lookup

Power engineering wikipedia , lookup

Alternating current wikipedia , lookup

Light switch wikipedia , lookup

Electric machine wikipedia , lookup

Relay wikipedia , lookup

Switch wikipedia , lookup

Brushless DC electric motor wikipedia , lookup

Electric motor wikipedia , lookup

AC motor wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Stepper motor wikipedia , lookup

Induction motor wikipedia , lookup

Transcript
EET272 Worksheet Week 8
answer questions 1-5 in preparation for discussion for the quiz on Monday. Finish the rest of the
questions for discussion in class on Wednesday.
Questions
Question 1
We will now look at a variety of circuits to control motors. This is not an exclusive list. The goal is
to learn to read ladder diagrams and diagnose what the function of the various parts of the circuit and the
complete function is.
In our text read and outline the section on Motor Control Circuits, Mutliple Start/Stop Controls, Multiple
Motor Starter Control, Sequential Starting Control, Various starting methods, and Braking in Ch 20 of our
text (pgs 476-498)
file q0060
Question 2
A very common form of latch circuit is the simple “start-stop” relay circuit used for motor controls,
whereby a pair of momentary-contact pushbutton switches control the operation of an electric motor. In
this particular case, I show a low-voltage control circuit and a 3-phase, higher voltage motor:
To 3-phase
power source
F1
F2
480/120 V
Stop
Start
M1
OL
M1
M1
OL
motor
Explain the operation of this circuit, from the time the “Start” switch is actuated to the time the “Stop”
switch is actuated. The normally-open M1 contact shown in the low-voltage control circuit is commonly
called a seal-in contact. Explain what this contact does, and why it might be called a “seal-in” contact.
Kuphaldt file i02304
1
Question 3
Examine this motor control circuit for a start/stop/jog control:
L1
L2
Stop
Start
CR1
CR1
Jog
M1
CR1
Explain in your own words what distinguishes the “Start” function from the “Jog” function, and think
of a practical application where this might be useful.
Kuphaldt file i02459
2
Question 4
The most common method of starting up a three-phase induction motor is to simply apply full power
all at once by closing the three contacts of a large “contactor” relay. This is called across-the-line starting:
"Across the line" motor starter
motor
3-θ power
Across-the-line starting is simple, but results in huge “inrush” currents at the moment of contactor
closure, and also places a lot of mechanical and thermal stress on the motor as it rushes to attain full speed.
A “gentler” method of starting an induction motor is to place impedances in series with the three-phase
power, using two contactors (one “start” and one “run”) to sequence the motor from start-up to full-speed
run. The impedances ideally take the form of inductors (“reactors”):
Run
motor
3-θ power
Start
Explain how and why this method of starting is gentler than across-the-line starting.
Suggestions for Socratic discussion
• Would large (high-power) resistors work instead of inductors?
• Would large capacitors work instead of inductors?
Kuphaldt file i02310
3
Question 5
Examine this control circuit diagram for an air compressor, where a pair of pressure switches controls
the starting and stopping of the electric motor turning the air compressor:
Control circuit schematic
L1
L2
Cut-out switch
Hand
M
OL
Off
Auto
Control switch
Pictorial diagram of system
PS
Cut-out switch
PS
Control switch
Intake filter
Receiver tank
Compressor
Compressed air
Condensate drain valve
Explain what the “Hand-Off-Auto” switch does in this circuit, and also describe the functions of each
pressure switch.
Suggestions for Socratic discussion
• Which of these two pressure switches should have the greater trip setting, and why?
• Why do you think operations personnel might find it useful to have a “Hand” position as well as an
“Auto” position on the switch in this air compressor system?
• Some “Hand-Off-Auto” switches place the “Auto” position in the middle, between the “Hand” and the
“Off” settings – explain why this might be a better way to arrange the three-position switch.
Kuphaldt file i04056
4
Question 6
Suppose we wish to have three separate pushbutton start/stop stations for operators to use in controlling
a single three-phase electric motor. The control circuit wiring schematic shows how this will work:
L2
Fuse
Stop
Stop
L3
Start
Stop
M1
Start
Start
M1
Sketch the necessary connecting wires to build this control circuit:
L1
L2
L3
Start
Start
Start
Stop
Stop
Stop
X2
X1
H1
H3
H2
H4
Transformer
Contactor
Fuse
Motor
T1 T2 T3
Suggestions for Socratic discussion
• An overload contact has been omitted from this motor control system for simplicity’s sake. Identify
where one would be properly inserted into the schematic diagram, and also in the pictorial diagram.
Kuphaldt file i02449
5
Question 7
This motor control circuit commands three motors to start and stop together:
Power circuit
M1
Control circuit
L1
L2
Stop
Start
M1
OL1
To 3-phase
power source
motor
OL1
M2
OL2
M3
motor
M1
M2
OL2
M3
M2
M3
OL3
OL3
motor
Examine the control circuit and then explain how starting one motor starts up the others. Also,
determine what will happen if motor #3 suffers an overload (i.e. OL3 warms up enough to trip).
Suggestions for Socratic discussion
• Explain why inrush current could be a problem in this three-motor control system, and identify at least
one practical solution for it.
Kuphaldt file i02399
6
Question 8
The direction of rotation for a three-phase AC electric motor may be reverse by reversing any two of
the three power conductor connections. With this in mind, explain how this reversing motor control circuit
works:
L1
L2
Forward
M2
M1
Reverse
M1
M2
M1
To 3-phase
power source
motor
M2
In particular, what it the function of the two normally-closed “M” contacts (called interlock contacts)
in the control circuit? What do you think might happen if those contacts were not there?
Suggestions for Socratic discussion
• Explain why reversing any two phase conductors supplying AC power to an induction motor will cause
it to reverse direction.
• Explain what arc flash is, and how to protect yourself from it while working on high-voltage motor
control circuits such as this one.
Kuphaldt file i01391
7
Question 9
Large electric motors are often equipped with some form of soft-start control, which applies power
gradually instead of all at once (as in “across the line” starting). Here is an example of a simple “reduced
voltage start” control system using a time-delay relay (TD1):
L1
L2
Stop
Start
CR1
CR1
OL
TD1
M2
M1
M2
TD1
R
M1
To 3-phase
power source
OL
motor
M2
Analyze this ladder logic diagram, and explain the function of the time-delay relay, particularly how to
interpret its switch symbol (with arrowhead). How does the time-delay relay cause a soft start?
Kuphaldt file i02382
8
Question 10
The following ladder logic diagram is for a reversing motor control circuit:
L1
L2
Stop
Forward
M2
M1
M1
M2
OL
M1
Reverse
M2
M1
To 3-phase
power source
OL
motor
M2
Study this diagram, then explain how motor reversal is accomplished. Also, identify the function of
each ”M” contact in the control circuit, especially those normally-closed contacts in series with the motor
starter coils.
9
Now consider the following modification made to the reversing motor control circuit (motor and power
contacts not shown here):
L1
L2
Stop
Forward
TD2
M2
M1
Reverse
M1
OL
TD1
TD1
M1
M2
M2
TD2
What extra functionality do the time-delay relays contribute to this motor control circuit?
Kuphaldt file i02496
10
Question 11
This motor-control “bucket” has a problem: the motor refuses to start when the “Start” pushbutton is
pressed. A voltmeter connected to test points C and E indicates 118 volts AC with no pushbuttons pressed:
To 3-phase
power source
F1
B
A
480/120 V
Start
Stop
C
D
M1
F
F2
OL
E
M1
M1
OL
motor
Identify the likelihood of each specified fault for this circuit. Consider each fault one at a time (i.e. no
multiple faults), determining whether or not each fault could independently account for all measurements
and symptoms in this circuit.
Fault
Fuse F1 blown
Fuse F2 blown
Start switch failed open
Stop switch failed open
M1 coil failed open
M1 auxiliary contact failed open
M1 power contact(s) failed open
OL contact failed open
Start switch failed shorted
Stop switch failed shorted
Transformer secondary failed shorted
Possible
Impossible
Finally, identify the next diagnostic test or measurement you would make on this system. Explain how
the result(s) of this next test or measurement help further identify the location and/or nature of the fault.
Kuphaldt file i02398
11
Question 12
An interesting way to achieve reduced-voltage starting for a three-phase motor is to use a 6-lead
motor where the three stator winding sets are individually wired so as to allow either wye (start) or delta
configurations:
Wye connection
6-lead, 3-phase motor
1
4
5
6
1
2
3
Delta connection
6
1
4
6
5
3
4
5
3
2
2
A “Start” contactor sends power to the stator windings in a wye configuration for a short start-up time
(perhaps 10 seconds), then that starter disengages and a “Run” starter energizes to send power to the stator
windings in a delta configuration. In the “wye” configuration, each winding receives √13 of the line voltage.
In the “delta” configuration, each winding receives the full line voltage.
Sketch the proper wire connections to create just such a “wye-delta” motor starter. Hint: terminals 1,
2, and 3 of the motor always connect to the three-phase power lines!
Start
Motor
Fuses
To three-phase
power source
Run
1
4
2
5
3
6
Suggestions for Socratic discussion
• Explain the purpose of using reduced-voltage starting for a large electric motor.
Kuphaldt file i03870
12
Question 13
Synchronous AC motors by their nature rotate at precisely the same speed as the rotating magnetic
field produced by the stator windings. The practical problem with this is how to get a synchronous motor
started, since it is physically impossible for the rotor to jump from a stand-still to 100% speed in zero time.
Therefore, synchronous motors are usually started as regular induction motors at first, and then they
are switched to synchronous mode when their speed is very near 100%. The following control circuit shows
one scheme for this dual-mode start-up. The rotor on this synchronous motor has its own winding:
Three-phase synchronous motor
OL
M
Line power
Stator windings
Run
125 VDC
+
−
Start
Rotor winding
Control circuit wiring
L1
L2
Stop
Start
OL
M
M
F
Run
Start
Explain how this start-up circuit functions, and what goes on with the switching of the rotor winding
to make the motor start up and then run in two different modes.
Suggestions for Socratic discussion
• What practical applications might warrant the use of a synchronous AC motor instead of an induction
AC motor?
Kuphaldt file i03758
13
Question 14
There are three basic types of braking control circuits. They are coasting, plugging, and dynamic
braking. Explain each one in your own words. What are some advantages and disadvantages of each type
of braking circuit?
Suggestions for Socratic discussion
• Many electric cars are able to recharge their batteries when the brakes are applied. They call this
regenerative braking. Explain how this works.
file q0061
14
Question 15
Expalin how this control circuit works. What is the function of TD1?
L1
L2
Stop
Start
M2
M1
OL
M1
M1
TD1
M1
TD1
M1
To 3-phase
power source
M2
OL
motor
M2
Suggestions for Socratic discussion
• If you are unsure how long the delay of TD1 should be. Decide if you would rather error on the side of
too short or too long. Explain why you chose the way you did.
file q0062
15
Question 16
Examine this three-phase motor control circuit (sometimes referred to as a “bucket”), where fuses protect
against overcurrent faults, a three-pole relay (called a contactor) turns power on and off to the motor, and
a set of overload heaters detect mild overcurrent conditions. Control circuit wiring has been omitted for
simplicity’s sake. Only the power wiring is shown:
Line 1
Fuse
Line 2
Fuse
Line 3
Schematic
diagram
Fuse
Fuses
1
2
3
1
2
3
OL’s
motor
Motor
3
1
2
3
1
2
3
2
1
Shaft
Contactor
Overload
block
Reset
After years of faithful service, one day this motor refuses to start. It makes a “humming” sound when the
contactor is energized (relay contacts close), but it does not turn. A mechanic checks it out and determines
that the shaft is not seized, but is free to turn. The problem must be electrical in nature!
16
You are called to investigate. Using a clamp-on ammeter, you measure the current through each of
the lines (immediately after each fuse) as another start is once again attempted. You then record the three
current measurements:
Line
1
2
3
Current
52.7 amps
51.9 amps
0 amps
Determine at least two possible faults, either one fully capable of causing the motor’s refusal to start
and the three current measurements taken. Then, decide what your next measurement(s) will be to isolate
the exact location and nature of the fault.
Suggestions for Socratic discussion
• Is there a way we could have determined a lack of current in line 3 without the use of a clamp-on
ammeter, using a multimeter incapable of directly measuring current over 10 amps?
Kuphaldt file i01445
17
Question 17
This “lift station” pump control circuit has a problem. The sump pump is supposed to come on when
the high level is reached, and turn off when the water pumps down to the low level point. Instead, however,
the motor “cycles” on and off at the low-level point. Using an AC voltmeter, you measure a voltage from
point B to point D that switches back and forth between 120 volts and 0 volts:
M1
OL
To 3-phase
AC power
(480 V)
motor
F1
F2
H2
H1
H3
H4
F3
C
120 VAC
A
LSH
B
LSL
M1
D
OL
E
M1
F
G
Identify the likelihood of each specified fault for this circuit. Consider each fault one at a time (i.e. no
multiple faults), determining whether or not each fault could independently account for all measurements
and symptoms in this circuit.
Fault
High level switch failed open
Low level switch failed open
Broken wire between D and M1 coil
Contactor auxiliary contact failed open
Contactor auxiliary contact failed shorted
Contactor main contact(s) failed open
Broken wire between B and G
Thermal overload unit tripped
High level switch failed shorted
Transformer secondary winding failed open
Possible
Impossible
Finally, identify the next diagnostic test or measurement you would make on this system. Explain how
the result(s) of this next test or measurement help further identify the location and/or nature of the fault.
Kuphaldt file i04018
18
Answers
Answer 1
Answer 2
Even though the “Start” and “Stop” switches are momentary, the “seal-in” contact makes the circuit
latch in one of two states: either motor energized or motor de-energized.
Answer 3
The “Start” function is latching, whereas the “Jog” function is not. A common application of this
concept is in a kitchen blender, where one button starts (and latches) the blender, while another simply
“pulses” the blender.
Answer 4
The “Start” contactor must be energized first, then at a later time is de-energized as the “Run” contactor
is simultaneously energized. Either timing relays or a PLC handles this sequencing of contactors.
Answer 5
Both pressure switches are normally closed and open when a specified pressure is reached.
Answer 6
L1
L2
L3
Start
Start
Start
Stop
Stop
Stop
X2
X1
H1
H3
H2
H4
Transformer
Fuse
Motor
T1 T2 T3
Answer 7
19
Answer 8
The normally-closed contacts are referred to as interlock contacts, and they prevent simultaneous forward
and reverse actuation of the motor.
Answer 9
For starting M1 should be closed and the resistors limit the motor current. During normal running M2
is closed and M1 is open. This applies full voltage to the motor.
Remember that time-delay relay symbols always use an arrowhead at the switch contact to denote the
direction of timing. With this switch, the arrowhead points in the closed direction, which means the relay
takes time to close. Being normally-open, this means the delay happens upon energization of the relay coil,
the implication being that the relay will return to its normal (open) state immediately upon de-energization.
Answer 10
The normally-open and normally-closed ”M” contacts provide seal-in and interlock functions,
respectively. The time-delay relays prevent the motor from being immediately reversed.
Answer 11
Fault
Fuse F1 blown
Fuse F2 blown
Start switch failed open
Stop switch failed open
M1 coil failed open
M1 auxiliary contact failed open
M1 power contact(s) failed open
OL contact failed open
Start switch failed shorted
Stop switch failed shorted
Transformer secondary failed shorted
20
Possible
√
√
√
Impossible
√
√
√
√
√
√
√
√
Answer 12
Start
Motor
Fuses
To three-phase
power source
Run
1
4
2
5
3
6
Answer 13
In the start-up mode, the motor’s rotor winding is short-circuited by the “Start” contact. This makes
the motor behave like a normal squirrel-cage induction motor with its rotor bars and shorting rings.
As soon as the speed switch detects adequate rotor speed, the “Start” coil de-energizes and the “Run”
coil energizes, connecting the rotor winding directly to a DC power source to magnetize it and lock it into
synchronous mode.
Answer 14
Coasting takes the longest to stop a motor. Plugging is faster but can be hard on the motor. Sometimes
plugging is pulsed on an off if you have digital control. Dynamic Braking is the fastest but also the most
complictated.
Answer 15
TD1 is involved in a braking of the motor. Be sure to explain the type of braking
Answer 16
Here are some possibilities:
•
•
•
•
Fuse #3 blown open
Third relay contact damaged (failed open) inside the contactor
Overload heater #3 failed open
One winding failed open inside the motor (assuming a “Y” winding configuration)
There are several valid “next steps” you could take from this point. Discuss alternatives with your
classmates.
21
Answer 17
Partial answer:
Fault
High level switch failed open
Low level switch failed open
Broken wire between D and M1 coil
Contactor auxiliary contact failed open
Contactor auxiliary contact failed shorted
Contactor main contact(s) failed open
Broken wire between B and G
Thermal overload unit tripped
High level switch failed shorted
Transformer secondary winding failed open
22
Possible
Impossible
√
√
√
√