ELECTRICAL HAZARDS
1
ELECTRICAL HAZARDS
• SHOCK. Electric shock occurs when the
human body becomes part of the path
through which current flows.
• The direct result can be electrocution.
• The indirect result can be injury
resulting from a fall or movement into
machinery because of a shock
www.IndTraining.com
2
ELECTRICAL HAZARDS
• BURNS. Burns can result when a person
touches electrical wiring or equipment that is
energized.
• ARC-BLAST. Arc-blasts occur from highamperage currents arcing through the air.
This can be caused by accidental contact with
energized components or equipment failure.
www.IndTraining.com
3
ELECTRICAL HAZARDS
• ARC-BLAST. The three primary
hazards associated with an arc-blast are:
• Thermal radiation.
• Pressure Wave.
• Projectiles.
www.IndTraining.com
4
ELECTRICAL HAZARDS
• EXPLOSIONS. Explosions occur when
electricity provides a source of ignition
for an explosive mixture in the
atmosphere.
www.IndTraining.com
5
ELECTRICAL HAZARDS
• FIRES. Electricity is one of the most
common causes of fires both in the home
and in the workplace. Defective or
misused electrical equipment is a major
cause.
www.IndTraining.com
6
EFFECTS ON THE
HUMAN BODY
Depends on:
Current and Voltage
Resistance
Path through body
Duration of shock
www.IndTraining.com
7
Effects of AC Electricity
• More than 3 mA- Painful shock- cause
indirect accident
• More than 10 mA- Muscle contraction –
“No Let Go” danger
• More than 30 mA- Lung paralysis, usually
temporary
www.IndTraining.com
8
Effects of AC Electricity
• More than 50 mA- Ventricular fibrillation,
usually fatal
• 100 mA to 4 A- Certain ventricular
fibrillation, fatal
• Over 4 A- Heart paralysis, severe burns
www.IndTraining.com
9
1910.303(b)
Examination of equipment
• Electrical equipment must be free of
recognized hazards that are likely to cause
death or serious physical harm to
employees.
www.IndTraining.com
10
1910.303(b)
Examination of equipment
Safety of equipment must be determined using
the following considerations:
Suitability for installation and use
Mechanical strength and durability
Electrical insulation
Heating effects under conditions of use
www.IndTraining.com
11
1910.303(b)
Examination of equipment
Safety of equipment must be determined using
the following considerations:
• Arcing effects
• Classification by type, size, voltage, current
capacity and specific use
• Other factors
www.IndTraining.com
12
1910.303(c)
Splices
Conductors must be spliced with:
Splicing devices suitable for the use
Brazing, welding or soldering (with a
mechanically and electrically secure joint
before soldering & then soldered)
www.IndTraining.com
13
1910.303(c)
Splices
All splices and joints and the free ends of
conductors must be covered with an
insulation equivalent to that of the
conductors or with an insulating device
suitable for the purpose.
www.IndTraining.com
14
1910.303(e)
Marking
Electrical equipment may not be used
unless the manufacturer’s name, trademark
or other identification is on the equipment.
www.IndTraining.com
15
1910.303(e)
Marking
• Other markings must be provided giving
voltage, current, wattage, or other ratings as
necessary.
• Markings must be durable enough to
withstand the environment.
www.IndTraining.com
16
1910.303(f)
Identification
Each disconnecting means must be legibly
marked to indicate its purpose, unless
located and arranged so that its purpose is
evident.
www.IndTraining.com
17
1910.303(f)
Identification
These markings must be durable enough to
withstand their environment.
www.IndTraining.com
18
1910.303(g)(1)
600 volts, nominal, or less
Working space about electrical equipment.
This section refers to a person qualified to
work on electrical equipment, usually an
electrician.
www.IndTraining.com
19
1910.303(g)(1)(i)
Working clearances
• Except as required or permitted, the
dimension of the working space in front of
live parts (operating at 600 volts or less)
and likely to require examination,
adjustment, servicing, or maintenance must
be at least three feet.(See table S-1).
www.IndTraining.com
20
1910.303(g)(1)(i)
Working clearances
• The workspace in front of electrical
equipment must not be less than 30 inches
wide.
www.IndTraining.com
21
1910.303(g)(1)(ii)
Working clearances
• Working spaces required for this standard
may not be used for storage.
www.IndTraining.com
22
1910.303(g)(2)
600 Volts or less
Guarding of live parts operating at 50 Volts or
more.
The purpose of this requirement is to
protect any person who is in the vicinity of
electrical equipment against accidental
contact, not just electricians.
www.IndTraining.com
23
1910.303(g)(2)
600 Volts or less
Guarding of live parts.
(i) Guard against accidental contact by:
(A) Location accessible only to qualified
persons
(B) Permanent, substantial partitions or
screens
www.IndTraining.com
24
1910.303(g)(2)
600 Volts or less
Guarding of live parts.
(i) Guard against accidental contact by:
(C) Location on a suitable elevated balcony or
platform
(D) Elevation of 8 feet or more above the
floor or other working surface
www.IndTraining.com
25
1910.303(g)(2)
600 Volts or less
Guardian of live parts.
In locations where electrical equipment
would be exposed to physical damage,
enclosures or guardians must be so arranged
and of such strength as to prevent such
damage.
www.IndTraining.com
26
1910.303(h)(3)
Over 600 Volts
Workspace around equipment.
Sufficient space must be provided and
maintained around electrical equipment to
permit ready and safe operation and
maintenance.
www.IndTraining.com
27
1910.303(h)(3)(ii)
Illumination (Over 600 Volts)
• Adequate illumination must be provided for
all working spaces around electrical
equipment.
• The lights and switches must be arranged so
that persons making repairs or turning on
lights wont contact live ports.
www.IndTraining.com
28
1910.303(h)(3)(
Elevation of unguarded live pa
• Unguarded live parts above working space
must be maintained at elevations not less
than specified in Table S-3.
• The minimum is 8 feet.
www.IndTraining.com
29
1910.30
Grounded and grounding condu
(1) Identification of conductors.
The grounded conductor is an energized
circuit conductor that is connected to earth
through the system ground. It is
commonly referred to as the neutral.
www.IndTraining.com
30
1910.304(a
Grounded and grounding conductors
(1) Identification of conductors.
The equipment grounding conductor is not an
energized conductor under normal
conditions. It is energized only if there is a
leak or fault in the normal current path and
directs current back to the source.
www.IndTraining.com
31
1910.304
Grounded and grounding conduc
(1) Identification of conductors.
The National Electric Code requires that:
The grounded conductor (neutral) be
continuous white or natural gray.
The equipment grounding conductor be
green, green with yellow stripes or bare.
www.IndTraining.com
32
1910.304(a)(2)
Polarity of connections
No grounded conductor may be attached to
any terminal or lead so as to reverse
designated polarity.
www.IndTraining.com
33
1910.304(a)(2)
Polarity of connections
Reversed polarity is a condition when neutral
conductor is incorrectly connected to the
“hot” terminal of a plug, receptacle or other
connector.
www.IndTraining.com
34
1910.304(e)
Overcurrent protection
(1) 600 volts or less.
(i) Conductors and equipment must be
protected from overcurrent.
www.IndTraining.com
35
1910.304(e)
Overcurrent protection
(1) 600 volts or less.
Fuses and circuit breakers are designed to
disconnect a circuit from its supply source
when a maximum allowable heat is
reached.
www.IndTraining.com
36
1910.304(e)
Overcurrent protection
(1) 600 volts or less
(iv) Location. Overcurrent devices must be
readily accessible but not located where
they will be exposed to physical damage
or in the vicinity of easily ignitable
material.
www.IndTraining.com
37
1910.304(f)
Grounding
(4) Grounding path.
The path to ground from circuits, equipment,
and enclosures must be permanent and
continuous
www.IndTraining.com
38
1910.304(f)
Grounding
(5)(v) Tools likely to be used in wet and
conductive locations need not be grounded
if supplied through an isolating transformer
with an ungrounded secondary of not over
50 volts.
www.IndTraining.com
39
1910.304(f)
Grounding
(5)(v) Listed or labeled portable tools and
appliances protected by an approved system
of double insulation, or its equivalent, need
not be grounded. However, they must be
distinctively marked.
www.IndTraining.com
40
Electrical Tools
Double Insulated
•
•
•
•
They work with GFCIs
Casing must be labeled
Tool must be inspected
Extension cord must be three-prong
www.IndTraining.com
41
1910.305
(a)Wiring methods.
(1) General requirements.
(ii) No wiring system of any type shall be in
ducts used to transport dust, loose stock or
flammable vapors, or used for vapor
removal or ventilation of commercial-type
cooking equipment.
www.IndTraining.com
42
1910.305
(a)Wiring methods.
(2) Temporary wiring.
Temporary electrical power and lighting
wiring may be of a class less than would be
required for a permanent installation.
www.IndTraining.com
43
1910.305
(a)Wiring methods.
(2) Temporary wiring.
(i) Uses permitted, 600 volts or less.
(A) During and for remodeling, maintenance
repair, or demolition or similar activities.
www.IndTraining.com
44
1910.305
(a)Wiring methods.
(i)Uses permitted, 600 volts or less.
(B) For experimental or developmental work
(C) For a period not to exceed 90 days for
Christmas decorative lighting, carnivals,
and similar purposes.
www.IndTraining.com
45
1910.305
(a)Wiring methods.
(2) Temporary wiring.
(i) Uses permitted, over 600 volts.
Only during tests, experiments and
emergencies.
www.IndTraining.com
46
1910.305
(a)Wiring methods.
(F) Lamps for general illumination must be
protected from accidental contact or
breakage.
Protection can be provided by an elevation of
7 feet or by a suitable fixture with a guard.
www.IndTraining.com
47
1910.305
(a)Wiring methods.
(G) Flexible cords and cables must be
protected from accidental damage.Sharp
corners or projections must be avoided.
Protection must be provided when passing
through doorways or other pinch points.
www.IndTraining.com
48
1910.305(b)(
Conductors entering boxe
cabinets, or fitting
• Conductors entering boxes, cabinets, or
fittings must be protected from abrasion.
• Unused openings in cabinets, boxes, and
fittings must be effectively closed.
www.IndTraining.com
49
1910.305(b)(2)
Electrical box covers
• All pull boxes, junction boxes, and fittings
must be provided with approved covers.
• Metal covers must be grounded.
www.IndTraining.com
50
1910.305(b)(2)
Electrical box covers
• Outlet boxes must have a cover or a
faceplate.
• Outlet box covers with holes for flexible
cords must bushings or smooth, wellrounded surfaces.
www.IndTraining.com
51
1910.30
(d)Switchboards and panelboards
• Panelboards must be mounted in approved
cabinets or boxes and must be dead front.
• Others are accessible only to qualified
persons.
www.IndTraining.com
52
1910.305(g)(1)(i)
Flexible cords and cables.
Allowed uses:
Pendants
Wiring fixtures
Portable lamps or appliances
Elevator cables
Wiring cranes or hoists
www.IndTraining.com
53
1910.305(g)(1)(i)
Flexible cords and cables.
Allowed uses:
Connect stationary equipment to facilitate
frequent interchange
Prevent transmission of noise or vibration
For removal for maintenance/repair
www.IndTraining.com
54
1910.305(g)(1)(iii)
Flexible cords and cables.
May not be used:
As a substitute for the fixed wiring of a
structure.
Where run through holes in walls, ceilings
or floors.
www.IndTraining.com
55
1910.305(g)(1)(iii)
Flexible cords and cables.
May not be used:
Where run through doorways, windows, or
similar openings
Where attached to building surfaces
Where concealed behind building walls,
ceilings, or floors.
www.IndTraining.com
56
1910.305(g)(2)
Flexible cords and cables.
(ii) Flexible cords must be used only in
continuous lengths without splice or tap.
www.IndTraining.com
57
1910.305(g)(2)
Flexible cords and cables.
(ii) Hard service flex cords, No. 12 or larger,
may be repaired if spliced so that the splice
retains the insulation, outer sheath
properties, and usage characteristics of the
original cord.
www.IndTraining.com
58
1910.305(g)(2)
Flexible cords and cables.
(iii) Flexible cords must be connected to
devices and fittings so that strain relief is
provided which will prevent pull off from
being directly transmitted to joints or
terminal screws.
www.IndTraining.com
59
1910.305(j)
Equipment for general use.
(2)(ii) A receptacle installed in a wet or damp
location must be suitable for the location.
www.IndTraining.com
60
1910.307
Hazardous (classified) locations.
(b) Electrical installations.
Equipment, wiring, and installations of
equipment in hazardous (classified)
locations must be intrinsically safe,
approved for the location, or safe for the
location.
www.IndTraining.com
61
Hazardous Locations
Class I locations
• Locations in which flammable gasses or
vapors are or may be present in the air in
quantities sufficient to produce explosive or
ignitable mixtures.
www.IndTraining.com
62
Hazardous Locations
Class I, Division 1
Location in which hazardous concentrations
of flammable gases or vapors may exist:
(a) Under normal operating conditions
(b) Because of repair or maintenance
operations or leakage
(c) Because of breakdown or faulty operation
www.IndTraining.com
63
Hazardous Locations
Class I, Division 2
Location in which flammable gases or vapors are:
(a) Normally confined within closed containers or
systems
(b) Normally kept below hazardous concentrations
by ventilation
(c) Normally kept below hazardous concentrations
by positive-pressure ventilation (adjacent to
Division 1)
www.IndTraining.com
64
Hazardous Locations
Class II Locations
Locations which are hazardous because of the
presence of combustible dust.
www.IndTraining.com
65
Hazardous Locations
Class II, Division 1
Location where combustible dust may be
present due to:
(a) Normal operations
(b) Mechanical failure or abnormal operation
of machinery or equipment
(c) combustible dust of an electrically
conductive nature may be present.
www.IndTraining.com
66
Hazardous Locations
Class II, Division 2
Location where:
(a) Combustible dust will not normally be in
suspension in ignitable quantities
(b) Dusts may be in suspension as a result of
an infrequent malfunction of handling or
processing equipment.
www.IndTraining.com
67
Hazardous Locations
Class III Locations
Locations that are hazardous because of the
presence of easily ignitable fibers or flyings
but in which such fibers or flyings are not
likely to be in suspension in the air in
quantities sufficient to produce ignitable
mixtures.
www.IndTraining.com
68
Hazardous Locations
Class III, Division 1
Locations in which easily ignitable fibers or
materials producing combustible flyings are
handled, manufactured or used.
www.IndTraining.com
69
Hazardous Locations
Class III, Division 2
Location in which easily ignitable fibers are
stored or handled, except in the process of
manufacture.
www.IndTraining.com
70
1910.331 - .335
Electrical Safe Work Practices
Covers work practices rather than electrical
equipment and installations.
This should be a part of your Lockout/Tagout
program
www.IndTraining.com
71
Electrical Protective Equipment
29 CFR1910.137 (59 FR 4435)
(a) Design Requirements
(b) In-service Care and Use
www.IndTraining.com
72
Electrical Protective Equipment
29 CFR1910.137 (59 FR 4435)
(a)Design Requirements
Insulating blankets,matting, covers, line hose,
gloves, and sleeves made of rubber shall
meet specified requirements for
manufacture, marking, electrical properties,
workmanship and finish.
www.IndTraining.com
73
(b) In-service Care and Use
• Electrical protective equipment shall be
maintained in a safe, reliable condition.
• Specific requirements for in-service care
and use are given for insulating blankets,
covers, line hose, gloves, and sleeves made
of rubber.
www.IndTraining.com
74
Qualified Employee
(Qualified Person)
One knowledgeable in the construction and
operation of the electric power generation,
transmission, and distribution equipment
involved, along with the associated hazards.
www.IndTraining.com
75
Qualified Employee
(Qualified Person)
• Must have the training required by
paragraph(a)(2)(ii).
• Has undergone on-the-job training and has
demonstrated an ability to perform duties
safely under the direct supervision of a
qualified person.
www.IndTraining.com
76
One employee was
climbing a metal
ladder to hand an
electric drill to the
journey installer on a
scaffold about five
feet above him. When
the victim reached
the third rung from
the bottom of the
ladder he received an
electric shock that
killed him.
www.IndTraining.com
77
The employee was attempting to correct an electrical problem
involving two non-operational lamps. He proceeded to the area
where he thought the problem was. He had not shut off the power at
the circuit breaker panel nor had he tested the wires to see if they
were live. He was electrocuted when he grabbed the two live wires
with his left hand and then fell from the ladder.
www.IndTraining.com
78
Review
• What are Electrical Hazards?
• Why is it important to examine equipment?
• How do we identity Electrical Hazards?
www.IndTraining.com
79
The material presented in this slide show
presentation is for reference purposes only.
In no way is the material in substitution for
any federal or state regulation.
www.IndTraining.com
80